For Vertical Runs - The vent system must be supported every eight (8) feet (2.4m) above the fireplace flue outlet by wall brackets.

To install support brackets for vertical runs:

Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws.

WALL BRACKET

WALL STUD

8 FT. (2.4m)

FLUE

OUTLET

1 INCH MIN. (25.4mm)

Figure 14. Installing Support Brackets

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes.

NOTE: Model DVK-01TRD does not need an exterior firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass through either interior or exterior walls:

Cut a 12-inch by 12-inch (305mm X 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.

Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.

The heat shields of the firestops MUST BE placed to- wards the top of the hole.

Continue the vent run through the firestops.

12"

(305mm)

12"

(305mm)

1" (25.4 mm)

VENT PIPE

Figure 15. 12" x 12" Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT

EXTERIOR

FIRESTOP

INTERIOR

FIRESTOP

Figure 16. Heat Shield, Interior & Exterior Firestops

18

Image 14
Contents Installers Guide What to do if you smell gasSafety and Warning Information Table of Contents Appliance Certification High Altitude InstallationsInstallation Codes CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Heat-N-Glo Gas Fireplaces Diagram of the 7000XLS and 6000XLSB Framing the Fireplace Fireplace Dimensions, LocationsLocating the Fireplace Space Requirements Clearance Requirements32 156mm Vent System Approvals Installing the Vent SystemIdentifying Vent Components Vent System Components and Termination KitsVenting with ONE 1 90 Elbow Venting with Three 3 90 Elbows Venting with three 90 elbowsInstalling Vent Components Attach the First Vent Component to the Starting CollarsTo install support brackets for horizontal runs To Install the Heat ShieldInstall Support Brackets Continue Adding Vent Components12 Hole and Vent Pipe Ceiling Firestop Ceiling Side Attic FirestopVent Termination Pointing UP=VENT Terminal =AIR Supply Inlet Minimum for vinyl clad soffitsMinimum Height from Roof to Lowest Discharge Opening Securing of a Fireplace Positioning, Leveling, and Securing the FireplaceGas Control System Standing Pilot Ignition SystemTo Check for GAS Leaks Gas Supply LineGas Pressure Requirements Optional Accessories Wiring the FireplaceFor Standing Pilot Ignition Wiring Appliance Requirements Remote Wall SwitchFinishing Hearth ExtensionsInstalling Trim, Logs, and Ember Material CeramicBefore Lighting the Fireplace After the InstallationDouble-check for faulty components Lighting the FireplaceFireplace Maintenance Important Turn OFF the GAS Before Servicing Your Fireplace