Carrier EY024-048, 48EJ, EW, EK installation instructions Airflow

Page 35

Table 12 Ð Fan Performance, 48EJ/EK024-034 Ð Vertical Discharge Units (For EW/EY units, reduce net available external static pressure by 0.3 in. wg)

AIRFLOW

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

 

1.2

 

1.4

 

1.6

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

 

Bhp

Rpm

 

Bhp

4,000

340

 

0.83

416

 

1.17

480

 

1.52

537

 

1.90

588

 

2.29

 

 

635

 

2.69

679

 

 

3.11

720

 

3.53

5,000

384

 

1.25

453

 

1.61

513

 

1.99

566

 

2.39

615

 

2.79

 

 

660

 

3.21

703

 

 

3.64

742

 

4.08

6,000

432

 

1.79

495

 

2.19

550

 

2.59

600

 

3.01

647

 

3.43

 

 

690

 

3.87

730

 

 

4.31

769

 

4.77

7,000

483

 

2.48

540

 

2.91

591

 

3.33

638

 

3.77

682

 

4.22

 

 

723

 

4.67

762

 

 

5.14

799

 

5.61

8,000

536

 

3.33

588

 

3.78

635

 

4.23

679

 

4.69

720

 

5.16

 

 

759

 

5.64

797

 

 

6.12

832

 

6.61

8,250

549

 

3.57

600

 

4.02

646

 

4.48

690

 

4.95

730

 

5.42

 

 

769

 

5.90

806

 

 

6.39

841

 

6.88

9,000

590

 

4.34

637

 

4.82

681

 

5.30

722

 

5.78

762

 

6.27

 

 

799

 

6.77

834

 

 

7.27

868

 

7.77

10,000

645

 

5.54

689

 

6.04

729

 

6.54

768

 

7.04

805

 

7.56

 

 

840

 

8.07

874

 

 

8.59

906

 

9.12

11,000

701

 

6.92

741

 

7.44

779

 

7.96

816

 

8.49

850

 

9.03

 

 

884

 

9.56

916

 

 

10.10

947

 

10.65

12,000

757

 

8.49

795

 

9.04

830

 

9.59

865

 

10.14

898

 

10.69

 

 

929

 

11.25

960

 

 

11.81

990

 

12.37

12,500

786

 

9.36

822

 

9.92

856

 

10.47

890

 

11.03

922

 

11.60

 

 

953

 

12.16

983

 

 

12.73

1012

 

13.31

13,000

814

 

10.28

849

 

10.84

883

 

11.41

915

 

11.98

946

 

12.56

 

 

976

 

13.13

1006

 

 

13.71

1034

 

14.30

13,750

857

 

11.75

890

 

12.34

922

 

12.92

953

 

13.51

983

 

14.10

 

1012

 

14.69

1041

 

 

15.28

1068

 

15.88

14,000

871

 

12.27

904

 

12.86

936

 

13.45

966

 

14.05

996

 

14.64

 

1025

 

15.23

1053

 

 

15.83

1080

 

16.43

15,000

929

 

14.50

960

 

15.10

990

 

15.71

1019

 

16.33

1047

 

16.94

 

1074

 

17.55

1101

 

 

18.17

1127

 

18.79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

1.8

 

2.0

 

2.2

 

2.4

 

2.6

 

 

2.8

 

3.0

 

3.2

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

 

Bhp

Rpm

 

Bhp

4,000

759

 

3.97

796

 

4.42

831

 

4.87

865

 

5.34

897

 

5.81

 

 

929

 

6.30

959

 

 

6.79

988

 

7.28

5,000

780

 

4.53

816

 

4.99

851

 

5.45

884

 

5.93

916

 

6.41

 

 

946

 

6.90

976

 

 

7.40

1005

 

7.91

6,000

805

 

5.23

840

 

5.70

874

 

6.18

906

 

6.67

937

 

7.16

 

 

968

 

7.66

997

 

 

8.17

1025

 

8.69

7,000

834

 

6.09

868

 

6.57

901

 

7.07

932

 

7.56

962

 

8.07

 

 

992

 

8.58

1020

 

 

9.10

1048

 

9.63

8,000

866

 

7.10

899

 

7.60

930

 

8.11

961

 

8.62

990

 

9.14

 

1019

 

9.67

1047

 

 

10.20

1074

 

10.74

8,250

874

 

7.38

907

 

7.89

938

 

8.40

968

 

8.92

998

 

9.44

 

1026

 

9.97

1054

 

 

10.50

1081

 

11.04

9,000

901

 

8.29

932

 

8.80

963

 

9.33

992

 

9.86

1021

 

10.39

 

1049

 

10.93

1076

 

 

11.48

1102

 

12.03

10,000

938

 

9.65

968

 

10.18

997

 

10.72

1026

 

11.27

1054

 

11.82

 

1081

 

12.37

1107

 

 

12.93

1133

 

13.49

11,000

977

 

11.19

1006

 

11.75

1035

 

12.30

1062

 

12.87

1089

 

13.43

 

1115

 

14.00

1141

 

 

14.57

1166

 

15.15

12,000

1019

 

12.94

1047

 

13.51

1074

 

14.08

1100

 

14.66

1126

 

15.24

 

1152

 

15.83

1177

 

 

16.42

1201

 

17.01

12,500

1040

 

13.88

1067

 

14.46

1094

 

15.05

1120

 

15.63

1146

 

16.22

 

1171

 

16.82

1195

 

 

17.41

Ð

 

Ð

13,000

1062

 

14.88

1089

 

15.47

1115

 

16.06

1140

 

16.66

1166

 

17.25

 

1190

 

17.86

Ð

 

 

Ð

Ð

 

Ð

13,750

1095

 

16.48

1121

 

17.08

1147

 

17.68

1172

 

18.29

1196

 

18.90

 

 

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

14,000

1106

 

17.04

1132

 

17.64

1157

 

18.25

1182

 

18.86

Ð

 

Ð

 

Ð

 

Ð

Ð

Ð

 

Ð

Ð

 

 

15,000

1152

 

19.41

1177

 

20.04

1200

 

20.66

Ð

 

Ð

Ð

 

Ð

Ð

 

Ð

 

Ð

Ð

 

 

Ð

Ð

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

 

3.4

 

3.6

 

 

3.8

(Cfm)

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

4,000

1017

 

7.79

1045

 

8.30

 

1072

 

8.82

5,000

1033

 

8.42

1061

 

8.94

 

1087

 

9.46

6,000

1053

 

9.21

1080

 

9.73

 

1106

 

10.27

7,000

1075

 

10.16

1102

 

10.69

 

1127

 

11.24

8,000

1100

 

11.28

1126

 

11.83

 

1151

 

12.38

8,250

1107

 

11.59

1133

 

12.14

 

1158

 

12.69

9,000

1128

 

12.58

1153

 

13.14

 

1178

 

13.70

10,000

1158

 

14.06

1183

 

14.63

 

Ð

 

Ð

11,000

1190

 

15.74

Ð

 

Ð

 

Ð

 

Ð

12,000

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

12,500

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

13,000

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

13,750

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

14,000

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

15,000

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

LEGEND

Bhp Ð Brake Horsepower

NOTES:

1.Fan performance is based on wet coils, economizer, roof curb, cabinet losses, and clean 2-in. ®lters.

2.Conversion Ð Bhp to watts:

Bhp x 746

Watts =

Motor efficiency

3.Variable Air Volume units will operate down to 70 cfm/ton. Per- formance at 70 cfm/ton is limited to unloaded operation and may be additionally limited by edb (entering dry bulb) and ewb (enter- ing wet bulb) conditions.

35

Image 35
Contents Installation, Start-Up Service Instructions Instructions on Field Fabricate DuctworkDegrees and Inches Unit Leveling Tolerances DimensionsRoof Curb Sizes Size WeightUnit Operating 48EJE044 Ft-in 48EJ,EKD03848EJE038 48EJ,EKD044Base Unit Dimensions, 48EW,EY024-034 Base Unit Dimensions, 48EW,EY038-048 48EJ,EK,EW,EYD038 Unit Weight 48EJ,EK,EW,EYD02448EJ,EK,EW,EYD028 48EJ,EK,EW,EYD030 48EJ,EK,EW,EYD034Unit 48EJ,EK,EW,EY Physical Data4442/4602 4668/4828 4955/5115 Air Distribution Ð Thru-the-Bottom Combustion Fan Housing Location VAV Unit Configuration Default Cooling Default HeatingField Control Remote Start/Stop Make Electrical Connections LED CCNSIO FLA LRA MCA Mocp Electrical DataRLA LRA NEC FLA LRAFLA HacrMinimum Circuit Amps Qty044 Heating, Air ConditioningTerminal Block GND Ð GroundPEC DIP8772 CCN Connection Approved Shielded CablesManufacturer Cable Part no 2413 orWhite Make Outdoor-Air Inlet AdjustmentsColor Code Recommendations REDAdding Seal Strip to Top of Hood Sides Adding Foam Strip to Hood Side Mounting Angle With Tabs Attached to Filter Track Assembly Psychrometric Chart for Enthalpy Control Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations START-UP SET Point VFD Supply Air Pressure Set PointPressure Control VFD Vdc Direct Digital Controls DIP Switch ConguraPotentiometer Signal Levels Building Pressure Signal LevelDIP Switch Factory Settings Power Exhaust Default Set PointsDIP Switch Conguration Airflow 19,000 16,00017,000 18,000528 572 615 656 695 733 769 805 Standard Efficiency Motors Fan Performance Ð Power ExhaustMotor Limitations ESPAir Quantity Limits Sequence of OperationUser Dened Set Points GAS HEATING, Variable AIR Volume VAV Units HIR DEG. F ResetCOM Device Pressurization Smoke Purge Evacuation Fire Shutdown Smoke Control ModesCompressor Cooling Capacity Staging Table, CV Units With 2 CompressorsStages Manufacturer Lubricant LubricationTypical Gas Heating Section Evaporator Fan Service and ReplacementCondenser-Fan Adjustment Evaporator-Fan Motor ReplacementProtective Devices Belt Tension AdjustmentGas Valve Tran AHAIFC IfcbTypical Power Schematic 48EJ,EK,EW,EY024-034 208/230-3-60 Typical VAV 115-v Control Circuit Typical CV 115-v Control Circuit Typical VAV 24-v Control Circuit Typical CV 24-v Control Circuit Troubleshooting Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 IGC Control Heating and Cooling Control Board LED Alarms IGC Control Board LED AlarmsSPT I/O Channel Designations Base Module Ð CVI/O Channel Designations Base Module Ð VAV Terminal no AssignmentPackaged Service Training START-UP Checklist General
Related manuals
Manual 118 pages 46.64 Kb

EW, EY024-048, EK, 48EJ specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.