Table 5: L7224 / L7248 Controller
Operating Sequence
Action | System Response |
Thermostat | Circulator starts when water temperature is |
calls for heat. | above Low Limit setting (if applicable). Boiler |
| temperature is checked. Burner starts when |
| water temperature is below High Limit setting. |
Boiler exceeds | Burner is turned off. Burner restarts when the |
the High Limit. | water temperature drops below the High Limit |
| setting minus the Differential. |
Thermostat is | Circulator and burner turn off. |
satisfied. |
|
Error condition | If an error condition is detected, all outputs ex- |
cept ZC are shut down. Burner is off. Control | |
| continues to function and restarts when error is |
| corrected. |
| During the error check sequence, the system |
| checks for drift in the sensor and corrosion in |
| the connections. |
Error | EnviraCOM communication is not available. |
condition 6. |
|
Error | The control has reset the High Limit, Low Limit |
condition 7. | and Differential setting to a default setting and |
| will continue to run at those settings. |
| Performance of the system will be degraded. |
Error | If the error condition is detected, all outputs |
condition 8. | except ZC are shut down. Burner is off. Control |
| continues to function and restarts when all |
| three user keys have been pressed longer than |
| 60 seconds. |
Differential. The L7248 models have High Limit Differential presets of 15°F (8°C). The L7224 models have High Limit Differential presets of 10°F (6°C).
Table 6: Trouble Shooting Guide
9.LOW LIMIT AND CIRCULATOR CONTROLLER
On a temperature rise, with the adjustable Differential at the default setting of 10°F (6°C), the burner circuit breaks and the circulator circuit makes (assuming no call for heat is present) at the Low Limit setpoint. On a temperature drop of 10°F (6°C) below the Low Limit setpoint, the burner circuit makes and the circulator circuit breaks. See Figure 24.
Figure 24: Setpoints and Differentials
System Condition | Diagnostic Condition | Check |
| Action | |
Boiler is cold, house is | Display is OFF. | 120 Vac System power. | Turn system power on. | ||
cold. |
|
|
|
| |
Display is ON. | 24 Vac | No 24 V; replace control. | |||
| |||||
|
| 24 V present; disconnect thermostat, | Boiler starts, check wiring and thermostat. | ||
|
| short | |||
|
|
|
| ||
|
| 120 Vac at | • | If no, replace control. | |
|
|
| • | If yes, check burner and wiring. | |
|
| Refer to Err on display. | |||
Boiler is hot, house is | Display is ON. | 120 Vac at | • | 120 Vac at | |
cold. |
|
|
| to pump. | |
|
|
| • | Wiring OK, is pump running? | |
|
|
| • | If not, replace the pump. | |
|
|
| • | If pump is running, check for | |
|
|
|
| trapped air or closed zone valves | |
|
| Boiler below the Low Limit tempera- |
|
| |
|
| ture, wait for boiler to go above Low | |||
|
| Limit temperature. |
|
| |
|
| Boiler above LL? If yes, check for | • | If no 120 Vac , replace control. | |
|
| • | If yes, check zone relays, circulators | ||
|
| 120 Vac between ZC and L2. | |||
|
|
| and wiring. | ||
|
|
|
|
32