Carrier 48EJ, EW, EK, EY024-048 installation instructions User Dened Set Points

Page 40

Table 18 Ð User De®ned Set Points

 

SET POINT

 

FORMAT

DESCRIPTION

LIMITS

DEFAULT

 

NAME

 

 

 

 

 

 

 

 

OHSP

 

xx.xF

Occupied Heat Set Point

55 to 80 F

68 F

 

OCSP

 

xx.xF

Occupied Cool Set Point

55 to 80 F

78 F

 

UHSP

 

xx.xF

Unoccupied Heat Set Point

40 to 80 F

55 F

 

UCSP

 

xx.xF

Unoccupied Cool Set Point

75 to 95 F

90 F

 

SASP

 

xx.xF

Supply Air Set Point

45 to 70 F

55 F

 

OATL

 

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65 F

 

NTLO

 

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50 F

 

RTIO

 

xx.x

Reset Ratio

0 to 10

3

 

LIMT

 

xx.xF

Reset Limit

0 to 20° F

10%

 

MDP

 

xxx%

Minimum Damper Position

0 to 100%

20%

 

LOWMDP

 

xxx%

Low Temperature Minimum

0 to 100%

100%

 

 

Damper Position Override

 

 

 

 

 

 

 

IAQS

 

xxxx

IAQ Set Point

1 to 5000 PPM

650 PPM

 

UHDB

 

xx.xF

Unoccupied Heating Deadband

0 to 10° F

1° F

 

UCDB

 

xx.xF

Unoccupied Cooling Deadband

0 to 10° F

1° F

 

LTMP

 

xxx%

Low Temp. Min. Position

0 to 100%

10%

 

HTMP

 

xxx%

High Temp. Min. Position

0 to 100%

35%

 

PES1

 

xxx%

CV Power Exhaust Stage 1 Point

0 to 100%

25%

 

PES2

 

xxx%

CV Power Exhaust Stage 2 Point

0 to 100%

75%

 

LEGEND

 

 

 

 

CV

Ð Constant Volume

 

 

 

 

IAQ

Ð Indoor Air Quality

 

 

 

 

OAT Ð Outdoor-Air Temperature

If thermostats are used to deenergize the G input, the con- trol board will turn off indoor fan without any delay and close economizer dampers.

When cooling, G must be energized before cooling can operate. The control board determines if outdoor conditions are suitable for economizer cooling using the standard out- door air thermistor. For economizer to function for free cool- ing, the enthalpy must be low, the outdoor air must equal to or less than the High Outdoor Air Temperature Lockout (de- fault is 65 F), the SAT (supply-air temperature) thermistor is NOT in alarm, and outdoor air reading is available. When these conditions are satis®ed, the control board will use econo- mizer as the ®rst stage of cooling.

When Y1 input is energized, the economizer will be modu- lated to maintain SAT at the de®ned set point. The default is 55 F. When SAT is above the set point, the economizer will be 100% open. When SAT is below the set point, the econo- mizer will modulate between minimum and 100% open po- sition. When Y2 is energized, the control will turn on com- pressor no. 1 and continue to modulate economizer as described above. If the Y2 remains energized and the SAT reading re- mains above the set point for 15 minutes, compressor no. 2 will turn on. If Y2 is deenergized at any time, only the last stage of compression that was energized will be turned off. If outdoor conditions are not suitable for economizer cool- ing, the economizer will go to minimum position and cycle compressor no. 1 and 2 based on demand from Y1 and Y2 respectively. The compressors will be locked out when the SAT temperature is too low (less than 40 F for compressor no. 1 and less than 45 F for compressor no. 2.) After a com- pressor is locked out, it can restart after normal time guard period.

The Time Guard function maintains a minimum off time of 5 minutes, a minimum ON time of 10 seconds, and a minimum delay before starting the second compressor of 10 seconds.

When heating, the heat stages respond to the demand from W1 and W2 of the thermostat input. Heating and cooling will be mutually locked out on demand on a ®rst call basis. The heating and the cooling functions cannot be operating simultaneously.

COOLING, VARIABLE VOLUME UNITS Ð On power up, the control module will activate the initialization software

of the control board. The initialization software then reads DIP switch no. 1 position to determine CV or VAV opera- tion. Initialization clears all alarms and alerts, re-maps the input/output database for VAV operation, sets maximum heat stages to 1 and sets maximum cool stages to 6. The control reads DIP switch no. 3 and if open, then it sets the internal ¯ag for expansion mode operation.

The control board will determine if an interface (linkage) is active and if the unit will operate in a Digital Air Volume (DAV) mode. In a DAV system, the room terminals are equipped with microprocessor controls that give commands to the base unit module. If an interface is active, the control will replace local comfort set points, space and return air temperatures and occupancy status with the linkage data supplied.

The control board will determine occupancy status from Time Schedules (if programmed), Remote Occupied/ Unoccupied input, global occupancy, or DAV. If tempera- ture compensated start is active, the unit will be controlled as in the Occupied mode.

NOTE: The temperature compensated start is a period of time calculated to bring the unit on while unoccupied to reach the occupied set point when occupancy occurs.

The control board will set the appropriate operating mode and fan control. The control board will turn VFD on if Oc- cupied mode is evident.

For units equipped with a start/stop switch only (no space temperature sensor), if unoccupied and valid return-air tem- perature reading is available (either from a sensor or DAV), the control will monitor return-air temperature against Un- occupied Heat and Cool set points.

For units with a start-stop switch and a space temperature sensor, the control board will start the VFD whenever SPT is outside of the set points (Unoccupied Heat or Unoccupied Cool). The VFD may also be started by nighttime thermostat via remote Occupied/Unoccupied input or by a temperature compensated start algorithm. When VFD is running in a nor- mal mode, the control will start heating or cooling as re- quired to maintain supply-air temperature at the supply air set point plus the reset (when enabled). The reset value is determined by SAT (supply-air temperature) reset and/or space temperature reset algorithms. The space temperature reset is only available when enabled through software.

40

Image 40
Contents Installation, Start-Up Service Instructions Field Fabricate Ductwork Instructions onUnit Leveling Tolerances Dimensions Degrees and InchesRoof Curb Sizes Unit Operating WeightSize Ft-in 48EJ,EKD038 48EJE03848EJ,EKD044 48EJE044Base Unit Dimensions, 48EW,EY024-034 Base Unit Dimensions, 48EW,EY038-048 Unit Weight 48EJ,EK,EW,EYD024 48EJ,EK,EW,EYD028 48EJ,EK,EW,EYD03048EJ,EK,EW,EYD034 48EJ,EK,EW,EYD038Physical Data Unit 48EJ,EK,EW,EY4442/4602 4668/4828 4955/5115 Air Distribution Ð Thru-the-Bottom Combustion Fan Housing Location Unit Configuration Default Cooling Default Heating VAVField Control Remote Start/Stop Make Electrical Connections SIO CCNLED RLA LRA Electrical DataFLA LRA MCA Mocp FLA LRA FLAHacr NECQty 044Heating, Air Conditioning Minimum Circuit AmpsGND Ð Ground Terminal BlockDIP PECCCN Connection Approved Shielded Cables Manufacturer Cable Part no2413 or 8772Make Outdoor-Air Inlet Adjustments Color Code RecommendationsRED WhiteAdding Seal Strip to Top of Hood Sides Adding Foam Strip to Hood Side Mounting Angle With Tabs Attached to Filter Track Assembly Psychrometric Chart for Enthalpy Control Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations START-UP Pressure Control VFD VFD Supply Air Pressure Set PointSET Point Direct Digital Controls DIP Switch Congura Potentiometer Signal LevelsBuilding Pressure Signal Level VdcDIP Switch Conguration Power Exhaust Default Set PointsDIP Switch Factory Settings Airflow 16,000 17,00018,000 19,000528 572 615 656 695 733 769 805 Fan Performance Ð Power Exhaust Motor LimitationsESP Standard Efficiency MotorsSequence of Operation Air Quantity LimitsUser Dened Set Points GAS HEATING, Variable AIR Volume VAV Units COM DEG. F ResetHIR Smoke Control Modes Device Pressurization Smoke Purge Evacuation Fire ShutdownStages Cooling Capacity Staging Table, CV Units With 2 CompressorsCompressor Lubrication Manufacturer LubricantEvaporator Fan Service and Replacement Typical Gas Heating SectionEvaporator-Fan Motor Replacement Condenser-Fan AdjustmentBelt Tension Adjustment Protective DevicesGas Valve AHA IFCIfcb TranTypical Power Schematic 48EJ,EK,EW,EY024-034 208/230-3-60 Typical VAV 115-v Control Circuit Typical CV 115-v Control Circuit Typical VAV 24-v Control Circuit Typical CV 24-v Control Circuit Troubleshooting Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 IGC Control Heating and Cooling IGC Control Board LED Alarms Control Board LED AlarmsI/O Channel Designations Base Module Ð CV I/O Channel Designations Base Module Ð VAVTerminal no Assignment SPTPackaged Service Training START-UP Checklist General
Related manuals
Manual 118 pages 46.64 Kb

EW, EY024-048, EK, 48EJ specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.