A.O. Smith 1300, 200, 201 GAS Connections, Single Unit INSTALLATION, Suggested Pipe Size, Btuh

Page 21

GAS CONNECTIONS

WARNING

THIS BOILER IS NOT INTENDED TO OPERATE AT GAS SUPPLY PRESSURE OTHER THAN SHOWN ON THE RATING PLATE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS.

WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUT-OFF VALVE OUTSIDE THE BOILER JACKET,ASUITABLE MAIN MANUAL SHUT-OFF VALVE MUST BE INSTALLED IN A LOCATION COMPLYING WITH THOSE CODES.

threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

THE BOILER MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS MAIN MANUAL GAS SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR MORE THAN 1/2 PSIG.

1.CORRECT GAS - Make sure gas on which the boiler will operate is the same as that specified on the rating plate. Do not install the boiler if equipped with a different type of gas. Consult your gas supplier.

2A. SIZING GAS SUPPLY LINE (For single boiler installations). See table 15.

2B. SIZING GAS SUPPLY LINE (For multiple installations of two or more boilers). See tables 13 (Natural Gas) and 14 (Propane Gas).

IT IS IMPORTANT TO GUARDAGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION. IF COPPER SUPPLY LINES ARE USED THEY MUST BE APPROVED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG) MUST BE INCORPORATED IN THE PIPING. THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOM- MENDATIONS OF SERVING GAS SUPPLIERS. REFER TO NATIONAL FUEL GAS CODE, ANSI Z223.1 OR CAN/CSA -B149.1 AND .2 (AND LATEST ADDENDA).

Gas Pipe sizing may be larger than heater connections on installations where a significant run of piping is required. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas inlet.

Fittings and unions in the gas line must be metal to metal type.

Apply joint compounds (pipe dope) sparingly and only to the male

TABLE 15. SINGLE UNIT INSTALLATION, SUGGESTED PIPE SIZE

DISTANCE FROM METER

BTU INPUT

0-50'

51-100'

101-200'

201-300'

301-500'

 

990,000

2"

2"

2 1/2"

2 1/2"

2 1/2"

 

1,300,000

2"

2 1/2"

2 1/2"

3"

3"

 

1,500,000

2"

2 1/2"

3"

3"

3 1/2"

 

1,850,000

2 1/2"

2 1/2"

3"

3"

3 1/2"

 

2,100,000

2 1/2"

3"

3"

3 1/2"

4"

 

2,500,000

2 1/2"

3"

4"

4"

4 1/2"

 

 

 

 

 

 

 

 

Use tables 13 or 14, which are taken from ANSI booklet Z223.1, NATIONAL FUEL GAS CODE, or CAN/CSA-B149.1and .2 (and latest addenda) to size iron pipe or equivalent gas supply line. Table 13 is based on a pressure drop of 0.5 inches of water and a specific gravity of 0.60 approximately that of natural gas. (LP gas has an S.G. of about 1.53). If the service pressure is five inches water column or less, use one pipe size larger than specified in tables 13-15 in order to minimize pressure drop in the line.

No additional allowance is necessary for an ordinary number of fittings. Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop.

TABLE 16. Orifice Size for Natural and Propane (LP) Gases (U.S. and Canadian Installations) [Drill size unless otherwise indicated.]

 

Rating Input

Number of

 

 

Model

BTUH

Burners

Natural (Holes)

Propane (Holes)

GB/GW 1000

990,000

10

0.111" (4X)

0.071" (3X)

GB/GW 1300

1,300,000

13

0.111" (4X)

0.071" (3X)

GB/GW 1500

1,500,000

15

0.111" (4X)

0.071" (3X)

GB/GW 1850

1,850,000

19

0.111" (4X)

0.071" (3X)

GB/GW 2100

2,100,000

21

0.111" (4X)

0.071" (3X)

GB/GW 2500

2,490,000

25

0.111" (4X)

0.071" (3X)

21

Image 21
Contents Limited Warranty For buying this cost efficient, high recovery unit fromROUGH-IN Dimensions GAS and Electrical CharacteristicsRough in Dimensions Heat Exchanger Pressure Drop Recovery CapacitiesForeword High Altitude InstallationGrounding Instructions Correct GASFEATURES/CONTROLS Safety Relief Valves Installation InstructionsCirculating Pump Required AbilityChemical Vapor Corrosion Installation ClearancesLevelling AIR RequirementsVenting Connecting Boiler to a Common VentUnconfined Space Confined SpaceLocation Requirements INTAKE/EXHAUST Intake/Exhaust Installation Requirements See figureType B or Standard Vent Vertical CategoryEquivalent 16 40.6 cmVenting Vent Size Vent Length Material Inches Feet Standard Vent Horizontal CategoryIII Stainless SteelDirect Vent Vertical Category Direct Vent Vertical Exhaust ConfigurationsDirect Vent Horizontal Category Direct Vent Horizontal Exhaust ConfigurationsVent Connector Model Number Horizontal Vent InstallationStandard Vertical VENTING, Category Standard Horizontal VENTING, CategoryHydronic Installation System InstallationSpace Heating Applications Cooling PipingHOT Water Supply Boiler Installation Single boiler with horizontal tank Single boiler with vertical tank Suggested Pipe Size For Multiple Gas Appliances Propane Gas GAS Connections Single Unit INSTALLATION, Suggested Pipe SizeDistance from Meter BTU Input BtuhFilling and Purging for Heating Boiler Installation Wiring ConnectionsFilling for HOT Water Supply Boiler Installation OperationPurging of GAS Line AdjustmentsInlet GAS Pressure Manifold PressureFor Your Safety Read Before Operating For Your Safety Read Before Operating DIA-SCAN II Display Board Operating Procedures Control SystemDescription of MULTI-STAGE Firing System Options/Features Setting Procedures Red Fault LightsGreen Status Lights Yellow Parameter Set Lights Temperature ProbesOutlet Probe Inlet ProbeProcedure for Setting Stage Differential Procedure for Setting Tank Probe TemperatureApplication Hydronic Heating Stage OneLast Error Mode Procedure for Setting Pump DelayDisplay Stage Cycle Count Appliance Operating SequenceMain Burners Preventative MaintenanceDeliming Replacement Parts Troubleshooting Ignition SystemLED Circulate Fault Flow Switch No GAS Valve Power SensedInsufficient AIR AIR Pressure Switch Stage Power VentNEW Boiler Limited Warranty Replacement Parts