Burnham RSA manual L7224 / L7248 Controller Operating Sequence, Trouble Shooting Guide

Page 32

Table 5: L7224 / L7248 Controller

Operating Sequence

Action

System Response

Thermostat

Circulator starts when water temperature is

calls for heat.

above Low Limit setting (if applicable). Boiler

 

temperature is checked. Burner starts when

 

water temperature is below High Limit setting.

Boiler exceeds

Burner is turned off. Burner restarts when the

the High Limit.

water temperature drops below the High Limit

 

setting minus the Differential.

Thermostat is

Circulator and burner turn off.

satisfied.

 

Error condition

If an error condition is detected, all outputs ex-

1-5.

cept ZC are shut down. Burner is off. Control

 

continues to function and restarts when error is

 

corrected.

 

During the error check sequence, the system

 

checks for drift in the sensor and corrosion in

 

the connections.

Error

EnviraCOM communication is not available.

condition 6.

 

Error

The control has reset the High Limit, Low Limit

condition 7.

and Differential setting to a default setting and

 

will continue to run at those settings.

 

Performance of the system will be degraded.

Error

If the error condition is detected, all outputs

condition 8.

except ZC are shut down. Burner is off. Control

 

continues to function and restarts when all

 

three user keys have been pressed longer than

 

60 seconds.

Differential. The L7248 models have High Limit Differential presets of 15°F (8°C). The L7224 models have High Limit Differential presets of 10°F (6°C).

Table 6: Trouble Shooting Guide

9.LOW LIMIT AND CIRCULATOR CONTROLLER

On a temperature rise, with the adjustable Differential at the default setting of 10°F (6°C), the burner circuit breaks and the circulator circuit makes (assuming no call for heat is present) at the Low Limit setpoint. On a temperature drop of 10°F (6°C) below the Low Limit setpoint, the burner circuit makes and the circulator circuit breaks. See Figure 24.

Figure 24: Setpoints and Differentials

System Condition

Diagnostic Condition

Check

 

Action

Boiler is cold, house is

Display is OFF.

120 Vac System power.

Turn system power on.

cold.

 

 

 

 

Display is ON.

24 Vac T-T

No 24 V; replace control.

 

 

 

24 V present; disconnect thermostat,

Boiler starts, check wiring and thermostat.

 

 

short T-T.

 

 

 

 

 

 

120 Vac at B1-B2

If no, replace control.

 

 

 

If yes, check burner and wiring.

 

 

Refer to Err on display.

-----

Boiler is hot, house is

Display is ON.

120 Vac at C1-C2

120 Vac at C1-C2, check wiring

cold.

 

 

 

to pump.

 

 

 

Wiring OK, is pump running?

 

 

 

If not, replace the pump.

 

 

 

If pump is running, check for

 

 

 

 

trapped air or closed zone valves

 

 

Boiler below the Low Limit tempera-

 

 

 

 

ture, wait for boiler to go above Low

-----

 

 

Limit temperature.

 

 

 

 

Boiler above LL? If yes, check for

If no 120 Vac , replace control.

 

 

If yes, check zone relays, circulators

 

 

120 Vac between ZC and L2.

 

 

 

and wiring.

 

 

 

 

32

Image 32
Contents RSA Series 8143508R21-1/10 Price $3.00Important Information Read Carefully Page Page Table of Contents RSA Packaged Boiler RSA170 / RSA285 Pre-Installation Do not drop boiler. Do not bump boiler jacket against floorPage Removal of Boiler II. Knock-Down Boiler AssemblyInstalling the Jacket Installation of Boiler Controls Burner MountingThis page is Left Intentionally Blank III. Water Piping and Trim Page Page Page Page Schematic Tankless Heater Piping Tankless Heater Ratings IV. Venting Recommended Smoke Pipe Arrangement and Chimney Requirements Electrical GeneralRsal Wiring Less Tankless, Single Circulator Circulator Zoned Wiring for Honeywell R8888 Zone Valve Zoned Wiring for R8889 Page Page Circulator Zoning with EC5000 Wiring Schematic SchematicWiring EC5000with ZonedValve Zone19 Single-Pipe Installation VI. Oil Piping Single-Stage Units 3450 RPM Two Pipe Systems Two-Stage Units 3450 RPM Two Pipe SystemsVII. System Start-Up LED Error Codes Display ReadoutOperation High Limit ControllerLOW Limit and Circulator Controller Trouble Shooting GuideL7224 / L7248 Controller Operating Sequence Beckett AFG, AF, & SF Burners Becket AFG BurnerCarlin EZ-2HP Burner Beckett Burner Carlin EZ-1HP BurnerRemove GUN Assembly Verify OIL Burner Settings Before StartingAdjust OIL Pressure Other AdjustmentsHigh Altitude Installations Hints on CombustionTest Controls Verify High Limit OperationUse Part Number 6183505 for the following models VIII. Service and Cleaning Clean the FiretubesAvoid Breathing Fiber Particulates and Dust IX. Repair Parts Description Part Number Fogire 28 Assembled BoilerRSA85-135 Bare Boiler Repair Parts ‘A’ RSA170-285 Boiler Repair Parts Jacket Top Panel Assembly Beckett Burner Parts List for RSA Series Steel Boilers Ordering Information for Quality Replacement Parts AF60XO AF60XP SF60FY Beckett AF and SF Model Burners Lwco Location Wiring of Typical LwcoLow Water Cut Off Lwco Service Record Limited Warranty