‰Install nozzle line assembly

yInsert the nozzle line assembly into the burner air tube as in Figure 6.

ySee Figures 6 and 7. Assemble the adjusting plate assembly per the instructions in the assembly pack- et.

ySlide the secondary adjusting plate (item f) com- pletely to the left on the indicator adjusting plate (item e). Finger-tighten acorn nut (item c) to secure the two plates together. Slide both plates completely to the left on the primary adjusting plate (item g) and finger-tighten acorn nut (item d).

ySlide the completed adjusting plate assembly over the nozzle line end. Move the plate assembly and the nozzle line so the plate assembly fits into posi- tion as shown in Figure 6.

yInstall the spline nut (Figure 6, item b) on the end of the nozzle line, leaving the nut loosely placed so the plates can be moved.

yConnect the high-voltage leads from the ignition transformer to the electrodes.

‰Set dimension Z

yReplace the rear access door on the burner, making sure that the adjusting plate assembly is now securely in the groove.

yLoosen acorn nut (item d) in Figure 5. Slide the nozzle line and plate assembly until dimension Z in Figure 5 is 1-3/4 ±1/16” (CF1400 and CF2300). When dimension Z (from end of air tube to flat area of front face of head) is correctly set, tighten acorn nut (item d). Verify that the adjusting plate assembly is properly seated in the groove.

yAttach the oil line from the oil valve to the nozzle line end. Tighten securely.

yBefore proceeding, check dimension Z once again. Loosen acorn nut (item d) if necessary to reposition the nozzle line. Once dimension Z is set, do not loosen acorn nut (item d) again.

Figure 6 – Nozzle line assembly in burner

 

Figure 7 – Adjusting plate assy.

Z

 

 

Measure dimension Z from

 

d

b

 

 

 

 

 

 

front (flat) face of head to

a

 

 

 

 

end of air tube, as shown.

 

 

 

 

 

 

 

 

 

c

Z = 1-3/4” ± 1/16”

2308

 

Measure dimension Z from the flat

2324

surface between (not on) the raised fins.

Legend (figure 6 & 7)

aAdjusting plate assembly

bSpline nut for securing nozzle line

cBottom acorn nut

dTop acorn nut (for setting dim. Z only)

eIndicator adjusting plate

fSecondary adjusting plate g Primary adjusting plate

10

Form 6104 BCF23-R05

 

Image 10
Contents Potential for Fire, Smoke and Asphyxiation Hazards To the Professional, Qualified Installer or Service AgencyTo the Homeowner or Equipment Owner Table of Contents Specifications General InformationAgency approvals Owner’s Responsibility Pre-installation checklistProfessional Installer/Service Agency Responsibility Follow These Instructions Exactly‰ Fuel supply Oil Supply Pressure Control RequiredCorrect Nozzle and Flow Rate Required ‰ Nozzle pressure‰ Verify burner components Nozzle capacities‰ Vent system ‰ Verify firing rate Air tube capacity Versus firebox pressure ‰ Verify air tubeProtect Against Dust Moisture Mount the burnerProtect Against Stray Light Lockout Protect the Air Tube From OverheatingMaintain Electrode Specifications ‰ Install nozzle‰ Check electrode settings ‰ Mount air tube to burner‰ Install nozzle line assembly ‰ Set dimension ZBurner installed in appliance front ‰ Insert burnerFactory-Installed Pump Bypass Plug Install Oil Supply To SpecificationsConnect fuel lines One-pipe oil flow with B pump Fuel unit gearset capacitiesWire the burner R7184B Electrical Shock HazardSequence of operation Typical Sequence of operation typicalProfessional Installation Service Required Do Not Bypass Safety ControlsKeep Service Access Covers Securely Installed Prepare the burner for start-upCF1400 Initial indicator adjustment plate settings CF2300 Initial indicator adjustment plate settings‰ Initial air settings Damper Motor with CoverHot Gas Puff-back Heavy Smoke Hazard Professional Service RequiredStart the burner Explosion and Fire Hazard‰ Set high-fire air ‰ Start burner and vent air from oil line‰ Set low-fire air Monthly maintenance by owner Perform Regular MaintenanceAnnual Service Annual Professional Service RequiredPart Name Replacement PartsDescription Burner Replacement Parts Flange a Flange B Flange CWarranty Limited Warranty Information