Lochinvar 50-210 service manual Viewable and changeable control parameters, Temperature settings

Page 17

Service Manual

1Service

Viewable and changeable control parameters

CAUTION

Before changing parameters, note the settings so that the unit can be returned to its original operating parameters.

A: General

Boiler model

The control will display “Knight Boiler” as the model number because the same control is used on several models. This will be displayed when parameter A1 has been accessed. This parameter is not changeable.

User code

The User Code allows the user to access and change a limited number of control parameters. The access code can be changed by the user or the installer to a code of their choosing. To change the code, parameter A2 must be accessed. The default code is 0704. The code can be changed one digit at a time by using the arrow keys on the display.

Date and time

The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than 30 days. To set the clock, parameter A3 must be accessed. The date and time are displayed as “YY:MM:DD W hh:mm”. YY = year, MM = month,

DD= date, W = day (1 = Sunday, 2 = Monday, etc.), hh = hour

(24 hour time; 2:00 PM = 14:00), mm = minutes.

NOTICE

The internal clock does not adjust for

Daylight Savings Time and therefore, will

 

 

require a manual adjustment.

Software version

The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.

Temperature units

The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A5. The default is °F.

Night setback temperature

Once the internal clock has been set correctly, the night setback feature can be used to program a lower water temperature set point for space heating. This parameter can be changed by the user or the installer by accessing parameter A6. The temperature range for this parameter is 32°F to 140°F. The feature is turned off with a setting of 32°F. The default value is 32°F.

Night setback times

If parameter A6 is set to anything other than 32°F, the night setback feature becomes active. This will require start and stop times to be programmed for the days that reduced temperatures are required. These times can be changed by the user or the installer by accessing parameter A7. Each day of the week (Sunday through Saturday) will have an on and off time.

Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish to skip a day and have no night setback, leave the on and off times the same. The default times for each day will be 00:00 (midnight).

B: Temperature settings

SH set point user

The SH set point user sets the water temperature set point for fixed operation or the maximum temperature set point when the outdoor air sensor is used. This parameter can be changed by the user or the installer by accessing parameter B1. The temperature range of this parameter is 50°F to 190°F. The default value is 125°F.

SH minimum set point

The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point. This parameter can only be changed by the installer by accessing parameter B2. The temperature range of this parameter is 32°F to 190°F. The default value is 70°F.

SH Maximum set point

The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point. This parameter can only be changed by the installer by accessing parameter B3. The temperature range of this parameter is 32°F to 190°F. The default value is 190°F.

SH Offset

The SH offset sets how many degrees above set point the temperature has to go before the boiler will shut off. This parameter can only be changed by the installer by accessing parameter B4. The temperature range of this parameter is 0°F to 86°F. The default value is 10°F.

17

Image 17
Contents Models 50 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Service What is in this manual?Maintenance TroubleshootingNear boiler piping ServiceKnight wall mount display Control inputs Smart Control ModuleControl outputs How the boiler operates General OperationHow the control module operates Sequence of operationOUT 123.8F129 Sequence of operationBLR SH 41% Rate Display panel menu access Display panel parameter access Parameter table Temperature DataControl Circulation Service Viewable and changeable control parameters Temperature settingsOutdoor air reset DHW settingsData logging FunctionsMaximum SH set point Shift reset curveMinimum SH set point Outdoor air shutdownAnti-cycling SH controlling sensor Control modesSH source Boiler cascade addressCirculation pumps Service NotificationCascade offset Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check boiler relief valveCheck all boiler wiring Check ignition ground wiringCheck control settings Inspect ignition and flame sense electrodesCleaning boiler heat exchanger Check flame signalReview with owner Oiled bearing circulatorsBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotTemperature Resistance Checking temperature sensorsNo Pump NoisyBoiler Pump System Pump DHW PumpFlow Switch/LWCOFlame SequenceNo Flame Ign Anti-cyclingRunning No FlameHigh Limit Auto ResetFan Low Fan Speed LowFan Speed High Fan HighSensor Open Sensor ShortedTemp O/Shoot Open Rem Ctrl FltParameters Progr Watch Dog Error Service BlkNo Error Stored Low 24 vacGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply Pressure2Gas Valve Adjustment Gas valve adjustment procedurePage

50-210 specifications

The Lochinvar 50-210 is a powerful and efficient boiler designed for residential and commercial heating applications. This model is a part of Lochinvar’s line of advanced heating solutions, known for their reliability, efficiency, and innovative technologies. The 50-210 offers a high thermal efficiency rating, ensuring that energy consumption is minimized while still providing excellent heating performance.

One of the standout features of the Lochinvar 50-210 boiler is its advanced control system. It is equipped with a user-friendly LCD display that allows easy access to system settings and real-time performance data. This technology enhances user experience, allowing for easy adjustments and monitoring, ensuring optimal performance based on specific heating needs.

The Lochinvar 50-210 is designed with a fully modulating burner, which means it can adjust its output to match the heating demand effectively. This feature not only provides superior comfort but also increases energy savings by preventing the boiler from running at full capacity when it's not necessary. Moreover, the modulating burner minimizes wear and tear, extending the lifespan of the unit.

In terms of safety, the Lochinvar 50-210 incorporates several features such as multiple temperature and pressure sensors, flame safeguard systems, and safety cut-off controls. These safeguard mechanisms ensure that the system operates safely and efficiently, providing peace of mind to users.

The construction of the Lochinvar 50-210 is robust, featuring high-grade stainless steel and a durable heat exchanger. This design helps resist corrosion, ensuring longevity and requiring minimal maintenance over the years. Additionally, its compact design allows for easier installation, making it suitable for various settings, even those with limited space.

Furthermore, the Lochinvar 50-210 operates quietly, which adds to its appeal for residential installations. Its environmental considerations are also noteworthy, with low emissions contributing to cleaner air quality.

Overall, the Lochinvar 50-210 is a sophisticated heating solution that blends efficiency, reliability, and advanced technology. With its user-friendly controls, modulating burner, safety features, and durable construction, it meets the heating demands of modern homes and commercial spaces, making it a top choice for those seeking dependable boiler performance.