and return line as illustrated in Figures 8 and 9 in order to regulate water flow for maintenance of higher boiler water temperature. Set the bypass and return valves to a half throttle position to start. Operate boiler until the system water temperature reaches its normal operating range. Adjust the valves to maintain 180°F to 200°F boiler water temperature and greater the 120°F return temperature. Adjust both valves simultaneously. Closing the boiler return valve while opening the bypass valve will raise the boiler return temperature. Opening the boiler return valve while closing the by-pass valve will lower the boiler return temperature.

e.A water boiler installed above radiation level must be provided with a low water cutoff device as part of the installation.

If a low water cut-off is required, it must be mounted in the system piping above the boiler.

The minimum safe water level of a hot water boiler is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.

B. Install Safety Relief Valve. See Figures 8 and 9. Safety Relief Valve must be installed with spindle in the vertical position. Installation of the relief valve

must be consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV.

WARNING

Safety (relief) valve discharge piping must be piped near floor to eliminate potential of severe burns. Do not pipe in any area where freezing could occur. Do not install any shut-off valves, plugs or caps.

C.Install Drain Valve in return piping. See Figures 8 and 9.

D. Oil, grease, and other foreign materials which accumulate in new hot water and a new or reworked system should be boiled out, and then thoroughly flushed. A qualified water treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.

E. After the boiler and system have been cleaned and flushed, and before refilling the entire system add appropriate water treatment chemicals, if necessary, to bring the pH between 7 and 11.

WARNING

Installation is not complete unless a safety relief valve is installed as shown in Figure 1 or 1A.

13

Image 13
Contents 8143508R21-1/10 Price $3.00 RSA SeriesImportant Information Read Carefully Page Page Table of Contents RSA Packaged Boiler RSA170 / RSA285 Do not drop boiler. Do not bump boiler jacket against floor Pre-InstallationPage Installing the Jacket II. Knock-Down Boiler AssemblyRemoval of Boiler Burner Mounting Installation of Boiler ControlsThis page is Left Intentionally Blank III. Water Piping and Trim Page Page Page Page Schematic Tankless Heater Piping Tankless Heater Ratings IV. Venting Recommended Smoke Pipe Arrangement and Chimney Requirements General ElectricalRsal Wiring Less Tankless, Single Circulator Circulator Zoned Wiring for Honeywell R8888 Zone Valve Zoned Wiring for R8889 Page Page Circulator Zoning with EC5000 Wiring Schematic SchematicWiring EC5000with ZonedValve Zone19 VI. Oil Piping Single-Pipe InstallationTwo-Stage Units 3450 RPM Two Pipe Systems Single-Stage Units 3450 RPM Two Pipe SystemsVII. System Start-Up Display Readout LED Error CodesOperation High Limit ControllerL7224 / L7248 Controller Operating Sequence Trouble Shooting GuideLOW Limit and Circulator Controller Becket AFG Burner Beckett AFG, AF, & SF BurnersCarlin EZ-2HP Burner Beckett Burner Carlin EZ-1HP BurnerVerify OIL Burner Settings Before Starting Remove GUN AssemblyAdjust OIL Pressure Other AdjustmentsHints on Combustion High Altitude InstallationsVerify High Limit Operation Test ControlsUse Part Number 6183505 for the following models Clean the Firetubes VIII. Service and CleaningAvoid Breathing Fiber Particulates and Dust IX. Repair Parts Fogire 28 Assembled Boiler Description Part NumberRSA85-135 Bare Boiler Repair Parts ‘A’ RSA170-285 Boiler Repair Parts Jacket Top Panel Assembly Beckett Burner Parts List for RSA Series Steel Boilers Ordering Information for Quality Replacement Parts AF60XO AF60XP SF60FY Beckett AF and SF Model Burners Low Water Cut Off Lwco Wiring of Typical LwcoLwco Location Service Record Limited Warranty