Bryant 580F operation manual Outdoor Air Damper Leakage, Return Air Pressure Drop in. wg, Cfm

Page 18

FROM FUSE BLOCK

BLK

YEL

BLU

 

 

 

B

13B

12 13A 13C

2 5 6

2

TO PRESSURE

TRANSDUCER

1 2 3

TO MOTOR(S)

Fig. 24 — Motormaster® V Control

XIII. STEP 13 — ADJUST FACTORY-INSTALLED OPTIONS A. Optional EconoMi$erIV

See Fig. 25 and 26 for EconoMi$erIV component locations.

NOTE: These instructions are for installing the optional EconoMi$erIV only. Refer to the accessory EconoMi$erIV or EconoMi$er2 installation instructions when field installing an EconoMi$erIV or EconoMi$er2 accessory.

To complete installation of the optional EconoMi$erIV, per- form the following procedure.

1.Remove the EconoMi$erIV hood. Refer to Step 11 — Install Outdoor-Air Hood on page 15 for information on removing and installing the outdoor-air hood.

2.Relocate outdoor air temperature sensor from ship- ping position to operation position on EconoMi$erIV. See Fig. 25.

IMPORTANT: Failure to relocate the sensor will result in the EconoMi$erIV not operating properly.

3. Re-install economizer hood.

 

 

 

 

 

 

 

OUTDOOR AIR

 

 

 

 

FRAME

 

 

TEMPERATURE SENSOR

SCREWS ECONOMI$ERIV

SCREWS (INSTALLED OPERATION

 

 

 

 

TOP

 

 

POSITION)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW TEMPERATURE

COMPRESSOR

LOCKOUT SWITCH

Fig. 25 — EconoMi$erIV Component Locations —

End View

SUPPLY AIR

TEMPERATURE SENSOR

LOCATION

ECONOMI$ERIV

ACTUATOR

CONTROLLER

FLANGE

AND SCREWS (HIDDEN)

Fig. 26 — EconoMi$erIV Assembled in Unit —

Side View

4.Install all EconoMi$erIV accessories. EconoMi$erIV wiring is shown in Fig. 27.

Outdoor air leakage is shown in Table 8. Return air pressure drop is shown in Table 9.

Table 8 — Outdoor Air Damper Leakage

 

DAMPER STATIC PRESSURE (in. wg)

 

0.2

0.4

0.6

0.8

1.0

1.2

LEAKAGE (cfm)

35

53

65

75

90

102

Table 9 — Return Air Pressure Drop (in. wg)

CFM

4500

5000

5400

6000

7200

7500

9000

10,000

11,250

0.040

0.050

0.060

0.070

0.090

0.100

0.110

0.120

0.140

B. EconoMi$erIV Standard Sensors

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$erIV can be used for free cooling. The sensor must be field-relocated. See Fig. 25. The operating range of tem- perature measurement is 40 to 100 F.

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 26. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Table 10 for sensor tempera- ture/resistance values.

The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.

Low Temperature Compressor Lockout Switch

The EconoMi$erIV is equipped with an ambient tempera- ture lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42 F ambient tem- perature. See Fig. 25.

18

Image 18
Contents Contents Safety ConsiderationsInstallation Provide Unit Support Roof Curb Details 580F180-240 Roof Curb Details 580F300 Positioning Alternate Unit SupportII. RIG and Place Unit Roof Mount210 Unit Maximum Dimensions Shipping Weight580F Ft-in 180 240Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data Freeze Protection Thermostat F Power ExhaustFurnace Section OUTDOOR-AIR Inlet ScreensIV. Make Unit Duct Connections Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork VI. Trap Condensate DrainVII. Orifice Change VIII. Install GAS Piping Field Control WiringOptional Non-Fused Disconnect Field Power Wiring Connections Optional Convenience OutletElectrical Data Make OUTDOOR-AIR Inlet Adjust MentsXI. Install OUTDOOR-AIR Hood Manual Outdoor-Air DamperXII. Install ALL Accessories Outdoor-Air Hood Component LocationMotormaster V Control Installation 580F240 Motormaster V Control Package UsageApplicable Voltages and Motors EconoMi$erIV Standard Sensors Outdoor Air Damper LeakageReturn Air Pressure Drop in. wg CFMTemperature F EconoMi$erIV Control ModesEconoMi$erIV Sensor Usage EconoMi$erIV Controller Potentiometer LED LocationsEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings Llsv LPSTran Page START-UP IV. Refrigerant Service PortsVI. Internal Wiring Unit PreparationFan Performance 580F180275 Low Heat Units AirflowFan Performance 580F180360 High Heat Units 7200 7500Fan Performance 580F210275 Low Heat Units Fan Performance 580F210360 High Heat UnitsRpm Bhp Watts 500 Fan Performance 580F240275 Low Heat Units Rpm Watts Bhp 000500 000 10,000 Fan Performance 580F240360 High Heat Units 000 500 10,000Fan Performance 580F300275 Low Heat Units Fan Performance 580F300360 High Heat UnitsGeneral Notes for FAN Performance Data Tables Air Quantity Limits Accessory/FIOP Static Pressure in. wg 580F180-300Fan Rpm at Motor Pulley Settings Evaporator-Fan Motor DataService Cleaning XIII. Operating SequenceIV. Evaporator FAN Service and Replacement II. LubricationVII. Power Failure Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VIII. Refrigerant ChargeNatural Gas IX. GAS Valve AdjustmentPerfect Humidity System Charging Main BurnersXI. Filter Drier XV. Replacement PartsXVII. Optional Hinged Access Doors XII. Protective DevicesSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown Comp AHACLO EquipTroubleshooting Unit Troubleshooting II. ECONOMI$ERIV TroublshootingEconoMi$erIV Troubleshooting Completion Heating Service AnalysisProblem Cause Remedy Cooling Service Analysis IGC Control Heating and Cooling Demand Control Enthalpy EconoMi$erIV Input/Output LogicInputs Outputs Terminal†Humidistat IndexService Training Call for Free CatalogCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page PRE-START-UP START-UP ChecklistTemperatures II. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.