A.O. Smith 1000, 200, 201, 2500, 2100, 1850, 1300, 1500 System Installation, Hydronic Installation

Page 15

SYSTEM INSTALLATION

GENERAL

If the system is to be filled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent a down draft entering the boiler or freezing air from contacting the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system. Damage due to freezing is not covered by the warranty.

Good practice requires that all piping, etc., be properly supported.

The boilers described in this manual may be used for space (hydronic) heating or for the heating of potable water. If the heater is to be used for hydronic space heating, follow the instructions on pages 15-17 given for equipment required for installation as in Figure 10. However, if units are to be used for heating potable water, the information describing specific systems is found on pages 17-19. See figures 11 and 13. Installations must comply with all local codes.

HYDRONIC INSTALLATION

The following is a brief description of the equipment required for installations noted in this manual. All installations must comply with local codes (see figure 10).

Table 12: INSTALLATION ITEMS

NO.

SUGGESTED ITEMS FOR INSTALLATION

1.

PAIR OF SHORT PIPE NIPPLES, PAIR OF BOILER

 

LOOP TEES AND BALL VALVE BETWEEN SYSTEM

 

SUPPLY AND RETURN - ONE SET PER EACH BOILER

2.

BOILER PIPE LOOP (See Sizing Data Table 4.)

3.

BOILER CIRCULATING PUMP (See Sizing Data Table 4.)

4.

THERMOMETER

5.

PRESSURE GAUGE

6.

LOW WATER CUTOFF (If Required By Local Code.)

7.

SAFETY FLOW SWITCH (Factory-Installed)

8.

RELIEF VALVE (Factory-Installed)

9.

BOILER INLET - OUTLET

10.

SYSTEM SUPPLY TEMPERATURE THERMOMETER

11.

DRAIN or BLOW-DOWN VALVE

 

WATER SUPPLY LINE

These boilers can be used ONLY in a forced circulation hot water heating system. The pump must be interlocked with the boiler to prevent boiler operation without water circulation. See maximum and minimum flow rate information. Since most forced circulation systems will be of the closed type, install the water supply line as shown on piping diagram, figure 10. Severe damage will occur if the boiler is operated without proper water flow circulation.

Fast filling of large pipe, old radiator installations (where high pressures are not available) requires bypassing of the pressure reducing valve. Generally, pressure purging is not possible with a well pump system. High point air venting is essential. For details, refer to OPERATION section of this manual on page 22.

If the system is of the open type, a pressure reducing valve will not be required as the water supply to the system will be controlled by a manually operated valve. An overhead surge tank is required. A MINIMUM PRESSURE OF 15 PSI (100 kPa) MUST BE MAINTAINED ON THE BOILER AT ALL TIMES to avoid potential damage to the boiler that may not be covered by the warranty.

CONVENTIONAL SPACE HEATING INSTALLATION

Modern fin type boilers are exceptionally fast heating units. The low water volumes in relation to firing rates require special attention to water flow rates for smooth, efficient operation. These considerations for the A. O. Smith copper heat exchanger boilers are covered below.

Refer to table 4 showing flow rate vs. pressure drop and temperature rise.

Figure 10 shows a typical installation of the boiler.

A system with several flow controlled zones, or with a 3-way mixing valve system could present a flow rate to the boiler of less than required for a maximum of 50°F (28°C) temperature rise. Design system with compensating bypasses to the boiler.

A system bypass should be installed as shown in figure 10 to prevent boiler circulation starvation when the system zones call for reduced flow.

This bypass may also be used with multiple boilers manifolded for reverse-return flow. The system bypass would be installed from boiler outlet to suction side of pump.

The boiler piping system of a hot water heating boiler connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. It is highly recommended that the piping be insulated.

INSTALLATION AS BOILER REPLACEMENT

Installation as boiler replacement on an old system with large water volume may result in condensation within the boiler on cold starts. This condensing of water vapor in the combustion area can be prevented if a portion of the system water flow is diverted past the boiler to cause an increase in boiler temperature rise.

BYPASS BALANCING

With systems where water temperature can be expected to drop appreciably due to long standby periods, or heavy draw down, a bypass pipe of at least 1" size with a balancing cock should be installed between the boiler inlet and outlet (see figure 10). When the system first starts, the valve should be slowly opened until the condensing ceases. This adjustment remains at a permanent setting to establish required temperature rise across the boiler.

AIR SEPARATOR

An air separator as shown in the piping diagram is reccommended especially for modern commercial hydronic systems.

VENT VALVES

It is recommended that automatic, loose key or screwdriver type vent valves be installed at each convector or radiator.

SYSTEM HEADERS

Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with minimum pressure drop for several circuits, manifolds should be larger than system loops.

15

Image 15
Contents Limited Warranty For buying this cost efficient, high recovery unit fromROUGH-IN Dimensions GAS and Electrical CharacteristicsRough in Dimensions Heat Exchanger Pressure Drop Recovery CapacitiesCorrect GAS High Altitude InstallationForeword Grounding InstructionsFEATURES/CONTROLS Required Ability Installation InstructionsSafety Relief Valves Circulating PumpAIR Requirements Installation ClearancesChemical Vapor Corrosion LevellingConfined Space Connecting Boiler to a Common VentVenting Unconfined SpaceLocation Requirements INTAKE/EXHAUST Intake/Exhaust Installation Requirements See figure16 40.6 cm Standard Vent Vertical CategoryType B or EquivalentSteel Standard Vent Horizontal CategoryVenting Vent Size Vent Length Material Inches Feet III Stainless Direct Vent Vertical Category Direct Vent Vertical Exhaust ConfigurationsDirect Vent Horizontal Category Direct Vent Horizontal Exhaust ConfigurationsStandard Horizontal VENTING, Category Horizontal Vent InstallationVent Connector Model Number Standard Vertical VENTING, CategoryHydronic Installation System InstallationSpace Heating Applications Cooling PipingHOT Water Supply Boiler Installation Single boiler with horizontal tank Single boiler with vertical tank Suggested Pipe Size For Multiple Gas Appliances Propane Gas Btuh Single Unit INSTALLATION, Suggested Pipe SizeGAS Connections Distance from Meter BTU InputOperation Wiring ConnectionsFilling and Purging for Heating Boiler Installation Filling for HOT Water Supply Boiler InstallationManifold Pressure AdjustmentsPurging of GAS Line Inlet GAS PressureFor Your Safety Read Before Operating For Your Safety Read Before Operating DIA-SCAN II Display Board Operating Procedures Control SystemDescription of MULTI-STAGE Firing System Options/Features Setting Procedures Red Fault LightsGreen Status Lights Inlet Probe Temperature ProbesYellow Parameter Set Lights Outlet ProbeStage One Procedure for Setting Tank Probe TemperatureProcedure for Setting Stage Differential Application Hydronic HeatingAppliance Operating Sequence Procedure for Setting Pump DelayLast Error Mode Display Stage Cycle CountMain Burners Preventative MaintenanceDeliming Replacement Parts Troubleshooting Ignition SystemLED Power Vent No GAS Valve Power SensedCirculate Fault Flow Switch Insufficient AIR AIR Pressure Switch StageNEW Boiler Limited Warranty Replacement Parts