The ST1210 sensors can be installed and wired directly to the UNI-TRAN Premium Plus housing and terminal board as per the wiring diagram (see Figure 10 ) or they may be remotely mounted using a sensor separation kit (JB2-3-ASSY) which is composed of a junction box and terminal strip (see Figure 11). The sensor and kit are then connected to the UNI-TRAN Premium Plus.

When sensor separation is required for units using the ST1210 Hydrogen Sulfide sensor use a minimum of 18AWG shielded copper instrument wire for separations up to 50 feet and 16AWG for separations up to 75 feet. Consult factory if greater separations are required (see Figure 11).

NOTE:

If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal and the

Common Terminal.

10

Image 16
Contents UNI-TRAN Premium Plus Toxic GAS Detector UT-P+-STXXXX Page Page Page Table of Contents Page Introduction FeaturesIntroduction Installation and Start Up What’s in the packageLocation of Sensors UnpackingMounting Toxic Detector LayoutDimensional Drawings Page Page Page Wiring Sensor Separation Page Wiring Diagrams Page Page Page Page Page Installation Checklist Start UpRelay Settings Default Relay SettingsSummary of Main Menu Exit Return to normal if no option is selectedReview Settings System CalibrationCalibration Procedure Page Periodic Response Check OperationOperator Interface Calibration Procedure Table of ResponsesMagnetic Reed Switch Activation Relay Settings Review Settings Start Delay Sensor FaultHardware Sensor DriftRelays 20 mATroubleshooting Sensor LifeGlossary of Terms Ordering Information Published in a ccordance w ith E1A standard Appendix B Wire Resistance In Ohms AWGAppendix C Specifications Sensor SpecificationsPage