Bryant 580F Start-Up, Unit Preparation, II. Compressor Mounting, III. GAS Piping, XII. GAS Heat

Page 26

START-UP

Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up.

I. UNIT PREPARATION

Check that unit has been installed in accordance with these installation instructions and all applicable codes.

II. COMPRESSOR MOUNTING

Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.

III. GAS PIPING

Check gas piping for leaks.

WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres- sures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is sub- jected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field- supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by man- ually closing the gas valve.

IV. REFRIGERANT SERVICE PORTS

Each refrigerant system has a total of 3 Schrader-type service gage ports. One port is located on the suction line, one on the compressor discharge line, and one on the liquid line. In addition, Schrader-type valves are located under- neath the low-pressure switches. Be sure that caps on the ports are tight.

V. COMPRESSOR ROTATION

It is important to be certain the compressors are rotating in the proper direction. To determine whether or not compres- sors are rotating in the proper direction:

1.Connect service gages to suction and discharge pres- sure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels:

1.Note that the evaporator fan is probably also rotating in the wrong direction.

2.Turn off power to the unit.

3.Reverse any two of the incoming power leads.

4.Turn on power to the compressor.

The suction and discharge pressure levels should now move to their normal start-up levels.

NOTE: When compressors are rotating in the wrong direc- tion, the unit will have increased noise levels and will not provide heating and cooling.

After a few minutes of reverse operation, the scroll compres- sor internal overload protection will open, which will

activate the unit’s lockout and requires a manual reset. Reset is accomplished by turning the thermostat on and off.

VI. INTERNAL WIRING

Check all electrical connections in unit control boxes; tighten as required.

VII. CRANKCASE HEATER

Crankcase heater(s) is energized as long as there is power to the unit and the compressor is not operating.

IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result.

VIII. EVAPORATOR FAN

Fan belt and variable pulleys are factory-installed. See Tables 13-20 for fan performance data. Be sure that fans rotate in the proper direction. See Table 21 for air quantity limits. See Table 22 for static pressure information for acces- sories and options. See Table 23 for fan rpm at various motor pulley settings. See Tables 24 and 25 for evaporator fan motor data. To alter fan performance, see Evaporator Fan Performance Adjustment section on page 35.

NOTE: A 31/2-in. bolt and threaded plate are included in the installer’s packet. They can be added to the motor support channel below the motor mounting plate to aid in raising the fan motor.

IX. CONDENSER-FANS AND MOTORS

Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section on page 36 as required. Be sure that fans rotate in the proper direction.

X. RETURN-AIR FILTERS

Check that correct filters are installed in filter tracks (see Table 1). Do not operate unit without return-air filters.

XI. OUTDOOR-AIR INLET SCREENS

Outdoor-air inlet screens must be in place before operating unit.

XII. GAS HEAT

Verify gas pressures before turning on heat as follows:

1.Turn off manual gas stop.

2.Connect pressure gage to supply gas pressure tap (see Fig. 14).

3.Connect pressure gage to manifold pressure tap on gas valve.

4.Turn on manual gas stop and set thermostat to HEAT position. After the unit has run for several minutes, verify that incoming pressure is 5.5 in. wg or greater, and that the manifold pressure is 3.3 in. wg. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section on page 37.

5.After unit has been in operation for 5 minutes, check temperature rise across the heat exchangers. See unit informative plate for correct rise limits of the heat supplied. Air quantities may need to be adjusted to bring the actual rise to within the allowable limits.

26

Image 26
Contents Installation Provide Unit Support ContentsSafety Considerations Roof Curb Details 580F180-240 Roof Curb Details 580F300 Positioning Alternate Unit SupportII. RIG and Place Unit Roof Mount210 Unit Maximum Dimensions Shipping Weight580F Ft-in 180 240Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data Freeze Protection Thermostat F Power ExhaustFurnace Section OUTDOOR-AIR Inlet ScreensIV. Make Unit Duct Connections Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork VI. Trap Condensate DrainVII. Orifice Change Optional Non-Fused Disconnect VIII. Install GAS PipingField Control Wiring Field Power Wiring Connections Optional Convenience OutletElectrical Data Make OUTDOOR-AIR Inlet Adjust MentsXI. Install OUTDOOR-AIR Hood Manual Outdoor-Air DamperXII. Install ALL Accessories Outdoor-Air Hood Component LocationApplicable Voltages and Motors Motormaster V Control Installation 580F240Motormaster V Control Package Usage EconoMi$erIV Standard Sensors Outdoor Air Damper LeakageReturn Air Pressure Drop in. wg CFMTemperature F EconoMi$erIV Control ModesEconoMi$erIV Sensor Usage EconoMi$erIV Controller Potentiometer LED LocationsEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings Tran LlsvLPS Page START-UP IV. Refrigerant Service PortsVI. Internal Wiring Unit PreparationFan Performance 580F180275 Low Heat Units AirflowFan Performance 580F180360 High Heat Units 7200 7500Rpm Bhp Watts 500 Fan Performance 580F210275 Low Heat UnitsFan Performance 580F210360 High Heat Units 500 000 10,000 Fan Performance 580F240275 Low Heat UnitsRpm Watts Bhp 000 Fan Performance 580F240360 High Heat Units 000 500 10,000General Notes for FAN Performance Data Tables Fan Performance 580F300275 Low Heat UnitsFan Performance 580F300360 High Heat Units Air Quantity Limits Accessory/FIOP Static Pressure in. wg 580F180-300Fan Rpm at Motor Pulley Settings Evaporator-Fan Motor DataService Cleaning XIII. Operating SequenceIV. Evaporator FAN Service and Replacement II. LubricationVII. Power Failure Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VIII. Refrigerant ChargeNatural Gas IX. GAS Valve AdjustmentPerfect Humidity System Charging Main BurnersXI. Filter Drier XV. Replacement PartsXVII. Optional Hinged Access Doors XII. Protective DevicesSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown Comp AHACLO EquipTroubleshooting Unit Troubleshooting II. ECONOMI$ERIV TroublshootingProblem Cause Remedy EconoMi$erIV Troubleshooting CompletionHeating Service Analysis Cooling Service Analysis IGC Control Heating and Cooling Demand Control Enthalpy EconoMi$erIV Input/Output LogicInputs Outputs Terminal†Humidistat IndexService Training Call for Free CatalogCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page PRE-START-UP START-UP ChecklistTemperatures II. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.