Sierra Monitor Corporation 4501-04, 4501-06, 4501-05 Model 4501-XXToxic Gas Sensor Module, Page

Page 21
•Wiring terminations clean and correct.

Model 4501-XX Toxic Gas Sensor Module

Wiring terminations clean and correct.

7.1.4MOISTURE TRAPS AND RAINSHIELDS

Conduit seals and drains installed to avoid moisture build up in electronics enclosure. Water accumulation in sensor module enclosures is a major cause of damage and system failures - take precautions to seal electrical conduits and provide moisture traps and drains to avoid water damage

Rain-shields installed where applicable.

7.1.5STANDARD VOLTAGES

Loop voltage to be applied to the sensor module must be between 14 VDC and 30 VDC.

7.2INSPECTION AND TROUBLESHOOTING GUIDE

The inspection and troubleshooting guide can be used to step through the system start-up and to determine the corrective action if a fault occurs.

7.2.1IF MODULE DOES NOT DISPLAY THE CORRECT PPM GAS

1.Repeat calibration procedure.

2.Remove the gas and wait for the timer to completely count down.

3.Apply Span Gas and verify that the sensor sees the correct value of the span gas after calibration.

4.If the sensor still does not respond to gas, power cycle the unit and repeat calibration.

7.2.2IF THE MODULE DOES NOT DISPLAY THE CORRECT PPM

1.Power cycle the module.

2.Recalibrate the sensor.

7.2.3IF THE DISPLAY SHOWS ‘NO SENSOR’ – SENSOR FAILING

1.Power down the unit

2.Open the enclosure and unplug the sensor from the transmitter board.

3.Plug the sensor back into the transmitter board carefully and ensure a secure fit.

4.Power up the unit.

7.2.4IF THE DISPLAY SHOWS “C” – CALIBRATION MODE

1.Complete calibration or exit to operating mode.

7.2.5 IF THE DISPLAY SHOWS “ T

” – DOWNSCALE INDICATOR

1.The reaction of the sensor to gas may, for a short period of time, result in a downscale indicator being shown on the display.

2.If this indicator remains for a longer period of time, the sensor may need re-calibration.

7.2.6IF THE DISPLAY SHOWS “HIGH” – UPSCALE INDICATOR

1.The concentration of the gas is outside the calibrated range.

Page: 17

Image 21
Contents 4501-05FM Approved 4501-06FM Pending APPLICABILITY & EFFECTIVITY2-WireSeries MODELFM PERFORMANCE APPROVAL Model 4501-XXToxic Gas Sensor ModuleModel 4501-05Hydrogen Sulfide Gas Sensor Module Sensor ModuleModel 4501-XXToxic Gas Sensor Module ContentsContents CABLING INSTALLATIONModel 4501-XXToxic Gas Sensor Module 1. PRODUCT DESCRIPTION PageModel 4501-XXToxic Gas Sensor Module 1.5INTERCONNECT WIRING 1.4.3SENSOR ASSEMBLY1.6POWER REQUIREMENTS Model 4501-XXToxic Gas Sensor ModulePage Model 4501-XXToxic Gas Sensor Module2. CAUTIONS & WARNINGS Model 4501-XXToxic Gas Sensor ModulePage 3. QUICK START Model 4501-XXToxic Gas Sensor ModulePage Figure 4-20mA Connection 4. INSTALLATIONModel 4501-XXToxic Gas Sensor Module PageModel 4501-XXToxic Gas Sensor Module Figure Connector Locations PageKey ENTER 5. OPERATIONFigure Face Plate with Operator Keypad Page Model 4501-XXToxic Gas Sensor ModuleDisplay FunctionDescription ReferenceSub-RoutineA Model 4501-XXToxic Gas Sensor ModuleFunction DisplayDiagnostics Sub Menu 5.5DIAGNOSTICS SUB-MENUModel 4501-XXToxic Gas Sensor Module PagePage Model 4501-XXToxic Gas Sensor Module6. CALIBRATION CALIBRATION PROCEDUREModel FlowModel 4501-XXToxic Gas Sensor Module 6.3 DIAGNOSTICS SUB-MENUPage Key Function7.1SENSOR MODULE CONFIGURATION 7. SERVICEENCLOSURE REPLACEMENT Figure Module Components PageSENSOR REPLACEMENT TRANSMITTER REPLACEMENTINSTALLATION INSPECTION Model 4501-XXToxic Gas Sensor ModuleWiring terminations clean and correct Model 4501-XXToxic Gas Sensor ModulePage APPENDIX A SPECIFICATIONS Specifications8. APPENDICES Model 4501-XXToxic Gas Sensor ModuleLimited warranty WarrantyModel 4501-XXToxic Gas Sensor Module PageModel 4501-XXToxic Gas Sensor Module APPENDIX B MODEL NUMBERS & PARTS LISTPage Sensor ModuleAPPENDIX C LIMITED WARRANTY Model 4501-XXToxic Gas Sensor ModulePage