A.O. Smith 200, 201, 2500, 2100, 1850, 1300, 1500, 1000 Cooling Piping, Space Heating Applications

Page 16

The circuits should be spaced on the header at a minimum of 3" (7.6 cm) center to center. Install a balancing cock in each return line.

Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow.

COOLING PIPING

When the boiler is used in conjunction with a refrigeration system it must be installed so that the chilled medium is piped in parallel with the boiler. Appropriate valves, manual or motorized, must be provided to prevent the chilled medium from entering the boiler.

Water temperature in the heating system must be reduced to less than 100°F before cooling system is started, or damage to the chiller unit may occur.

If the boiler is connected to chilled water piping or heating coils exposed to refrigerated air, the boiler piping system must be equipped with flow control valves or other automatic means to prevent gravity circulation through the boiler during the cooling cycle. Primary/secondary pumping of both the chiller(s) and the boiler(s) is an excellent winter-summer change-over method, because cooling flow rates are much more than heating flow rates. In this way each system (heating or cooling) is circulated independently.

SPACE HEATING APPLICATIONS

Controlling of these systems is decided mainly by the type of building system controlling that is desired. A single boiler

Figure 10. Single or Multiple Boiler Installation Diagram

installation might be controlled directly from space temperature thermostat(s). Multiple boiler installations are more effective when the boilers are sequenced in and out of operation by some form of main water temperature controller. With one or two boilers, individual control settings at progressive temperature may be used. For more than two boilers, electronic sequencing controlling is recommended.

Individual controls, or the separate stages of a step controller, should fire a boiler and also start the boiler loop circulator whenever that boiler is fired. Some large installations may require the firing of more than one boiler per stage.

The system or primary circulator may or may not be controlled by the boiler sequencer. When this pump is operated through the first switch of any type of step controller, care should be taken to determine if a motor starter is needed due to insufficient switch capacity.

If the primary pump is controlled by a manual switch or any other controllers, the electric current supply to the boiler group should be through the primary pump controller. The fast response of A.O. Smith boilers eliminates any need to maintain boiler temperature when the system is satisfied. Wiring should always prevent firing of boiler(s) when there is no water flow in the mains.

Installation diagrams show safety flow switches in the outlet piping from each boiler as good protection against any boiler being fired when the boiler loop circulator is not in operation. These safety flow switches will also provide some protection if there is a loss of water.

Multiple boiler installations are especially adapted to the use of outdoor reset for main water temperatures. This feature is not

16

Image 16
Contents For buying this cost efficient, high recovery unit from Limited WarrantyGAS and Electrical Characteristics ROUGH-IN DimensionsRough in Dimensions Recovery Capacities Heat Exchanger Pressure DropHigh Altitude Installation ForewordGrounding Instructions Correct GASFEATURES/CONTROLS Installation Instructions Safety Relief ValvesCirculating Pump Required AbilityInstallation Clearances Chemical Vapor CorrosionLevelling AIR RequirementsConnecting Boiler to a Common Vent VentingUnconfined Space Confined SpaceIntake/Exhaust Installation Requirements See figure Location Requirements INTAKE/EXHAUSTStandard Vent Vertical Category Type B orEquivalent 16 40.6 cmStandard Vent Horizontal Category Venting Vent Size Vent Length Material Inches FeetIII Stainless SteelDirect Vent Vertical Exhaust Configurations Direct Vent Vertical CategoryDirect Vent Horizontal Exhaust Configurations Direct Vent Horizontal CategoryHorizontal Vent Installation Vent Connector Model NumberStandard Vertical VENTING, Category Standard Horizontal VENTING, CategorySystem Installation Hydronic InstallationCooling Piping Space Heating ApplicationsHOT Water Supply Boiler Installation Single boiler with horizontal tank Single boiler with vertical tank Suggested Pipe Size For Multiple Gas Appliances Propane Gas Single Unit INSTALLATION, Suggested Pipe Size GAS ConnectionsDistance from Meter BTU Input BtuhWiring Connections Filling and Purging for Heating Boiler InstallationFilling for HOT Water Supply Boiler Installation OperationAdjustments Purging of GAS LineInlet GAS Pressure Manifold PressureFor Your Safety Read Before Operating For Your Safety Read Before Operating Control System DIA-SCAN II Display Board Operating ProceduresDescription of MULTI-STAGE Firing System Red Fault Lights Options/Features Setting ProceduresGreen Status Lights Temperature Probes Yellow Parameter Set LightsOutlet Probe Inlet ProbeProcedure for Setting Tank Probe Temperature Procedure for Setting Stage DifferentialApplication Hydronic Heating Stage OneProcedure for Setting Pump Delay Last Error ModeDisplay Stage Cycle Count Appliance Operating SequencePreventative Maintenance Main BurnersDeliming Troubleshooting Ignition System Replacement PartsLED No GAS Valve Power Sensed Circulate Fault Flow SwitchInsufficient AIR AIR Pressure Switch Stage Power VentNEW Boiler Limited Warranty Replacement Parts