Bryant 580F operation manual EconoMi$erIV Control Modes, Temperature F

Page 19

LEGEND

Potentiometer Default Settings:

DCV — Demand Controlled Ventilation

Power Exhaust

Middle

Minimum Pos.

Fully Closed

IAQ — Indoor Air Quality

DCV Max.

Middle

LALS — Low Temperature Compressor

DCV Set

Middle

Lockout Switch

Enthalpy

C Setting

OAT — Outdoor-Air Temperature

 

 

POT — Potentiometer

NOTES:

1.620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.

2.If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.

3.For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.

Fig. 27 — EconoMi$erIV Wiring

Table 10 — Supply Air Sensor Temperature/

Resistance Values

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

C. EconoMi$erIV Control Modes

Determine the EconoMi$erIV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 11. The EconoMi$erIV is supplied from the fac- tory with a supply air temperature sensor, a low temperature compressor lockout switch, and an outdoor air temperature sensor. This allows for operation of the EconoMi$erIV with out- door air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$erIV and unit.

Outdoor Dry Bulb Changeover

The standard controller is shipped from the factory config- ured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as stan- dard. For this control mode, the outdoor temperature is com- pared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$erIV will adjust the outdoor-air dampers to mini- mum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dampers will be con- trolled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potentiome- ter will be on. The changeover temperature set point is con- trolled by the free cooling set point potentiometer located on the control. See Fig. 28. The scale on the potentiometer is A, B, C, and D. See Fig. 29 for the corresponding temperature changeover values.

19

Image 19
Contents Safety Considerations ContentsInstallation Provide Unit Support Roof Curb Details 580F180-240 Roof Curb Details 580F300 Roof Mount Alternate Unit SupportII. RIG and Place Unit Positioning240 Unit Maximum Dimensions Shipping Weight580F Ft-in 180 210Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data OUTDOOR-AIR Inlet Screens Power ExhaustFurnace Section Freeze Protection Thermostat FVI. Trap Condensate Drain Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork IV. Make Unit Duct ConnectionsVII. Orifice Change Field Control Wiring VIII. Install GAS PipingOptional Non-Fused Disconnect Optional Convenience Outlet Field Power Wiring ConnectionsManual Outdoor-Air Damper Make OUTDOOR-AIR Inlet Adjust MentsXI. Install OUTDOOR-AIR Hood Electrical DataOutdoor-Air Hood Component Location XII. Install ALL AccessoriesMotormaster V Control Package Usage Motormaster V Control Installation 580F240Applicable Voltages and Motors CFM Outdoor Air Damper LeakageReturn Air Pressure Drop in. wg EconoMi$erIV Standard SensorsEconoMi$erIV Control Modes Temperature FEconoMi$erIV Controller Potentiometer LED Locations EconoMi$erIV Sensor UsageEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings LPS LlsvTran Page Unit Preparation IV. Refrigerant Service PortsVI. Internal Wiring START-UPAirflow Fan Performance 580F180275 Low Heat Units7200 7500 Fan Performance 580F180360 High Heat UnitsFan Performance 580F210360 High Heat Units Fan Performance 580F210275 Low Heat UnitsRpm Bhp Watts 500 Rpm Watts Bhp 000 Fan Performance 580F240275 Low Heat Units500 000 10,000 000 500 10,000 Fan Performance 580F240360 High Heat UnitsFan Performance 580F300360 High Heat Units Fan Performance 580F300275 Low Heat UnitsGeneral Notes for FAN Performance Data Tables Evaporator-Fan Motor Data Accessory/FIOP Static Pressure in. wg 580F180-300Fan Rpm at Motor Pulley Settings Air Quantity LimitsXIII. Operating Sequence Service CleaningII. Lubrication IV. Evaporator FAN Service and ReplacementVIII. Refrigerant Charge Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VII. Power FailureMain Burners IX. GAS Valve AdjustmentPerfect Humidity System Charging Natural GasXII. Protective Devices XV. Replacement PartsXVII. Optional Hinged Access Doors XI. Filter DrierSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown Equip AHACLO CompII. ECONOMI$ERIV Troublshooting Troubleshooting Unit TroubleshootingHeating Service Analysis EconoMi$erIV Troubleshooting CompletionProblem Cause Remedy Cooling Service Analysis IGC Control Heating and Cooling Terminal† EconoMi$erIV Input/Output LogicInputs Outputs Demand Control EnthalpyIndex HumidistatCall for Free Catalog Service TrainingCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page II. START-UP Electrical START-UP ChecklistTemperatures PRE-START-UP
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.