Start Delay
When power is first applied to the monitor it will initiate a 90 second
Sensor Fault
CAUTION
The fault detection circuitry does not monitor the operation of external response equipment or the external wiring to these devices. It is important that these devices be checked periodically to ensure they are operational.
The
When a system fault is detected, the Status LED flashes (fast) red, the LED alphanumeric display shows “Sensor Fault” and the fault relay changes state.
Sensor Drift
It is a normal characteristic of gas sensors to exhibit a slow drift from zero. When the amount of drift exceeds 10% since the last calibration, the analog output switches to a value of 2.5mA, the status LED flashes red and the NEG DRIFT message scrolls on the display until manually reset and the system is
Normal
With no gas present and no fault detected “Normal” will be illuminated on the alphanumeric LED display to indicate a clean air status, Status LED will blip green and the analog output is 4.0 mA.
Hardware
Cal/Reset
A pushbutton for programming, zeroing, and resetting the Toxic Detector is provided. Depressing this push button for less than one second will initiate a basic system reset (clear a latched gas alarm). Programming the Toxic Detector is accomplished by depressing the push button for greater than one second.