AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

AIR FOR COMBUSTION AND VENTILATION

7

Ventilation Air

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

(see options 1 and 2, Figure 2). You can also remove door into

Room,

Or

Option 2

adjoining room (see option 3, Figure 2). Follow the National Fuel

Option 1

Remove

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

For morevisit www..com

107070-01F

Image 7
Contents What to do if YOU Smell GAS Unvented VENT-FREE GAS LOG HeaterSafety Information Table of ContentsSafety Information Flame-MaxBirch Logs Product IdentificationUnpacking Optional Remote Control AccessoriesProduct Features Local CodesConfined and Unconfined Space Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationLOG Sizing Requirements Minimum Noncombustible Material Clearances If Not Using MantelFloor Clearances Mantel ClearancesDetermining Minimum Mantel Clearance Area of Various Standard Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Installation Items NeededLogs, pages 15 External Regulator With Vent Pointing Down Connecting to GAS SupplyChecking GAS Connections Pressure Testing gas Supply Piping systemPressure Testing Heater Gas Connections Installing LogsInstalling Vintage Oak One-Piece Log Set Lighting Instructions Operating HeaterShutting Off Heater Manual Lighting ProcedureTo Turn OFF GAS To Appliance Thermostat Control OperationVariable Control Operation REMOTE-READY Models For Your Safety Read Before LightingFlame Adjustment Knob ON/OFF Series Model Ghrcb Optional HAND-HELD Remote OperationThermostat Series Model Ghrctb Inspecting BurnersPilot Flame Pattern Main Burner Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Burner Primary AIR HolesObserved Problem Possible Cause Remedy TroubleshootingClean burner see Cleaning and Mainte Gas leak. See Warning statement For Masonry and FACTORY-BUILT Metal Fireplace Optional Positioning of Thermostat Sensing BulbThermostat-Controlled Models Only Specifications Technical Service Wiring DiagramService Hints Replacement PartsVYS24NA, H24N, VYS30PA VYS30NA Illustrated Parts BreakdownODS Pilot Natural Gas ODS Pilot Propane/LP Variable MANUALLY-CONTROLLED FLAME-MAXVINTAGE OAK LOG Models Parts ListVYD36PA Parts Available not Shown ODS Pilot Natural Gas Variable MANUALLY-CONTROLLED FLAME-MAXGOLDEN OAK LOG AND1BBurner Retainer Spring VYD24NTA, VYD30PTA and VYD30NTA THERMOSTAT-CONTROLLED FLAME-MAXGOLDEN OAK LOG Models VYD36PRA and HD36PR REMOTE-READY FLAME-MAXGOLDEN OAK LOG Models VYD36NRA and HD36NR Parts List VYBD24NR, VYBD30PR and VYBD30NR REMOTE-READY FLAME-MAXBIRCH LOG Models Accessories Owners Registration Form Postage Required 107070-01F Warranty Information