Burnham SCG manual Pre-Installation, Provide combustion and ventilation air in accordance

Page 6

I. Pre-Installation

 

 

F. Provide combustion and ventilation air in accordance

WARNING

 

with applicable provisions of local building codes,

 

 

or: USA - National Fuel Gas Code, NFPA 54/ANSI

If you do not follow these instructions

 

Z223.1, Air for Combustion and Ventilation;

exactly, a fire or explosion may result

 

 

Canada - Natural Gas Installation Code, CAN/

causing property damage or personal

 

 

CGA-B149.1, or Propane Installation Code, CAN/

injury.

 

 

CGA-B149.2, Venting Systems and Air Supply for

 

 

 

 

Appliances.

DANGER

 

 

 

WARNING

 

 

Do not install boiler where gasoline or other

 

 

 

Adequate combustion and ventilation air

flammable vapors or liquids, or sources of

 

 

must be provided to assure proper

hydrocarbons (i.e. bleaches, cleaners,

 

 

combustion.

chemicals, sprays, paint removers, fabric

 

 

 

softeners, etc.) are used or stored.

 

The following guideline is based on the National Fuel Gas

 

 

 

 

 

Code, NFPA 54/ANSI Z223.1.

NOTICE

 

1. Determine volume of space (boiler room). Rooms

 

 

communicating directly with space (through

Due to the low water content of the boiler,

 

openings not furnished with doors) are considered

mis-siz ing of the boiler with regard to the

 

 

part of space.

heating system load will result in excessive

 

 

Volume [ft³] = Length [ft] x Width [ft] x Height [ft]

boiler cycling and accelerated component

 

 

2. Determine Total Input of all appliances in space.

failure. Burnham DOES NOT warrant

 

failures caused by mis-siz ed boiler

 

Round result to nearest 1,000 Btu per hour (Btuh).

applications. DO NOT oversiz e the boiler to

 

3. Determine type of space. Divide Volume by Total

the system. Modular boiler installations

 

Input.

greatly reduce the likelihood of boiler

 

a. If result is greater than or equal to 50 ft³ per

oversiz ing.

 

 

1,000 Btuh, space is considered an unconfined

 

 

A. Installation must conform to the requirements of the

 

space.

 

b. If result is less than 50 ft³ per 1,000 Btuh, space

authority having jurisdiction. In the absence of such

 

 

is considered a confined space.

requirements, installation must conform to the National

 

 

4. Determine building type. A building of unusually

Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/

 

CGA B149 Installation Codes.

 

tight construction has the following characteristics:

B.

Appliance is design certified for installation on

a. Walls and ceiling exposed to outside atmosphere

have a continuous water vapor retarder with a

 

combustible flooring. Do not install boiler on

 

rating of 1 perm or less with openings gasketed

 

carpeting.

 

and sealed, and;

 

 

C.Provide clearance between boiler jacket and combustible material in accordance with local fire ordinance. Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Service clearances may be reduced to minimum clearances to combustible materials.

D.Install on level floor. For basement installation provide solid base such as concrete, if floor is not level or if water may be encountered on floor around boiler. Floor must be able to support weight of boiler, water and all additional system components.

E.Protect gas ignition system components from water (dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).

b.Weather-stripping has been added on openable windows and doors, and;

c.Caulking or sealants applied in joints around window and door frames, between sill plates and floors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.

5.For boiler located in an unconfined space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors.

6

Image 6
Contents SCG Important Information Read Carefully Page Table of Contents Dimensions Appliance is design certified for installation on Pre-InstallationInstallation must conform to the requirements Provide combustion and ventilation air in accordanceII. Unpack Boiler Do not drop boiler. Do not bump boiler jacket against floorIII. Venting / Air Intake Piping See SectionVent System Components Part Number Vent Guidelines Due to Removal of an Existing Boiler General GuidelinesInstall Vent Pipe, Burnham Gasketed Vent System Burnham Gasketed Vent Joint DetailVent Piping Recommended Separate Horizontal Vent/Air Intake Installation Alternate Separate Horizontal Vent/Air Intake Installation Page Page Separate Vertical Venting System See Figures 6, 7, 8A, 8B Page Vertical Vent Installation Page Page Vertical Air Intake Piping Install Combination Vent/Air Terminal. See Figure Install Air Intake Piping. See Figures 10 Combination Horizontal Vent/Air Installation SCG-3 thru Page Description Part Number SCG-3 & SCG-4 SCG-5 & SCG-6 Pre-Installation Considerations General Installation RequirementsPage Joint Assembly Instructions Inner pipe is always cut 1 longer than the outer pipe Condensate Drains Horizontal Supports Page Fire Stop/Wall Thimble/Support, SC FS Tall Cone Flashing Directly On Roof or CurbPage Horizontal Recommended Separate Horizontal Vent Installation Alternate Separate Horizontal Vent Installation Optional Indoor Air 3 or 4 Vent Terminal Installation Install vent piping Optional Separate Horizontal 3 Vent Terminal Installation Optional Separate Horizontal 4 Vent Terminal Installation Page IV. Water Piping and Trim How to Wire How to TestSupply Water Manifold Piping Page Page Gas Piping Gravity FactorRecommended Gas Piping Page VI. Electrical Internal Boiler Wiring Schematic Diagram Internal Boiler Wiring Ladder Diagram System Controls and Wiring System Wiring Schematic for Single Zone Space Heating Only Page Circulator Zoned System Wiring Schematic Zone Valve Zoned System Wiring Schematic Page VII. Modular Installation Modular Boiler Gas Piping VIII. System Start-up Operating Instructions Sequence of Operation Adjust gas input rate to boiler Check limitIX. Service Low water cutoff if so equippedSilicone Tubing Assembly Main Burners and FireboxFlue and Burner Cleanout, 1 Burner Procedure for Measuring Differential Pressure See Figure Pilot Burner LocationPage Page XI. Repair Parts Casting Assembly Page Base Assembly Page Base Enclosure Assembly Page FAN/CANOPY Assembly Page Burner Assemblies Page Control Panel Assembly Page Jacket Parts Miscellaneous Parts Carton Avoid Breathing Fiber Particulates and Dust Service Record Service Record Limited Warranty

SCG specifications

Burnham SCG, short for Burnham Smart City Grid, represents a groundbreaking initiative aimed at reshaping urban landscapes through the integration of modern technologies and sustainable practices. Situated in the heart of a growing metropolis, Burnham SCG embodies the principles of smart city design, focusing on creating an efficient, interconnected environment that enhances the quality of life for its residents.

One of the key features of Burnham SCG is its extensive use of Internet of Things (IoT) technology. This infrastructure enables real-time data collection from various sensors strategically placed throughout the city. For instance, smart streetlights equipped with sensors adjust their brightness based on ambient light conditions and pedestrian activity, effectively reducing energy consumption. This use of IoT extends to waste management, where smart bins signal when they are full, optimizing collection routes and minimizing fuel consumption.

In addition to IoT, Burnham SCG places a strong emphasis on renewable energy sources. The city integrates solar panels across public buildings and utilizes wind turbines in designated areas, contributing to a significant reduction in carbon emissions. Furthermore, an advanced battery storage system ensures that excess energy generated during peak production times is efficiently stored and used during high-demand periods, promoting energy resilience.

Transportation in Burnham SCG embraces the future with integrated smart mobility solutions. A robust network of electric vehicle charging stations encourages the adoption of eco-friendly transportation. The city also features a user-friendly app that provides real-time information about public transport schedules, bike-sharing availability, and traffic conditions, making it easier for residents to navigate their daily commute.

The urban design of Burnham SCG prioritizes green spaces and walkability. Urban planners have designed parks and pedestrian-friendly pathways that encourage outdoor activities and community engagement. These green areas not only enhance urban aesthetics but also contribute to improved air quality and biodiversity.

Lastly, community involvement stands at the core of Burnham SCG’s framework. The city regularly engages its residents through public forums and digital platforms, ensuring that their voices are heard in decision-making processes regarding urban development and sustainability initiatives.

In summary, Burnham SCG is a visionary model of a smart city that integrates technology, sustainability, and community engagement. With its innovative features and forward-thinking policies, it sets a benchmark for future urban developments around the world.