A.O. Smith 1850, 200, 201, 2500, 2100 Suggested Pipe Size For Multiple Gas Appliances Propane Gas

Page 20

Table 13. Suggested Pipe Size For Multiple Gas Appliances (Natural)

 

 

 

 

Maximum Capacity of Pipe in BTU/hr and kW for Gas Pressures of 14 in. W.C. (0.5 psi) or Less and a Pressure Drop of 0.5 in. W.C.

 

Nominal

 

 

 

 

(based on 0.60 Specific Gravity Gas w/Heating Value of 1,000 BTU’s/Ft3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length of Pipe in Feet (Metres)

 

 

 

 

 

 

Iron Pipe

 

 

 

 

 

 

 

 

 

 

 

Size

Cap.

10 Ft.

20 Ft.

30 Ft.

40 Ft.

50 Ft.

60 Ft.

70 Ft.

80 Ft.

90 Ft.

100 Ft.

125 Ft.

150 Ft.

175 Ft.

200 Ft.

(Inches)

 

(3.05)

(6.10)

(9.14)

(12.19)

(15.24)

(18.29)

(21.34)

(24.38)

(27.43)

(30.48)

(38.10)

(45.72)

(53.34)

(60.96)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/4"

 

BTU/hr

1,400,000

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

 

 

kW

410

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

1 1/2"

 

BTU/hr

2,100,000

1,460,000

1,180,000

990,000

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

 

 

kW

615

428

346

290

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

2"

 

BTU/hr

3,950,000

2,750,000

2,200,000

1,900,000

1,680,000

1,520,000

1,400,000

1,300,000

1,220,000

1,150,000

1,020,000

- - -

- - -

- - -

 

 

kW

1,157

805

644

556

492

445

410

381

357

337

299

- - -

- - -

- - -

2 1/2"

 

BTU/hr

6,300,000

4,350,000

3,520,000

3,000,000

2,650,000

2,400,000

2,250,000

2,050,000

1,950,000

1,850,000

1,650,000

1,500,000

1,370,000

1,280,000

 

 

kW

1,845

1,274

1,031

879

776

703

659

600

571

542

483

439

401

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3"

 

BTU/hr

11,000,000

7,700,000

6,250,000

5,300,000

4,750,000

4,300,000

3,900,000

3,700,000

3,450,000

3,250,000

2,950,000

2,650,000

2,450,000

2,280,000

 

 

kW

3,222

2,255

1,830

1,552

1,391

1,259

1,142

1,084

1,010

952

864

776

718

668

4"

 

BTU/hr

23,000,000

15,800,000

12,800,000

10,900,000

9,700,000

8,800,000

8,100,000

7,500,000

7,200,000

6,700,000

6,000,000

5,500,000

5,000,000

4,600,000

 

 

kW

6,736

4,627

3,749

3,192

2,841

2,577

2,372

2,197

2,109

1,962

1,757

1,611

1,464

1,347

20

Table 14. Suggested Pipe Size For Multiple Gas Appliances (Propane Gas)

 

 

Maximum Capacity of Pipe in BTU/hr and kW for Gas Pressures of 14 in. W.C. (0.5 psi) or Less and a Pressure Drop of 0.5 in. W.C.

 

Nominal

 

 

 

(based on 1.53 Specific Gravity Gas w/Heating Value of 2,500 BTU’s/Ft3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length of Pipe in Feet (Metres)

 

 

 

 

 

 

 

Iron Pipe

 

 

 

 

 

 

 

 

 

 

 

 

Size

Cap.

10 Ft.

20 Ft.

30 Ft.

40 Ft.

50 Ft.

60 Ft.

70 Ft.

80 Ft.

90 Ft.

 

100 Ft.

125 Ft.

150 Ft.

175 Ft.

200 Ft.

(Inches)

 

(3.05)

(6.10)

(9.14)

(12.19)

(15.24)

(18.29)

(21.34)

(24.38)

(27.43)

(30.48)

(38.10)

(45.72)

(53.34)

(60.96)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1"

BTU/hr

1,060,800

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

 

kW

311

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

1 1/4"

BTU/hr

2,184,000

1,482,000

1,201,200

1,029,600

- - -

- - -

- - -

- - -

- - -

 

- - -

- - -

- - -

- - -

- - -

 

kW

640

434

352

302

- - -

- - -

- - -

- - -

- - -

 

- - -

- - -

- - -

- - -

- - -

1 1/2"

BTU/hr

3,276,000

2,277,600

1,840,800

1,544,400

1,404,000

1,263,600

1,170,000

1,076,400

1,014,000

 

- - -

- - -

- - -

- - -

- - -

 

kW

959

667

539

452

411

370

343

315

297

- - -

- - -

- - -

- - -

- - -

2"

BTU/hr

6,162,000

4,290,000

3,432,000

2,964,000

2,620,800

2,371,200

2,184,000

2,028,000

1,903,200

1,794,000

1,591,200

1,482,000

1,326,000

1,248,000

 

kW

1,805

1,256

1,005

868

768

694

640

594

557

525

466

434

388

366

2 1/2"

BTU/hr

9,828,000

6,786,000

5,491,200

4,680,000

4,134,000

3,744,000

3,510,000

3,198,000

3,042,000

2,886,000

2,574,000

2,340,000

2,137,200

1,999,800

 

kW

2,878

1,987

1,608

1,371

1,211

1,097

1,028

937

891

845

754

685

626

585

3"

BTU/hr

17,160,000

12,012,000

9,750,000

8,268,000

7,410,000

6,708,000

6,084,000

5,772,000

5,382,000

5,070,000

4,602,000

4,134,000

3,822,000

3,556,800

4"

kW

5,026

3,518

2,856

2,421

2,170

1,965

1,782

1,690

1,576

1,485

1,348

1,211

1,119

1,042

BTU/hr

35,880,000

24,648,000

19,968,000

17,004,000

15,132,000

13,728,000

12,636,000

11,700,000

11,232,000

10,452,000

9,360,000

8,580,000

7,800,000

7,176,000

 

kW

10,508

7,219

5,848

4,980

4,432

4,021

3,701

3,427

3,290

3,061

2,741

2,513

2,284

2,102

Image 20
Contents For buying this cost efficient, high recovery unit from Limited WarrantyRough in Dimensions ROUGH-IN DimensionsGAS and Electrical Characteristics Recovery Capacities Heat Exchanger Pressure DropHigh Altitude Installation ForewordGrounding Instructions Correct GASFEATURES/CONTROLS Installation Instructions Safety Relief ValvesCirculating Pump Required AbilityInstallation Clearances Chemical Vapor CorrosionLevelling AIR RequirementsConnecting Boiler to a Common Vent VentingUnconfined Space Confined SpaceIntake/Exhaust Installation Requirements See figure Location Requirements INTAKE/EXHAUSTStandard Vent Vertical Category Type B orEquivalent 16 40.6 cmStandard Vent Horizontal Category Venting Vent Size Vent Length Material Inches FeetIII Stainless SteelDirect Vent Vertical Exhaust Configurations Direct Vent Vertical CategoryDirect Vent Horizontal Exhaust Configurations Direct Vent Horizontal CategoryHorizontal Vent Installation Vent Connector Model NumberStandard Vertical VENTING, Category Standard Horizontal VENTING, CategorySystem Installation Hydronic InstallationCooling Piping Space Heating ApplicationsHOT Water Supply Boiler Installation Single boiler with horizontal tank Single boiler with vertical tank Suggested Pipe Size For Multiple Gas Appliances Propane Gas Single Unit INSTALLATION, Suggested Pipe Size GAS ConnectionsDistance from Meter BTU Input BtuhWiring Connections Filling and Purging for Heating Boiler InstallationFilling for HOT Water Supply Boiler Installation OperationAdjustments Purging of GAS LineInlet GAS Pressure Manifold PressureFor Your Safety Read Before Operating For Your Safety Read Before Operating Description of MULTI-STAGE Firing System DIA-SCAN II Display Board Operating ProceduresControl System Green Status Lights Options/Features Setting ProceduresRed Fault Lights Temperature Probes Yellow Parameter Set LightsOutlet Probe Inlet ProbeProcedure for Setting Tank Probe Temperature Procedure for Setting Stage DifferentialApplication Hydronic Heating Stage OneProcedure for Setting Pump Delay Last Error ModeDisplay Stage Cycle Count Appliance Operating SequencePreventative Maintenance Main BurnersDeliming LED Replacement PartsTroubleshooting Ignition System No GAS Valve Power Sensed Circulate Fault Flow SwitchInsufficient AIR AIR Pressure Switch Stage Power VentNEW Boiler Limited Warranty Replacement Parts