Regency P40-NG, P40-LP installation manual Unit Installation with Horizontal Termination

Page 21

INSTALLATION

UNIT INSTALLATION WITH HORIZONTAL TERMINATION

(Rigid Vent Systems)

Install the vent system according to the manufacturer's instructions included with the components.

1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.

2)DirectVentpipeandfittingsaredesignedwith special twist-lock connections to connect the venting system to the appliance fl ue outlet. A twist-lock appliance adaptor is required.

3)In conjunction with the Simpson Dura-Vent Direct Vent GS system. Install the adaptor after the unit is set in its desired location. Put a bead of high temperature silicone inside the outer section of the adapter and a bead of Mill Pack on the inner collar. Slip the adapter over the existing inner and outer flue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).

4)Levelthefireplaceandfastenittotheframing using nails or screws through the top and side nailing strips.

5)Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

Note: Apply sealant "Mill-Pac" to inner pipe and high temp silicone sealant to outer pipe on every twist-lock joint.

Diagram 1

Horizontalrunsofventmustbesupported every 3 feet (0.9meter). Wall straps are available for this purpose.

6)Mark the wall for a 11" x 11" (279mm x 279mm) square hole. The center of the square hole should line up with the center- line of the horizontal pipe. Cut and frame the 11 inch (279mm) square hole in the exterior wall where the vent will be terminated. See diagram 2 for center line requirements.

If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, an 8" (203mm) diameter hole is acceptable.

Diagram 2

Note:

a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.

The arrow on the vent cap should be pointing up.

b)The location of the horizontal vent terminationonanexteriorwallmustmeet all local and national building codes, and must not be blocked or obstructed. See "Exterior Vent Termination Locations"

7)Insurethatthe1-1/4"(32mm)pipeclearances to combustible materials are maintained (Diagram 5). Install the termination cap.

Note: If installing termination on a vinyl siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.

Diagram 5

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

8)Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 1247) over the vent pipe, required in Canada.

9)Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32mm).Secure theconnectionbetweenthe vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.

Diagram 6

10)Install wall thimble in the center of the 11" (279mm) square and attach with wood screws (Diagram 7).

INSTALLATION

Diagram 7

Regency® P40 Direct Vent Gas Fireplace

21

Image 21
Contents P40 Gas Fireplace Information for MOBILE/MANUFACTURED Homes After First Sale Manufactured Mobile Home RequirementsTable of Contents Copy of Safety Label Safety LabelMA Code CO Detector RequirementsUnit Dimensions General Safety Information InstallationInstallation Checklist Important Message Save These InstructionsHeat Release KIT Manufactured Mobile Home Additional RequirementsHearth Requirements Locating Your GAS FireplaceClearances Mantel LEG Clearances Mantel ClearancesHeight = 42-1/2 plus height of hearth Framing & FinishingVenting Introduction Unit Assembly Prior to InstallationVent Restrictor Position ScrewExterior Vent Termination Requirements InstallationHorizontal Termination Flex Venting ArrangementsBasic Horizontal & Vertical Terminations Rigid Pipe Venting SystemsRigid Pipe Adaptor Must use with all Rigid Piping Rigid Pipe Venting Components ListVertical Height Feet Allowable Horizontal TerminationsHorizontal Venting with Two 2 90o Elbows Vertical Venting with Two 2 90o Elbows Vent must be supported at offsets Allowable Vertical TerminationsArrow on the vent cap should be pointing up Unit Installation with Horizontal TerminationThis allows for small adjustments Unit Installation With Vertical TerminationDiagram Minimum VentAstrocap XL Dimensions Unit InstallationPilot Adjustment GAS Line InstallationHigh Elevation P40-NG System DataBACK-UP Battery Installation GAS Pipe Pressure TestingUnplug the power source Power ModuleLP Conversion Kit Contains Qty Description Conversion KIT #502-969 from NG to LPControl Module Ensure that the logs are not in the unit Brick Panel InstallationTop Brick Panel Back Brick PanelEmber Bed LOG SET InstallationEmber Bed Completed Log Set Installation Installing the Manual Control Box Aeration AdjustmentStandard Flush Door Flush LouversWiring Diagram Finishing TrimDo not cut the ground terminal off under any circumstances Operating Instructions Lightingshutdown Procedure ProcedureOperating Instructions First FireOperation During Power Outage Firewizardtm Remote Control FunctionsSummary Controls Copy Lighting Plate Instructions Normal Operating Sounds GAS AppliancesMaintenance Control Module FAN ReplacementFender Valve ReplacementBack Burner Solenoid Valve Front Air BoxDC Sparker Replacement Control Module Replacement Power Module ReplacementBackup Battery Replacement Heat ShieldParts List Main AssemblyDescription Valve Tray Assembly Flush Door & Louvers Regency P40 Direct Vent Gas Fireplace Regency P40 Direct Vent Gas Fireplace Warranty Limited Lifetime WarrantyInstaller Please complete the following information

P40, P40-LP, P40-NG specifications

The Regency P40 series, comprising the P40-LP, P40, and P40-NG models, represents a significant advancement in the world of portable radio communications. Designed with both versatility and performance in mind, these devices cater to a diverse range of users, from public safety professionals to outdoor enthusiasts.

One of the standout features of the P40 series is its robust build quality. The radios are engineered to withstand harsh environments, boasting IP67 water and dust resistance ratings. This ensures reliable performance even in challenging conditions, making them ideal for emergency responders who operate in adverse weather or rugged terrains. The P40's durable design is complemented by a lightweight construction, allowing for prolonged use without fatigue.

The P40 series is equipped with advanced digital technology that enhances both audio clarity and range. With a powerful speaker and noise-canceling capabilities, users can communicate clearly even in noisy surroundings. The P40-NG model takes this a step further by incorporating digital signal processing (DSP) technology, which optimizes sound for both transmission and reception.

Battery life is a critical aspect of any portable device, and the P40 series excels in this regard. With options for high-capacity lithium-ion batteries, users can expect extended operational times, vital for those on long shifts or field operations. Additionally, the smart battery management system provides real-time battery status updates, ensuring users are never caught off guard.

Interoperability is another key characteristic of the P40 series. The radios support multiple frequency bands and can seamlessly integrate with existing communication infrastructures. This capability is particularly beneficial for agencies that require coordination across various channels and networks.

User-friendly interfaces define the P40 series, with intuitive controls and customizable features. The color display on the P40 and P40-NG models enhances usability, allowing for easy navigation through settings and features. Furthermore, programmable buttons facilitate quick access to frequently used functions, ensuring efficient communication even in high-pressure scenarios.

Overall, the Regency P40-LP, P40, and P40-NG radios embody reliability, advanced technology, and ruggedness, making them essential tools for effective communication in a variety of demanding environments. With their combination of durability, audio performance, and battery life, these radios stand out as a top choice for both professional and recreational use.