Carrier EK, 48EJ, EW, EY024-048 Evaporator Fan Service and Replacement, Typical Gas Heating Section

Page 46

NOTES:

1.Torque set screws on blower wheel to 70 in. lbs ± 2 in. lbs.

2.Torque set screw on propeller fan to 15 in. lbs ± 2 in. lbs.

3.Dimensions are in inches.

Fig. 47 Ð Typical Gas Heating Section

3. Slide fan pulley along fan shaft.

4. Make angular alignment by loosening motor from mount- ing plate.

5. Retighten pulley.

Evaporator Fan Service and Replacement

 

1.

Shut off unit power supply.

 

2.

Remove supply-air section panels.

 

3.

Remove belt and blower pulley.

 

4.

Loosen setscrews in blower wheels.

 

5.

Remove locking collars from bearings.

 

6.

Remove shaft.

 

7.

Remove venturi on opposite side of bearing.

 

8.

Lift out wheel.

 

9.

Reverse above procedure to reinstall fan.

Fig. 48 Ð Gas Heat Section Details

10.

Check and adjust belt tension as necessary.

Belt Tension Adjustment Ð To adjust belt tension:

Evaporator Fan Performance Adjustment

(Fig. 49) Ð Fan motor pulleys are designed for speed shown in Table 1 (factory speed setting).

IMPORTANT: Check to ensure that the unit drive matches the duct static pressure using Tables 12-14.

1.Shut off unit power supply.

2.Loosen motor mounting nuts and bolts. See Fig. 50.

3.Loosen fan motor nuts.

4.Turn motor jacking bolts to move motor mounting plate left or right for proper belt tension. A slight bow should be present in the belt on the slack side of the drive while running under full load.

To change fan speeds, change pulleys. To align fan and motor pulleys:

1.Shut off unit power supply.

2.Loosen fan shaft pulley bushing.

5.Tighten nuts.

6.Adjust bolts and nut on mounting plate to secure motor in ®xed position. Recheck belt tension after 24 hours of operation. Adjust as necessary.

46

Image 46
Contents Installation, Start-Up Service Instructions Field Fabricate Ductwork Instructions onUnit Leveling Tolerances Dimensions Degrees and InchesRoof Curb Sizes Unit Operating WeightSize 48EJ,EKD044 Ft-in 48EJ,EKD03848EJE038 48EJE044Base Unit Dimensions, 48EW,EY024-034 Base Unit Dimensions, 48EW,EY038-048 48EJ,EK,EW,EYD034 Unit Weight 48EJ,EK,EW,EYD02448EJ,EK,EW,EYD028 48EJ,EK,EW,EYD030 48EJ,EK,EW,EYD038Physical Data Unit 48EJ,EK,EW,EY4442/4602 4668/4828 4955/5115 Air Distribution Ð Thru-the-Bottom Combustion Fan Housing Location Unit Configuration Default Cooling Default Heating VAVField Control Remote Start/Stop Make Electrical Connections SIO CCNLED RLA LRA Electrical DataFLA LRA MCA Mocp Hacr FLA LRAFLA NECHeating, Air Conditioning Qty044 Minimum Circuit AmpsGND Ð Ground Terminal BlockDIP PEC2413 or CCN Connection Approved Shielded CablesManufacturer Cable Part no 8772RED Make Outdoor-Air Inlet AdjustmentsColor Code Recommendations WhiteAdding Seal Strip to Top of Hood Sides Adding Foam Strip to Hood Side Mounting Angle With Tabs Attached to Filter Track Assembly Psychrometric Chart for Enthalpy Control Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations START-UP Pressure Control VFD VFD Supply Air Pressure Set PointSET Point Building Pressure Signal Level Direct Digital Controls DIP Switch ConguraPotentiometer Signal Levels VdcDIP Switch Conguration Power Exhaust Default Set PointsDIP Switch Factory Settings Airflow 18,000 16,00017,000 19,000528 572 615 656 695 733 769 805 ESP Fan Performance Ð Power ExhaustMotor Limitations Standard Efficiency MotorsSequence of Operation Air Quantity LimitsUser Dened Set Points GAS HEATING, Variable AIR Volume VAV Units COM DEG. F ResetHIR Smoke Control Modes Device Pressurization Smoke Purge Evacuation Fire ShutdownStages Cooling Capacity Staging Table, CV Units With 2 CompressorsCompressor Lubrication Manufacturer LubricantEvaporator Fan Service and Replacement Typical Gas Heating SectionEvaporator-Fan Motor Replacement Condenser-Fan AdjustmentBelt Tension Adjustment Protective DevicesGas Valve Ifcb AHAIFC TranTypical Power Schematic 48EJ,EK,EW,EY024-034 208/230-3-60 Typical VAV 115-v Control Circuit Typical CV 115-v Control Circuit Typical VAV 24-v Control Circuit Typical CV 24-v Control Circuit Troubleshooting Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 IGC Control Heating and Cooling IGC Control Board LED Alarms Control Board LED AlarmsTerminal no Assignment I/O Channel Designations Base Module Ð CVI/O Channel Designations Base Module Ð VAV SPTPackaged Service Training START-UP Checklist General
Related manuals
Manual 118 pages 46.64 Kb

EW, EY024-048, EK, 48EJ specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.