Reliance Water Heaters 196296-001, 606 Series instruction manual GAS Piping

Page 18

FIGURE 28.

There must be a minimum of 6” (153 mm) clearance between single wall vent pipe and any combustible material. Fill and seal any clearance between single wall vent pipe and combustible material with mortar mix, cement, or other noncombustible substance. For other than single wall, follow vent pipe manufacturer’s clearance specifications. To insure a tight fit of the vent pipe in a brick chimney, seal around the vent pipe with mortar mix cement.

Failure to have required clearances between vent piping and combustible material will result in a fire hazard.

Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation.

Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

GAS PIPING

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (2.6 kPa) for natural and propane (L.P.) gas. If the gas control valve is subjected to pressures exceeding 1/2 pound per square inch (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also turn “off” the gas at each appliance. Leave all gas appliances shut off until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54 and your gas supplier concerning pipe size.

There must be:

A readily accessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

The minimum inlet gas pressure shown on the rating plate is that which will permit firing at the rated input.

Standard Models are for installation up to 2,000 feet (610 m) above sea level.

High Altitude models are for installation from 2,000 feet (610 m) to 4,500 feet (1,370 m) above sea level.

18

Image 18
Contents Residential GAS Water Heaters Safe INSTALLATION, USE and Service Important DefinitionsGeneral Safety Table of Contents IntroductionTypical Installation GET to Know Your Water Heater GAS ModelsMixing Valve Usage Removing the OLD Water Heater Deciding on the Type of Installation Materials and Basic Tools NeededLocating the NEW Water Heater Facts to Consider about the LocationInsulation Blankets ALL AIR from Inside Buildings See Figures 10 Page Installing the NEW Water Heater Section a Galvanized PipingSection B Copper Sweat Piping Page TEMPERATURE-PRESSURE Relief Valve Filling the Water Heater VentingGAS Piping GAS Piping with Flexible Connector Sediment TrapsFor Your Safety Read Before Lighting For Your Safety Read Before Lighting Start UP Conditions Temperature RegulationFor Your Information Draft Hood OperationStrange Sounds Smoke / OdorThermal Expansion Smelly WaterVenting System Inspection Periodic MaintenanceHigh Water Temperature Shut OFF System Burner InspectionHousekeeping Burner CleaningTEMPERATURE-PRESSURE Relief Valve Operation Anode ROD InspectionDrain Valve Washer Replacement ServiceLeakage Checkpoints Troubleshooting Guidelines Problem Cause SolutionRepair Parts List Drain PANT&P Relief Valve Service and Labor Responsibility Model SeriesConditions and Exceptions Limitation on Implied Warranties Claim ProcedureInstallation Information DisclaimersLindahl Parkway Ashland City, TN