Harman VF3000 manual 12Venting, Chimney

Page 12

12Venting

 

Non-combustible cover, one

 

side only. If two covers are

Hole with a minimum

used, each must be mounted

clearance of 18" (450 mm)

on non-combustible spacers

between connector and wall.

at least 7/8" (21mm) away

 

from the wall.

1" (25mm) Clearance

AN APPROVED CANADIAN

WALL PASS-THROUGH

The Chimney

This unit must be installed into a chimney approved for use with solid-fuel appliances. In the U.S., it must be connected to (1) a prefabricated chimney comply- ing with the requirements for Type HT chimneys in the Standard for Chimneys, Factory-Built, Residential Type and Building Heating Appliances, UL 103, or (2) a code-approved masonry chimney with a flue liner.

In Canada, this unit is listed for use with prefabricat- ed chimneys tested and listed to the high temperature (650 degrees C) chimney standard, ULC S-629, or with a code approved masonry chimney.

Closest

Minimum 2" (50mm)

Combustible

Material

Clearance to Brick

 

Liner

Minimum 12"

 

(300mm) to Brick

 

 

 

Flue

Fire Clay

 

Thimble

 

 

 

Chimney

Chimney

 

 

Connector

Masonry Chimney Built to

NFPA 211 Specifications.

Minimum 12" (300mm)

to Combustibles AN APPROVED U.S.

WALL PASS-THROUGH

Do not connect this unit to a chimney flue servicing another appliance.

This VF3000 Is Approved To Burn Anthracite “Rice” Coal Only.

The minimum recommended height for any chimney is 16 ft (4.8 m) above flue collar height. A round flue (either masonry or approved prefabricated), of either 6" (150 mm), 7" (180 mm) or 8" (200 mm) may be used. For square or rectangular masonry chimneys, nominal sizes of 8" x 8" or 8"x 12" (200mm x 200 mm, 200 mm x 300 mm) may be used.

Codes require that solid-fuel chimneys extend 3 ft (0.9 m) above the highest point at which they exit from the roof. Then, the chimney must extend 2 ft.(6

m)above the highest point within a 10 ft (3 m) radius. Thus, the 3 foot, 2 foot, 10 foot rule:

3ft. - Above roof exit point

2ft. - Higher than anything within- 10ft. of the chimney.

More Than 10 ft. (3m)

10 ft. (3m)

2 ft. (0.6m) min.

Ridge

Height Necessary Above Any Roof Sur- face Within 10ft. (3m)

3ft. (0.9m) minimum above exit

point

Chimney

The 3-foot, 2-foot, 10 foot rule

Image 12
Contents VF3000 Coal Stoker Boiler Page Contents Introduction Specifications/Hot Water Coil Hot Water CoilWarnings Never sleep in the same room with any coal burning stovePacking List Assembly Assembly FeederGrate 10Assembly Grates and FirebrickVenting11 Draft12Venting ChimneyVenting13 Do not connect to any air distribution duct or system14Installation Aquastat and WiringInstallation Basic Plumbing16Installation Clearances InstallationVerti-Flow Stoker Control Verti-FlowStoker ControlHow to operate the Stoker Control Verti-Flow Stoker ControlFeed Adjustment Operation19Starting a fire 20Maintenance Ash RemovalWeekly Every 3 monthsMaintenance21 Annually22Troubleshooting Feeding ProblemsStoker Control Troubleshooting Aquastat Installation A350My350, s35024AQUASTAT Feeder Parts List Wiring Diagram & Fuel CoalVF3000 At har Warranty29 Harman Central Heating Products Limited Warranty30Notes