3Troubleshooting (continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

While the unit is in Service Mode, the outlet

• Establish a heating load to remove the heat from the

 

temperature has exceeded 185°F.

boiler loop.

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight Wall Mount Installation and Operation

 

 

Manual for the proper piping methods for the Knight

Service Blk

 

wall mount boiler.

 

 

• Check 120 vac to the boiler pump motor on a call for

 

 

heat. If voltage is not present, check the wiring back

 

 

to the main control board. Replace the main control

 

 

board if necessary.

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

• Verify that the boiler pump is set to the proper speed

 

 

or that the boiler pump is the proper size. Reference

 

 

Section 6 - Hydronic Piping of the Knight

 

 

Boiler Installation and Operation Manual for boiler

 

 

pump specifications.

 

 

 

 

120 vac input to the main control board has

• Check 120 vac supply to the transformer.

 

dropped below 80 vac.

 

 

 

 

Low 24 vac

 

• Check wiring connections at the low voltage terminal

 

strip.

 

 

• Check the wire size/length to remote devices.

 

 

• Replace the transformer.

Watch Dog Error

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

 

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

CRC Parameters

internal fault.

 

 

 

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

No Error Stored

internal fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

 

 

 

 

 

 

 

 

 

Image 39
Contents Models 50 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceKnight wall mount display Control inputs Smart Control ModuleControl outputs Sequence of operation General OperationHow the boiler operates How the control module operatesOUT 123.8F129 Sequence of operationBLR SH 41% Rate Display panel menu access Display panel parameter access Parameter table Temperature DataControl Circulation Service Viewable and changeable control parameters Temperature settingsFunctions DHW settingsOutdoor air reset Data loggingOutdoor air shutdown Shift reset curveMaximum SH set point Minimum SH set pointAnti-cycling Boiler cascade address Control modesSH controlling sensor SH sourceService Notification Cascade offsetCirculation pumps Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsOiled bearing circulators Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationTemperature Resistance Checking temperature sensorsDHW Pump NoisyNo Pump Boiler Pump System PumpSequence Switch/LWCOFlow FlameNo Flame Ign Anti-cyclingRunning No FlameFan Speed Low Auto ResetHigh Limit Fan LowSensor Shorted Fan HighFan Speed High Sensor OpenTemp O/Shoot Rem Ctrl Flt Parameters ProgrOpen Low 24 vac Service BlkWatch Dog Error No Error StoredGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or Obstruction2Gas Valve Adjustment Gas valve adjustment procedurePage

50-210 specifications

The Lochinvar 50-210 is a powerful and efficient boiler designed for residential and commercial heating applications. This model is a part of Lochinvar’s line of advanced heating solutions, known for their reliability, efficiency, and innovative technologies. The 50-210 offers a high thermal efficiency rating, ensuring that energy consumption is minimized while still providing excellent heating performance.

One of the standout features of the Lochinvar 50-210 boiler is its advanced control system. It is equipped with a user-friendly LCD display that allows easy access to system settings and real-time performance data. This technology enhances user experience, allowing for easy adjustments and monitoring, ensuring optimal performance based on specific heating needs.

The Lochinvar 50-210 is designed with a fully modulating burner, which means it can adjust its output to match the heating demand effectively. This feature not only provides superior comfort but also increases energy savings by preventing the boiler from running at full capacity when it's not necessary. Moreover, the modulating burner minimizes wear and tear, extending the lifespan of the unit.

In terms of safety, the Lochinvar 50-210 incorporates several features such as multiple temperature and pressure sensors, flame safeguard systems, and safety cut-off controls. These safeguard mechanisms ensure that the system operates safely and efficiently, providing peace of mind to users.

The construction of the Lochinvar 50-210 is robust, featuring high-grade stainless steel and a durable heat exchanger. This design helps resist corrosion, ensuring longevity and requiring minimal maintenance over the years. Additionally, its compact design allows for easier installation, making it suitable for various settings, even those with limited space.

Furthermore, the Lochinvar 50-210 operates quietly, which adds to its appeal for residential installations. Its environmental considerations are also noteworthy, with low emissions contributing to cleaner air quality.

Overall, the Lochinvar 50-210 is a sophisticated heating solution that blends efficiency, reliability, and advanced technology. With its user-friendly controls, modulating burner, safety features, and durable construction, it meets the heating demands of modern homes and commercial spaces, making it a top choice for those seeking dependable boiler performance.