Bacharach HGM300, RDM800 warranty Alarm, Line

Page 5

SECTION 3

HGM300 Relay Connector

Alarm

Alarm

Alarm

Fault

 

1

2

3

 

 

 

 

 

Relay

Relay

Relay

Relay

#1

#2

#3

#4

COMMON

NO

NC

COMMON

NO

NC

COMMON

NO

NC

COMMON

NO

NC

Strobe

Horn

Aux. Power

Main Power

Line

Neutral

Line

Neutral

Jumper the ‘Neutral’ of the auxiliary power connector to the ‘Common’ on the relay block.

Connect one end of strobe or horn to the ‘NO’ of whichever level of alarm is appropriate for application.

The other end of strobe or horn is connected to a 120VAC power source, or to the ‘Line’ of the auxiliary power connector.

Rev 3/2/09

5

Image 5
Contents HGM300/RDM800 Preventative Maintenance and Technical Support RDM800 CPU Reset HGM300 / RDM800 Technical Support Notes HGM300 CPU ResetTo Bypass the Warm UP Mode Monitor will not Come OUT of Warm UPCommon RDM800 Indications Section Line AlarmSection No Flow Check Procedure Rev 3/2/09 No Flow Problems HOW to Force Taking NEW Pressure Readings Clipping Fault Adjustment Page HGM300 Voltage Check Connector J9HOW to Silence Alarms on the HGM300 Alarm Detail ScreenSample Flow Ndir Source Rev 3/2/09 Materials Used Rev 3/2/09 Materials Used ProcedureRev 3/2/09 Rev 3/2/09 Contact Peter Pape