Chromalox CES-6 Operation, Adjusting Operating Pressure Controls, Recommended START-UP Procedures

Page 12

OPERATION

ADJUSTING OPERATING PRESSURE CONTROLS

1.Chromalox boilers are supplied with operating and high limit pres- sure controls. One is used for controlling the operating pressure of the boiler while the other is used as a high limit control. To deter- mine the difference in the controls, the high limit has a manual reset lever on top of the case. Also, there is no differential scale present.

2.On all controls, the pressure adjusting screw on the top of the case sets the desired pressure. Turning the screw counterclockwise reduces the pressure setting (CUT OUT) (See Figure 2). High limit control should be set at 10 psig above the operating pressure of the boiler.

3.The differential adjusting screw on the operating control is set in the same manner as the pressure adjusting screw. The CUT OUT set- ting minus the differential setting, equals CUT IN pressure of the operating control.

 

Differential Adjusting Screw

 

Pressure Adjusting Screw

Differential

 

Setting

Terminal 1 Open on

Indicator

 

Pressure Rise

Pressure

Terminal 2

Setting

Common

Indicator

 

Figure 1

CES-12 through CES-72, one pressure control supplied; CES-100 through CES- 180, two pressure controls supplied.

To check operation of the controls, close steam outlet valve and adjust operating pressure control to a low pressure setting. Also, set high limit control at 10 psig above operating pressure control. Turn on boiler, and allow pressure to build up. When pressure gauge reading approaches set point of pressure control, the switch will trip and shut off boiler. Turn off boiler.

To reset pressure control, bleed off enough pressure in the boiler by opening steam outlet drain, or blowdown valve to allow the operating control to reset.

4.HIGH LIMIT PRESSURE CONTROL OPERATION

The high limit is tested in the same manner but with the operating control set above the pressure setting of the high limit. (Figure 3)

CAUTION: This is for test purposes only!

When the high limit trips, turn off boiler and reset high limit to proper setting. The manual reset level must be pushed to resume operation upon startup.

Pressure

Manual Reset Lever

Adjusting

 

Screw

 

Terminal 1 Open on

Pressure Rise

Terminal 2

CutoutCommon

Pressure

Indicator

Figure 2

OPERATION

RECOMMENDED START-UP PROCEDURES

1.Close globe valve on steam outlet side of boiler. (Customer Supplied)

2.Turn on boiler and allow pressure to build up to operating pressure.

3.Only open globe valve at quarter turns at first, introducing smaller amounts of steam into process. Avoid opening globe valve all at once. This will eliminate the possibility of evacuating the boiler of water caused by the suddenly increased boiling of the water in the vessel as the pressure is reduced. On boilers where constant pres- sure is not maintained, globe valve should be kept partially closed. This will maintain a constant head on the boiler and stabilize any fluctuation in boiler water level.

Note: For best boiler performance, a 1/4” less steam valve

than size of safety valve should be plumbed as close as practi- cable to steam outlet. Where 1/2” safety valve is used on boil- er, a 1/4” steam valve is recommended.

MANUAL BLOWDOWN INSTRUCTIONS

Blowdown is an essential part of boiler operation. It is the best preventative maintenance you can give your boiler and will add years of life to the unit. Make sure a blowdown schedule is estab- lished and followed regularly.

In extremely hard water areas, blowdown is necessary once a day. In soft water areas, once each week. If there is a particular problem which applies to your own local water condition other

than mineral content, take this into consideration in determining which schedule is to be followed.

1.At end of the working day, while boiler is still operating, turn switch to the OFF position and close water supply valve. De-ener- gize wall mounted safety switch.

2.If blowing-down into a receptacle, allow pressure to decrease to 15-20 psi before opening blowdown valve.

3.It is preferable to connect the blowdown valve directly into a drainage system. If this is done, the boiler can be discharged at operating pressure.

4.When discharge is complete and boiler is drained — (a) close the blowdown valve; (b) open water supply valve; (c) put boiler switch in the ON position; and, (d) close wall mounted safety switch.

5.When refilling is complete, turn off the boiler switch unless further operation is desirable.

6.If you have been supplied with a Manual Reset Low Water control as required in some states, the reset button on the control must be pushed before boiler will begin developing pressure. (Do not push reset until boiler has filled with water.)

The use of chemical boiler cleaning compounds in these boilers voids all warranties unless approved by manufacturer. Some com- pounds will damage copper sheathed heating elements to shorten useful life.

12

Image 12
Contents Chromalox Dimensions Model CES-6 through CES-18Installation ModelWiring Typical Wiring DiagramsDiagram Boiler 208 240 480Boilers under 40 Amps total not fused Black Diagram Diagram Black Brown Blue White PRE-OPERATION Check Miller LOW Water Cutoff ControlAdjusting Operating Pressure Controls Recommended START-UP ProceduresOperation High Limit Pressure Control OperationAutomatic Blowdown Instructions If FurnishedOptional Equipment for Steam Boilers Boiler Sequence Solid State Solid State Progressive SequencerPump Motor Dimensions Water Feed SystemsLOW Pressure Feed High Pressure FeedMaintenance Installation WiringPlumbing SequenceMaintenance Immersion Heater Failure Causes Renewal Parts Identification Part Description Part NumberLimited Warranty Valves & Gauges

CES-6 specifications

The Chromalox CES-6 is a state-of-the-art electric heating solution designed for industrial and commercial applications. This versatile unit offers a range of features that enhance its efficiency, durability, and ease of use. With a focus on advanced technology, the CES-6 is engineered to meet the demands of various heating requirements, from process heating to temperature maintenance.

One of the standout features of the CES-6 is its robust construction. Built to withstand harsh environments, it is made from high-quality materials that ensure longevity and reliability. The unit's enclosure is resistant to moisture and dust, making it ideal for applications in challenging conditions. This durability ensures that the CES-6 can operate effectively in settings such as manufacturing plants, warehouses, and outdoor installations.

The CES-6 leverages cutting-edge heating technologies, including advanced thermal management systems. This feature allows for precise temperature control, ensuring optimal performance and energy efficiency. By utilizing programmable temperature settings, users can customize their heating profiles to match specific operational needs, reducing energy consumption and operating costs.

Another significant characteristic of the CES-6 is its ease of installation and maintenance. Designed with user convenience in mind, the unit comes equipped with adaptable mounting options and user-friendly interfaces. This makes it straightforward for technicians to install and service, minimizing downtime and enhancing productivity.

Safety is a top priority with the CES-6, which incorporates multiple safety features to protect users and equipment. Over-temperature protection, built-in alarm systems, and fail-safe mechanisms are just a few of the safeguards included. These features not only enhance user safety but also contribute to the overall integrity of the heating process.

In conclusion, the Chromalox CES-6 stands out in the market for its combination of durability, advanced technology, and user-friendly design. Its robust construction makes it suitable for demanding industrial settings, while its energy-efficient heating capabilities and ease of installation ensure it meets the needs of a wide range of applications. Whether you are looking for reliable heating for your manufacturing processes or need a dependable solution for temperature maintenance, the CES-6 is an exceptional choice that delivers performance and efficiency.