6CHECK PILOT FLAME. Flame should be a blue medium hard flame enveloping approximately 3/8” of the end of the sensing probe, see Figure 14.
7CHECK THERMOSTAT OPERATION. Raise and lower thermostat setting as required to start and stop burners.
8CHECK HIGH LIMIT CONTROL. Allow boiler to operate until burners are shut down by limit control (approximately 235°F). If burners are not shut down by limit control, determine cause of malfunction. Replace control if necessary and check its operation.
9CHECK IGNITION SYSTEM SAFETY SHUTOFF DEVICE. Remove pilot ground lead from electrical junction block. If burners are not shut down by module, determine cause of malfunction. Replace module or gas valve if necessary.
10MAIN BURNER FLAMES should have a clearly defined inner cone, see Figure 15, with no yellow tipping.
11CHECK LWCO OPERATION (if so equipped). Drain boiler water below LWCO set point. Burners should shutdown. If burners do not shut down determine cause of malfunction and repair.
12WARNING – BEFORE INSTALLATION OF THE BOILER IS CONSIDERED COMPLETE, THE OPERATION OF THE BOILER CONTROLS SHOULD ALL BE CHECKED, PARTICULARLY THE LOW WATER
Figure 14
TYPICAL PILOT FLAME
Figure 15
MAIN BURNER FLAME
22