Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.

NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13 mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch

(13 mm) gas supply line. To install the gas supply line:

A listed (and State of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substituting for these components, please consult local codes for compliance.

Locate the gas line access hole in the outer casing of the fireplace.

The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox.

Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve.

When attaching the pipe, support the control so that the lines are not bent or torn.

After the gas line installation is complete, use a soap solution to carefully check all gas connections for leaks.

!

WARNING: DO NOT USE AN OPEN FLAME

TO CHECK FOR GAS LEAKS.

 

 

• Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

• At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.

Step 7. Gas Pressure Requirements

Pressure requirements for Heat-N-Glo gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

 

 

 

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

USE A WRENCH ON

SHUT-OFF VALVE WHEN

TIGHTENING GAS LINE

MANUAL

SHUT-OFF VALVE

GAS VALVE

FLEX

CONNECTOR

CONTROL

VALVE

GAS LINE

ACCESS HOLE

Figure 25. Gas Supply Line

24

Image 20
Contents Installers Guide What to do if you smell gasSafety and Warning Information Table of Contents High Altitude Installations Installation CodesAppliance Certification CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Heat-N-Glo Gas Fireplaces Diagram of the 7000XLS and 6000XLSB Fireplace Dimensions, Locations Locating the FireplaceFraming the Fireplace Space Requirements Clearance Requirements32 156mm Installing the Vent System Identifying Vent ComponentsVent System Approvals Vent System Components and Termination KitsVenting with ONE 1 90 Elbow Venting with Three 3 90 Elbows Venting with three 90 elbowsInstalling Vent Components Attach the First Vent Component to the Starting CollarsTo Install the Heat Shield Install Support BracketsTo install support brackets for horizontal runs Continue Adding Vent Components12 Hole and Vent Pipe Ceiling Firestop Ceiling Side Attic FirestopVent Termination Pointing UP=VENT Terminal =AIR Supply Inlet Minimum for vinyl clad soffitsMinimum Height from Roof to Lowest Discharge Opening Positioning, Leveling, and Securing the Fireplace Gas Control SystemSecuring of a Fireplace Standing Pilot Ignition SystemTo Check for GAS Leaks Gas Supply LineGas Pressure Requirements Wiring the Fireplace For Standing Pilot Ignition Wiring Appliance RequirementsOptional Accessories Remote Wall SwitchFinishing Hearth ExtensionsInstalling Trim, Logs, and Ember Material CeramicAfter the Installation Double-check for faulty componentsBefore Lighting the Fireplace Lighting the FireplaceFireplace Maintenance Important Turn OFF the GAS Before Servicing Your Fireplace