Sierra Monitor Corporation 4501-XX, 4501-04, 4501-06, 4501-05 Installation, 20mA Connection, Page

Page 10
4. INSTALLATION

Model 4501-XX Toxic Gas Sensor Module

4. INSTALLATION

4.1SENSOR MODULE LOCATIONS

The gas sensor module utilizes a diffusion type sensor which should be located close to either the expected source or destination of the gas hazard. If the gas is heavier than air, the sensor module should be installed within 24 inches of the ground or floor. If it is lighter than air, move it above 6’.

After optimum locations are determined based on the above recommendations, consideration should be given to placing the sensor modules in locations which are accessible for calibration service. Slight adjustments to the location of the sensor module may have little impact on effectiveness but major effect on accessibility.

Modules should be placed in areas accessible for calibration.

The cover should face out from the wall for easy access.

Sensors should be pointed down and the conduit should include an inverse trap to reduce moisture (condensation) from accumulating in the electronics enclosure.

4.2WIRING

Wire should be 16 AWG minimum at a maximum distance is 5,000 feet. Install conduit as required by local code or construction specifications.

See figure 4-1 for typical 2 terminal and 4 terminal connections.

Figure 4-1

4-20 mA Connection

4.3ENCLOSURE INSTALLATION

To protect the transmitter and sensor assembly they should be removed from the enclosure and preserved until final installation and wiring termination.

Prior to installation and wiring:

Page: 6

Image 10
Contents 2-WireSeries APPLICABILITY & EFFECTIVITY4501-05FM Approved 4501-06FM Pending MODELModel 4501-05Hydrogen Sulfide Gas Sensor Module Model 4501-XXToxic Gas Sensor ModuleFM PERFORMANCE APPROVAL Sensor ModuleContents Model 4501-XXToxic Gas Sensor ModuleCABLING INSTALLATION ContentsModel 4501-XXToxic Gas Sensor Module Page 1. PRODUCT DESCRIPTIONModel 4501-XXToxic Gas Sensor Module 1.6POWER REQUIREMENTS 1.4.3SENSOR ASSEMBLY1.5INTERCONNECT WIRING Model 4501-XXToxic Gas Sensor ModuleModel 4501-XXToxic Gas Sensor Module PageModel 4501-XXToxic Gas Sensor Module 2. CAUTIONS & WARNINGSPage Model 4501-XXToxic Gas Sensor Module 3. QUICK STARTPage Model 4501-XXToxic Gas Sensor Module 4. INSTALLATIONFigure 4-20mA Connection PageFigure Connector Locations Page Model 4501-XXToxic Gas Sensor ModuleFigure Face Plate with Operator Keypad Page 5. OPERATIONKey ENTER Model 4501-XXToxic Gas Sensor ModuleDescription FunctionDisplay ReferenceFunction Model 4501-XXToxic Gas Sensor ModuleSub-RoutineA DisplayModel 4501-XXToxic Gas Sensor Module 5.5DIAGNOSTICS SUB-MENUDiagnostics Sub Menu PageModel 4501-XXToxic Gas Sensor Module PageModel CALIBRATION PROCEDURE6. CALIBRATION FlowPage 6.3 DIAGNOSTICS SUB-MENUModel 4501-XXToxic Gas Sensor Module Key FunctionENCLOSURE REPLACEMENT 7. SERVICE7.1SENSOR MODULE CONFIGURATION Figure Module Components PageINSTALLATION INSPECTION TRANSMITTER REPLACEMENTSENSOR REPLACEMENT Model 4501-XXToxic Gas Sensor ModuleModel 4501-XXToxic Gas Sensor Module Wiring terminations clean and correctPage 8. APPENDICES SpecificationsAPPENDIX A SPECIFICATIONS Model 4501-XXToxic Gas Sensor ModuleModel 4501-XXToxic Gas Sensor Module WarrantyLimited warranty PagePage APPENDIX B MODEL NUMBERS & PARTS LISTModel 4501-XXToxic Gas Sensor Module Sensor ModuleModel 4501-XXToxic Gas Sensor Module APPENDIX C LIMITED WARRANTYPage