Emerson MA N-00 05-00, UT-P+-STXXXX user manual Sensor Separation

Page 15

non-hazardous area. Conform to local wiring codes.

When pouring a seal, use a fibre dam to assure proper formation of the seal. Seals should never be poured at temperatures below freezing.

The jacket and shielding of the cable should be stripped back to permit the seal to form around the individual wires. This will prevent air, gas and water leakage through the inside of the shield and into the enclosure.

It is recommended that explosion-proof drains and conduit breathers be used. In some applications, alternate changes in temperature and barometric pressure can cause 'breathing' which allows moist air to enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this 'breathing'.

Refer to applicable wiring codes when installing and wiring. After the field wiring has been carefully connected, check that the correct wires are connected to the corresponding terminals and that voltage levels do not exceed the specifications. When the wiring and voltages have been verified remove power

Figure 6 Display Board Layout

from the system. Set the Display board back in place and tighten the two retaining screws.

Sensor Separation

The ST1200, ST1300, ST1400, ST1500 and ST1600 sensors can be installed and wired directly to the UNI- TRAN Premium Plus housing and terminal board as per the wiring diagrams (see Figure 7and 9 ) or they may be remotely mounted using a sensor separation kit (JB2-2-ASSY) which is composed of a junction box and terminal strip (see Figure 8 and 10). The sensor and kit are then connected to the UNI-TRAN Premium Plus.

When sensor separation is required for units using the ST1200, ST1300, ST1400, ST1500 and ST1600 sensor use a minimum of 18AWG shielded copper instrument wire for separations up to 500 feet. Consult factory if greater separations are required (see Appendix B Wire Resistance in Ohms).

NOTE:

Use a minimum of 18AWG shielded copper instrument wire for separations up to 500 feet and 16AWG for separations up to 2000 feet. Consult factory if greater separations are required.

9

Image 15
Contents UNI-TRAN Premium Plus Toxic GAS Detector UT-P+-STXXXX Page Page Page Table of Contents Page Features IntroductionIntroduction Unpacking Installation and Start UpWhat’s in the package Location of SensorsToxic Detector Layout MountingDimensional Drawings Page Page Page Wiring Sensor Separation Page Wiring Diagrams Page Page Page Page Page Start Up Installation ChecklistDefault Relay Settings Relay SettingsExit Return to normal if no option is selected Summary of Main MenuSystem Calibration Review SettingsCalibration Procedure Page Operation Periodic Response CheckOperator Interface Table of Responses Calibration ProcedureMagnetic Reed Switch Activation Relay Settings Review Settings Sensor Drift Start DelaySensor Fault Hardware20 mA RelaysSensor Life TroubleshootingGlossary of Terms Ordering Information Published in a ccordance w ith E1A standard AWG Appendix B Wire Resistance In OhmsSensor Specifications Appendix C SpecificationsPage