B.Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler will automatically restart once the condition that caused the lockout is corrected.

Table 14.3: Soft Lockout Codes Displayed

CODE

CONDITION

POSSIBLE CAUSES

 

 

• Blockage in intake or vent system.

 

 

• Vent and/or intake system not constructed in accordance

 

 

with Part VII.

b 08

Pressure switch circuit open.

• Blocked or leaking pressure switch tubing.

 

 

• Heat exchanger or burner blockage.

 

 

• Terminals exposed to high winds.

 

 

• Blockage in condensate trap above vent.

 

 

 

 

 

• Heating load at time of error was far below the minimum

 

 

firing rate of the boiler.

b 18

MCBA supply sensor detected temperatures in excess

• Defective primary pump or no flow in primary loop (Piping

of 200°F.

Method 1).

 

 

 

• Control system miswired so that boiler operation is

 

 

permitted when no zones are calling.

 

 

 

b 19

MCBA return sensor detected temperatures in excess of

• See possible causes for “b18”.

200°F.

• Flow through boiler reversed.

 

 

 

• Sensor wiring reversed.

 

 

 

 

 

• Flow through boiler reversed. Verify correct piping and

 

MCBA is reading a return sensor temperature higher

pump orientation.

 

• No boiler water flow. Verify that system is purged of air

b 24

than the supply sensor temperature. Condition must be

and that appropriate valves are open.

 

present for at least 75s for this error code to appear.

 

• Sensor wiring reversed.

 

 

 

 

• Supply or return sensor defective.

 

 

 

 

 

• See possible causes for “b18”.

b 25

Supply water temperature has risen too quickly.

• Inadequate boiler water flow. Verify that pump is

operating and that pump and piping are sized per Part IX

 

 

 

 

of this manual.

 

 

 

b 26

Boiler safety limit, or external limit wired across terminals

• See possible causes for “b18”.

3&4, is open.

• Defective supply sensor.

 

 

 

 

 

 

• Inadequate boiler water flow. Verify that pump is

b 30

Temperature rise between supply and return is too high.

operating and that pump and piping are sized per Part IX

 

 

of this manual.

 

 

• Blockage in pressure switch hose.

 

 

• Pressure switch wires shorted together.

b 61

Pressure switch circuit closed with fan off.

• Defective pressure switch.

 

 

• Loose or miswired fan speed harness (if “b61” error code

 

 

is observed while fan is running).

 

 

 

b 65

Fan is not achieving set point speed.

• Loose or incorrect fan speed control connection.

• Defective fan.

 

 

 

 

 

71

Image 73
Contents Page Page III Page III Before Installing Page Clearances From Vent Piping To Combustible Construction Page Page Page VI Air for Ventilation Page VII Venting Page Summary of Horizontal Venting Options Page Vent Option Manufacturer Vent Size Component Part Number Page Snorkel Terminal Configuration VENT/ AIR Intake Fitting Equivalent Length 10 Vertical Twin Pipe Vent System Vent Option Removing an Existing Boiler From a Common Chimney Page Page Page Page 30a Cuttable Straight Section Page Page Page Page Page Page Page Page Page 47 CORR/GUARD Connection to Vent Collar 48 Z-VENT III Connection to Vent Collar 49 SAF-T Vent EZ Seal Connection to Vent Collar Page Condensate Trap and Drain Line Page Page IX System Piping Page Page Page Page Pipe and Circulator Sizing for Indirect Water Heater Loop Page Boiler Head Loss Piping for Special Situations Page Wiring Page Page Page XI Start-up and Checkout Page For Your Safety Read Before Lighting Page Page Page Page Page Page Page Outdoor Reset Curve XIII. Service and Maintenance Page Page Soft Lockout Codes Displayed Page XV Parts Page Page Page Page