Carrier 48EJ, EW, EK, EY024-048 Cooling Capacity Staging Table, CV Units With 2 Compressors, Stages

Page 44

·When the outdoor air quality is greater than the outdoor air quality set point (ppm)

High priority Ð When the priority is set to high, the IAQ set point controls the outside air damper exclusively, with no regard to comfort conditioning.

TIME GUARD CIRCUIT Ð The Time Guard function (built into the rooftop control board) maintains a minimum off time of 5 minutes, a minimum on time of 10 seconds, and a 10-second delay between compressor starts.

CRANKCASE HEATER Ð Unit main power supply must remain on to provide crankcase heater operation. The crank- case heater in each compressor keeps oil free of refrigerant while compressor is off.

HEAD PRESSURE CONTROL Ð Each unit has a fan cy- cling, outdoor thermostat to shut off the outdoor-fan mo- tor(s) at 55 F (one outdoor-fan motor on 024-034 units and two outdoor fan motors on 038-048 units). The head pres- sure control permits unit to operate with correct condensing temperatures down to 35 F outdoor-air temperature.

MOTORMASTER III CONTROL Ð The Motormaster

IIISolid-State Head Pressure Control is a ®eld-installed ac- cessory fan speed control device actuated by a temperature sensor. It is speci®cally designed for use on Carrier equip- ment and controls the condenser-fan motor speed in re- sponse to the saturated condensing temperature. For outdoor temperatures down to −20 F, it maintains condensing tem- perature at 100 F. Refer to the accessory Motormaster in- stallation instructions for more information.

CAPACITY CONTROL, COOLING Ð The cooling capac- ity staging tables are shown in Tables 20 and 21.

Table 20 Ð Cooling Capacity Staging Table, CV Units

with 2 Compressors

 

 

Stages

 

 

 

0

1

2

3

 

Economizer

 

 

 

 

Compressor 1

off

off

on

on

Compressor 2

off

off

off

on

 

 

 

 

 

NOTE: On CV units that require additional unloading, add suction pres- sure unloaders to Compressor 1 only.

Table 21 Ð Cooling Capacity Staging Table VAV Units

with 2 Compressors and 2 Unloaders*

 

 

 

 

Stages

 

 

 

 

0

1

2

3

 

4

5

6

Compressor 1

off

on

on

on

 

on

on

on

Unloader 1

off

on

on

off

 

on

on

off

Unloader 2

off

on

off

off

 

on

off

off

Compressor 2

off

off

off

off

 

on

on

on

 

 

 

 

 

 

 

 

 

*40 ton units have only one unloader.

FIELD TEST Ð The ®eld test program is initiated by mov- ing up DIP switch no. 4 to the OPEN position. The outdoor- air damper will close. The control allows 90 seconds for the damper to close in case it was in the full open position. Next, the indoor-fan contactor will be energized, and the outside- air damper will begin to open to its default value of 20% and stay at that position for a short period of time. The outdoor- air damper will then open to its full open position and stay at that position for a short period of time. The outdoor-air damper will then close.

If the unit is equipped with power exhaust, stage 1 will be energized for 5 seconds. If the unit is con®gured for stage 2 of power exhaust, stage 2 will be energized for 5 seconds after the ®rst stage is deenergized.

The ®rst stage of heat will be energized for 30 seconds, after which the second stage heat will be energized for an additional 30 seconds. Heat is then deenergized.

The last step is the Cooling mode. Outdoor-fan contactor no. 1 is energized. This is followed by each stage of cooling energized with a 10-second delay between stages. After this is complete, outdoor-fan contactor no. 2 is energized for 10 seconds.

The compressors will now deenergize, followed by the outdoor-fan contactors and indoor-fan contactors. If the unit is equipped with the Integrated Gas Control (IGC) board, the indoor fan will continue to operate for an additional 30 seconds after deenergizing the circuit.

The ®eld test is then complete.

SERVICE

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

Service Access Ð All unit components can be reached through clearly labelled hinged access doors. These doors are not equipped with tiebacks, so if heavy duty servicing is needed, either remove them or prop them open to prevent accidental closure.

Each door is held closed with 3 latches. The latches are secured to the unit with a single 1¤4-in. - 20 x 1¤2-in. long bolt. See Fig. 45.

Fig. 45 Ð Door Latch

44

Image 44
Contents Installation, Start-Up Service Instructions Field Fabricate Ductwork Instructions onUnit Leveling Tolerances Dimensions Degrees and InchesRoof Curb Sizes Size WeightUnit Operating Ft-in 48EJ,EKD038 48EJE03848EJ,EKD044 48EJE044Base Unit Dimensions, 48EW,EY024-034 Base Unit Dimensions, 48EW,EY038-048 Unit Weight 48EJ,EK,EW,EYD024 48EJ,EK,EW,EYD028 48EJ,EK,EW,EYD03048EJ,EK,EW,EYD034 48EJ,EK,EW,EYD038Physical Data Unit 48EJ,EK,EW,EY4442/4602 4668/4828 4955/5115 Air Distribution Ð Thru-the-Bottom Combustion Fan Housing Location Unit Configuration Default Cooling Default Heating VAVField Control Remote Start/Stop Make Electrical Connections LED CCNSIO FLA LRA MCA Mocp Electrical DataRLA LRA FLA LRA FLAHacr NECQty 044Heating, Air Conditioning Minimum Circuit AmpsGND Ð Ground Terminal BlockDIP PECCCN Connection Approved Shielded Cables Manufacturer Cable Part no2413 or 8772Make Outdoor-Air Inlet Adjustments Color Code RecommendationsRED WhiteAdding Seal Strip to Top of Hood Sides Adding Foam Strip to Hood Side Mounting Angle With Tabs Attached to Filter Track Assembly Psychrometric Chart for Enthalpy Control Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations START-UP SET Point VFD Supply Air Pressure Set PointPressure Control VFD Direct Digital Controls DIP Switch Congura Potentiometer Signal LevelsBuilding Pressure Signal Level VdcDIP Switch Factory Settings Power Exhaust Default Set PointsDIP Switch Conguration Airflow 16,000 17,00018,000 19,000528 572 615 656 695 733 769 805 Fan Performance Ð Power Exhaust Motor LimitationsESP Standard Efficiency MotorsSequence of Operation Air Quantity LimitsUser Dened Set Points GAS HEATING, Variable AIR Volume VAV Units HIR DEG. F ResetCOM Smoke Control Modes Device Pressurization Smoke Purge Evacuation Fire ShutdownCompressor Cooling Capacity Staging Table, CV Units With 2 CompressorsStages Lubrication Manufacturer LubricantEvaporator Fan Service and Replacement Typical Gas Heating SectionEvaporator-Fan Motor Replacement Condenser-Fan AdjustmentBelt Tension Adjustment Protective DevicesGas Valve AHA IFCIfcb TranTypical Power Schematic 48EJ,EK,EW,EY024-034 208/230-3-60 Typical VAV 115-v Control Circuit Typical CV 115-v Control Circuit Typical VAV 24-v Control Circuit Typical CV 24-v Control Circuit Troubleshooting Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 IGC Control Heating and Cooling IGC Control Board LED Alarms Control Board LED AlarmsI/O Channel Designations Base Module Ð CV I/O Channel Designations Base Module Ð VAVTerminal no Assignment SPTPackaged Service Training START-UP Checklist General
Related manuals
Manual 118 pages 46.64 Kb

EW, EY024-048, EK, 48EJ specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.