Burnham SCG manual Gas Piping, Gravity Factor

Page 50

V. Gas Piping

 

WARNING

 

 

4. Specific gravity of gas. Gas piping systems for

 

 

 

 

gas with a specific gravity of 0.70 or less can be

 

 

 

 

 

 

 

sized directly from Table 7, unless authority having

Failure to properly pipe gas supply to

 

 

 

 

jurisdiction specifies a gravity factor be applied.

boiler may result in improper operation and

 

 

 

 

For specific gravity greater than 0.70, apply gravity

damage to the boiler or structure. Always

 

 

 

 

 

 

factor from Table 6. If exact specific gravity is not

assure gas piping is absolutely leak free

 

 

 

 

 

 

shown choose next higher value.

 

and of the proper size and type for the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connected load.

 

 

 

 

Table 6: Specific Gravity Correction Factors

An additional gas pressure regulator may

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be needed. Consult gas supplier.

 

 

Specific

 

Correction

 

Specific

Correction

A. Size gas piping. Design system to provide adequate gas

Gravity

 

Factor

 

Gravity

Factor

 

 

 

 

 

 

 

 

 

 

 

----

 

 

----

 

 

0.85

0.81

supply to boiler. Consider these factors:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Allowable pressure drop from point of delivery to

 

----

 

 

----

 

 

0.90

0.82

boiler. Maximum allowable system pressure is ½

 

 

0.60

 

 

1.00

 

 

1.00

0.78

psig. Actual point of delivery pressure may be less;

 

 

 

 

 

 

 

 

 

 

 

 

 

0.65

 

 

0.96

 

 

1.10

0.74

contact gas supplier for additional information.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum gas valve inlet pressure is stamped on

 

 

0.70

 

 

0.93

 

 

1.20

0.71

the rating label located in the boiler’s vestibule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.75

 

 

0.90

 

 

1.30

0.68

compartment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Maximum gas demand. Refer to the boiler’s input

 

0.80

 

 

0.87

 

 

1.40

0.66

as printed on it’s rating label. Also consider existing

 

 

 

 

 

 

 

 

 

 

 

 

and expected future gas utilization equipment (i.e.

 

For materials or conditions other than those listed

water heater, cooking equipment).

 

 

 

 

above, refer to National Fuel Gas Code, NFPA54/ANSI

3. Length of piping and number of fittings. Refer to

 

 

 

 

Z223.1, or size system using standard engineering

Table 7 for maximum capacity of Schedule 40 pipe.

 

methods acceptable to authority having jurisdiction.

Table 8 lists equivalent pipe length for standard

 

 

 

 

 

 

 

 

 

 

 

 

 

fittings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5: Gas Ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

Natural/LP

Minimum Natural

 

 

Minimum LP

 

Natural

 

LP

 

 

 

Maximum

Gas Pressure

 

Gas Pressure

 

Manifold

 

Manifold

 

 

Model

 

 

 

 

 

Gas Pressure

(in. w.c.)

 

 

(in. w.c.)

 

Pressure

 

Pressure

 

 

Number

 

 

 

 

 

 

(in. w.c.)

Inlet to Gas Valve

 

Inlet to Gas Valve

 

(in. w.c.)

 

(in. w.c.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-6

14

4.5

 

 

11.5

 

 

 

3.5

 

10.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCG-9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTICE

SCG boilers built for altitudes greater than 4,999 feet above sea level need to be specially orificed to adjust for changes in atmospheric conditiions. The SCG boiler "H" Model has been certified to operate in atmospheric conditions from 5,000 to 10,000 feet above sea level. Input is derated by 10% for applications at 5,000 feet above sea level, and 20% for applications at 10,000 feet above sea levels. Derate is based on 2% reduction per 1000 feet.

The SCG boiler is available in two (2) altitude Models: The "S" Model 0-4,999 feet above sea level, and the "H" Model 5,000-10,000 feet above sea level.

For applications above 10,000 feet, consult the manufacturer.

50

Image 50
Contents SCG Important Information Read Carefully Page Table of Contents Dimensions Appliance is design certified for installation on Pre-InstallationInstallation must conform to the requirements Provide combustion and ventilation air in accordanceII. Unpack Boiler Do not drop boiler. Do not bump boiler jacket against floorIII. Venting / Air Intake Piping See SectionVent System Components Part Number Vent Guidelines Due to Removal of an Existing Boiler General GuidelinesInstall Vent Pipe, Burnham Gasketed Vent System Burnham Gasketed Vent Joint DetailVent Piping Recommended Separate Horizontal Vent/Air Intake Installation Alternate Separate Horizontal Vent/Air Intake Installation Page Page Separate Vertical Venting System See Figures 6, 7, 8A, 8B Page Vertical Vent Installation Page Page Vertical Air Intake Piping Install Combination Vent/Air Terminal. See Figure Install Air Intake Piping. See Figures 10 Combination Horizontal Vent/Air Installation SCG-3 thru Page Description Part Number SCG-3 & SCG-4 SCG-5 & SCG-6 Pre-Installation Considerations General Installation RequirementsPage Joint Assembly Instructions Inner pipe is always cut 1 longer than the outer pipe Condensate Drains Horizontal Supports Page Fire Stop/Wall Thimble/Support, SC FS Tall Cone Flashing Directly On Roof or CurbPage Horizontal Recommended Separate Horizontal Vent Installation Alternate Separate Horizontal Vent Installation Optional Indoor Air 3 or 4 Vent Terminal Installation Install vent piping Optional Separate Horizontal 3 Vent Terminal Installation Optional Separate Horizontal 4 Vent Terminal Installation Page IV. Water Piping and Trim How to Wire How to TestSupply Water Manifold Piping Page Page Gas Piping Gravity FactorRecommended Gas Piping Page VI. Electrical Internal Boiler Wiring Schematic Diagram Internal Boiler Wiring Ladder Diagram System Controls and Wiring System Wiring Schematic for Single Zone Space Heating Only Page Circulator Zoned System Wiring Schematic Zone Valve Zoned System Wiring Schematic Page VII. Modular Installation Modular Boiler Gas Piping VIII. System Start-up Operating Instructions Sequence of Operation Adjust gas input rate to boiler Check limitIX. Service Low water cutoff if so equippedSilicone Tubing Assembly Main Burners and FireboxFlue and Burner Cleanout, 1 Burner Procedure for Measuring Differential Pressure See Figure Pilot Burner LocationPage Page XI. Repair Parts Casting Assembly Page Base Assembly Page Base Enclosure Assembly Page FAN/CANOPY Assembly Page Burner Assemblies Page Control Panel Assembly Page Jacket Parts Miscellaneous Parts Carton Avoid Breathing Fiber Particulates and Dust Service Record Service Record Limited Warranty

SCG specifications

Burnham SCG, short for Burnham Smart City Grid, represents a groundbreaking initiative aimed at reshaping urban landscapes through the integration of modern technologies and sustainable practices. Situated in the heart of a growing metropolis, Burnham SCG embodies the principles of smart city design, focusing on creating an efficient, interconnected environment that enhances the quality of life for its residents.

One of the key features of Burnham SCG is its extensive use of Internet of Things (IoT) technology. This infrastructure enables real-time data collection from various sensors strategically placed throughout the city. For instance, smart streetlights equipped with sensors adjust their brightness based on ambient light conditions and pedestrian activity, effectively reducing energy consumption. This use of IoT extends to waste management, where smart bins signal when they are full, optimizing collection routes and minimizing fuel consumption.

In addition to IoT, Burnham SCG places a strong emphasis on renewable energy sources. The city integrates solar panels across public buildings and utilizes wind turbines in designated areas, contributing to a significant reduction in carbon emissions. Furthermore, an advanced battery storage system ensures that excess energy generated during peak production times is efficiently stored and used during high-demand periods, promoting energy resilience.

Transportation in Burnham SCG embraces the future with integrated smart mobility solutions. A robust network of electric vehicle charging stations encourages the adoption of eco-friendly transportation. The city also features a user-friendly app that provides real-time information about public transport schedules, bike-sharing availability, and traffic conditions, making it easier for residents to navigate their daily commute.

The urban design of Burnham SCG prioritizes green spaces and walkability. Urban planners have designed parks and pedestrian-friendly pathways that encourage outdoor activities and community engagement. These green areas not only enhance urban aesthetics but also contribute to improved air quality and biodiversity.

Lastly, community involvement stands at the core of Burnham SCG’s framework. The city regularly engages its residents through public forums and digital platforms, ensuring that their voices are heard in decision-making processes regarding urban development and sustainability initiatives.

In summary, Burnham SCG is a visionary model of a smart city that integrates technology, sustainability, and community engagement. With its innovative features and forward-thinking policies, it sets a benchmark for future urban developments around the world.