Bryant 580F operation manual CO2 Sensor Standard Settings

Page 23

percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.

(TO x

OA

) + (TR x

RA

) = TM

100

100

TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air

TR = Return-Air Temperature

RA = Percent of Return Air

TM = Mixed-Air Temperature

Once base ventilation has been determined, set the mini- mum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 33 to determine the maximum setting of the CO2 sensor. For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 33 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to deter- mine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$erIV controller will output the

6.7volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV set point may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$erIV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been deter- mined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 12.

Use setting 1 or 2 for Bryant equipment. See Table 12.

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. See Table 12.

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed any- time after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humid- ity load on any zone is the fresh air introduced. For some applications, a field-supplied energy recovery unit can be added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most com- mercial applications.

If normal rooftop heating and cooling operation is not ade- quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Table 12 — CO2 Sensor Standard Settings

 

 

 

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

CONTROL RANGE

RELAY SETPOINT

HYSTERESIS

OUTPUT

 

 

 

(cfm/Person)

(ppm)

(ppm)

(ppm)

 

 

 

 

1

 

Proportional

Any

0-10V

0-2000

1000

50

 

4-20 mA

 

 

 

 

 

 

 

2

Interface w/Standard

Proportional

Any

2-10V

0-2000

1000

50

Building Control System

7-20 mA

 

 

 

 

 

 

3

 

Exponential

Any

0-10V

0-2000

1100

50

 

4-20 mA

 

 

 

 

 

 

 

4

 

Proportional

15

0-10V

0-1100

1100

50

 

4-20 mA

 

 

 

 

 

 

 

5

 

Proportional

20

0-10V

0- 900

900

50

 

4-20 mA

 

Economizer

 

 

 

 

 

6

Exponential

15

0-10V

0-1100

1100

50

 

 

4-20 mA

 

 

 

 

 

 

 

7

 

Exponential

20

0-10V

0- 900

900

50

 

4-20 mA

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0-10V

0-9999

5000

500

4-20 mA

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0-10V

0-2000

700

50

Loading Docks

4-20 mA

 

 

 

 

 

 

LEGEND

ppm — Parts Per Million

23

Image 23
Contents Installation Provide Unit Support ContentsSafety Considerations Roof Curb Details 580F180-240 Roof Curb Details 580F300 Roof Mount Alternate Unit SupportII. RIG and Place Unit Positioning240 Unit Maximum Dimensions Shipping Weight580F Ft-in 180 210Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data OUTDOOR-AIR Inlet Screens Power ExhaustFurnace Section Freeze Protection Thermostat FVI. Trap Condensate Drain Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork IV. Make Unit Duct ConnectionsVII. Orifice Change Optional Non-Fused Disconnect VIII. Install GAS PipingField Control Wiring Optional Convenience Outlet Field Power Wiring ConnectionsManual Outdoor-Air Damper Make OUTDOOR-AIR Inlet Adjust MentsXI. Install OUTDOOR-AIR Hood Electrical DataOutdoor-Air Hood Component Location XII. Install ALL AccessoriesApplicable Voltages and Motors Motormaster V Control Installation 580F240Motormaster V Control Package Usage CFM Outdoor Air Damper LeakageReturn Air Pressure Drop in. wg EconoMi$erIV Standard SensorsEconoMi$erIV Control Modes Temperature FEconoMi$erIV Controller Potentiometer LED Locations EconoMi$erIV Sensor UsageEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings Tran LlsvLPS Page Unit Preparation IV. Refrigerant Service PortsVI. Internal Wiring START-UPAirflow Fan Performance 580F180275 Low Heat Units7200 7500 Fan Performance 580F180360 High Heat UnitsRpm Bhp Watts 500 Fan Performance 580F210275 Low Heat UnitsFan Performance 580F210360 High Heat Units 500 000 10,000 Fan Performance 580F240275 Low Heat UnitsRpm Watts Bhp 000 000 500 10,000 Fan Performance 580F240360 High Heat UnitsGeneral Notes for FAN Performance Data Tables Fan Performance 580F300275 Low Heat UnitsFan Performance 580F300360 High Heat Units Evaporator-Fan Motor Data Accessory/FIOP Static Pressure in. wg 580F180-300Fan Rpm at Motor Pulley Settings Air Quantity LimitsXIII. Operating Sequence Service CleaningII. Lubrication IV. Evaporator FAN Service and ReplacementVIII. Refrigerant Charge Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VII. Power FailureMain Burners IX. GAS Valve AdjustmentPerfect Humidity System Charging Natural GasXII. Protective Devices XV. Replacement PartsXVII. Optional Hinged Access Doors XI. Filter DrierSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown Equip AHACLO CompII. ECONOMI$ERIV Troublshooting Troubleshooting Unit TroubleshootingProblem Cause Remedy EconoMi$erIV Troubleshooting CompletionHeating Service Analysis Cooling Service Analysis IGC Control Heating and Cooling Terminal† EconoMi$erIV Input/Output LogicInputs Outputs Demand Control EnthalpyIndex HumidistatCall for Free Catalog Service TrainingCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page II. START-UP Electrical START-UP ChecklistTemperatures PRE-START-UP
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.