Bryant Motormaster V Control Installation 580F240, Motormaster V Control Package Usage

Page 17

Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor mount provided with accessory.

Transformer (460-v Units Only) — On 460-v units, a trans- former is required. The transformer is provided with the accessory and must be field-installed.

Motormaster® I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti- cally, with leads protruding from bottom of extrusion.

B. Motormaster V Control Installation (580F240 and 300)

Install Field-Fabricated Wind Baffles

Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 22 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.

Install Motormaster V Controls

The Motormaster V control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid refrigerant pressure. A properly applied Motormaster V control extends the operating range of air- conditioning systems and permits operation at lower outdoor ambient temperatures.

The minimum ambient temperatures at which the unit will operate are:

TEMPERATURE OPERATING LIMITS — F°

Standard

Unit with

Unit with

Unit

Low Ambient Kit

MMV Control

40

25

–20

To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 24) must be added. Field- fabricated and installed wind baffles are also required for all units (see Fig. 22). The Motormaster V control permits opera- tion of the unit to an ambient temperature of –20 F. The con- trol regulates the speed of 3-phase fan motors that are compatible with the control. These motors are factory installed.

See Table 6 for the Motormaster V control accessory package usage. Table 7 shows applicable voltages and motors. Replacement of motor or fan blade IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the factory-installed fan motors. Only field wiring control is required.

Install the Motormaster V control per instructions supplied with accessory.

Table 6 — Motormaster V Control Package Usage

UNIT

VOLTAGE

ITEM DESCRIPTION

580F180-300

208/230

CRLOWAMB015A00

 

 

460

CRLOWAMB016A00

 

 

 

 

Table 7 — Applicable Voltages and Motors

VOLTAGE

COMPATIBLE MOTOR

208/230-3-60

HD52AK654

460-3-60

HD52AK654

NOTE: Dimensions in ( ) are in mm.

Fig. 22 — Wind Baffle Details

SENSOR

SENSOR

LOCATION

LOCATION

HAIRPIN END

HAIRPIN END

580F180580F210

NOTE: All sensors are located on the eighth hairpin up from the bottom.

Fig. 23 — Motormaster I Sensor Locations

17

Image 17
Contents Installation Provide Unit Support ContentsSafety Considerations Roof Curb Details 580F180-240 Roof Curb Details 580F300 II. RIG and Place Unit Alternate Unit SupportPositioning Roof Mount580F Ft-in 180 Unit Maximum Dimensions Shipping Weight210 240Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data Furnace Section Power ExhaustFreeze Protection Thermostat F OUTDOOR-AIR Inlet ScreensIII. Field Fabricate Ductwork Install Flue Hood and Wind BaffleIV. Make Unit Duct Connections VI. Trap Condensate DrainVII. Orifice Change Optional Non-Fused Disconnect VIII. Install GAS PipingField Control Wiring Optional Convenience Outlet Field Power Wiring ConnectionsXI. Install OUTDOOR-AIR Hood Make OUTDOOR-AIR Inlet Adjust MentsElectrical Data Manual Outdoor-Air DamperOutdoor-Air Hood Component Location XII. Install ALL AccessoriesApplicable Voltages and Motors Motormaster V Control Installation 580F240Motormaster V Control Package Usage Return Air Pressure Drop in. wg Outdoor Air Damper LeakageEconoMi$erIV Standard Sensors CFMEconoMi$erIV Control Modes Temperature FEconoMi$erIV Controller Potentiometer LED Locations EconoMi$erIV Sensor UsageEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings Tran LlsvLPS Page VI. Internal Wiring IV. Refrigerant Service PortsSTART-UP Unit PreparationAirflow Fan Performance 580F180275 Low Heat Units7200 7500 Fan Performance 580F180360 High Heat UnitsRpm Bhp Watts 500 Fan Performance 580F210275 Low Heat UnitsFan Performance 580F210360 High Heat Units 500 000 10,000 Fan Performance 580F240275 Low Heat UnitsRpm Watts Bhp 000 000 500 10,000 Fan Performance 580F240360 High Heat UnitsGeneral Notes for FAN Performance Data Tables Fan Performance 580F300275 Low Heat UnitsFan Performance 580F300360 High Heat Units Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg 580F180-300Air Quantity Limits Evaporator-Fan Motor DataXIII. Operating Sequence Service CleaningII. Lubrication IV. Evaporator FAN Service and ReplacementVI. CONDENSER-FAN Adjustment Belt Tension AdjustmentVII. Power Failure VIII. Refrigerant ChargePerfect Humidity System Charging IX. GAS Valve AdjustmentNatural Gas Main BurnersXVII. Optional Hinged Access Doors XV. Replacement PartsXI. Filter Drier XII. Protective DevicesSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown CLO AHAComp EquipII. ECONOMI$ERIV Troublshooting Troubleshooting Unit TroubleshootingProblem Cause Remedy EconoMi$erIV Troubleshooting CompletionHeating Service Analysis Cooling Service Analysis IGC Control Heating and Cooling Inputs Outputs EconoMi$erIV Input/Output LogicDemand Control Enthalpy Terminal†Index HumidistatCall for Free Catalog Service TrainingCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page Temperatures START-UP ChecklistPRE-START-UP II. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.