Bryant 580F XI. Filter Drier, XII. Protective Devices, XIII. Relief Devices, XIV. Control Circuit

Page 38

2 LEADS, #18 WIRE 1/32 INSULATION,

REGULATOR

600V. MAX., 105°C

ADJUSTMENT SCREW

 

(REMOVE COVER)

OUTLET PRESSURE TAP (PLUGGED) 1/8-27 N.P.T. THDS.

 

D-1

D-2

RECEPTACLE AND

ON

TAB COMBINATION

W-1

 

C1

 

TERMINAL

 

 

OFF

 

 

C2

 

 

PILOT ADJ.

W-2

PILOT CONNECTION

 

 

 

INLET PRESSURE TAP

 

 

 

FOR 1/4” O.D. TUBING

 

 

 

(PLUGGED)

(PLUGGED)

 

 

 

 

1/8 - 27 N.P.T. THDS.

RECEPTACLE TERMINAL

Fig. 43 — Gas Valve

B.Cleaning and Adjustment

1.Remove burner rack from unit as described in Main Burner Removal section on page 37.

2.Inspect burners, and if dirty, remove burners from rack.

3.Using a soft brush, clean burners and crossover port as required.

4.Adjust spark gap. See Fig. 44.

5.Reinstall burners on rack.

6.Reinstall burner rack as described above.

XI. FILTER DRIER

Replace whenever refrigerant system is exposed to atmosphere.

XII. PROTECTIVE DEVICES

A. Compressor Protection

Overcurrent

Each compressor has internal line break motor protection.

Crankcase Heater

All units are equipped with a 70-watt crankcase heater to prevent absorption of liquid refrigerant by oil in the crank- case when the compressor is idle. The crankcase heater is energized whenever there is main power to the unit and the compressor is not energized.

IMPORTANT: After prolonged shutdown or servicing, ener- gize the crankcase heaters for 24 hours before starting the compressors.

Compressor Lockout

If any of the safeties (high-pressure, low-pressure, freeze protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressors, the cooling lockout (CLO) will lock the compressors off. To reset, manu- ally move the thermostat setting.

B. Evaporator Fan Motor Protection

A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or

increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.

C. Condenser-Fan Motor Protection

Each condenser-fan motor is internally protected against overtemperature.

D. High and Low-Pressure Switches

If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automati- cally locked out by the CLO. To reset, manually move the thermostat setting.

E. Freeze Protection Thermostat (FPT)

An FPT is located on the top and bottom of the evaporator coil. They detect frost build-up and turn off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized by resetting the compressor lockout.

XIII. RELIEF DEVICES

All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side.

XIV. CONTROL CIRCUIT, 24-V

This control circuit is protected against overcurrent by a

3.2amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. See Fig. 45 and 46 for typical wiring diagrams.

XV. REPLACEMENT PARTS

A complete list of replacement parts may be obtained from any Bryant distributor upon request.

XVI. DIAGNOSTIC IGC CONTROL LEDs

The unit control boards have LEDs for diagnostic purposes. Refer to Troubleshooting section on page 43.

XVII. OPTIONAL HINGED ACCESS DOORS

When the optional hinged access doors option is ordered, the unit will be provided with external and internal hinged access doors to facilitate service.

Four external hinged access doors are provided on size 180- 240 units. Two external hinged doors are provided on size 300 units. All external doors are provided with 2 large 1/4 turn latches with folding bail-type handles. (Compressor access doors have one latch.) A single door is provided for filter and drive access. One door is provided for control box access. The control box access door is interlocked with the non-fused disconnect which must be in the OFF position to open the door. Two doors are provided on 580F180-240 units for access to the compressor compartment.

Two internal access doors are provided inside the filter/drive access door. The filter access door (on the left) is secured by

2small 1/4 turn latches with folding bail-type handles. This door must be opened prior to opening the drive access door. The drive access door is shipped with 2 sheet metal screws holding the door closed. Upon initial opening of the door, these screws may be removed and discarded. The door is then held shut by the filter access door, which closes over it.

38

Image 38
Contents Installation Provide Unit Support ContentsSafety Considerations Roof Curb Details 580F180-240 Roof Curb Details 580F300 Positioning Alternate Unit SupportII. RIG and Place Unit Roof Mount210 Unit Maximum Dimensions Shipping Weight580F Ft-in 180 240Base Unit Dimensions 580F180 Base Unit Dimensions 580F240 Base Unit Dimensions 580F300 Physical Data Freeze Protection Thermostat F Power ExhaustFurnace Section OUTDOOR-AIR Inlet ScreensIV. Make Unit Duct Connections Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork VI. Trap Condensate DrainVII. Orifice Change Optional Non-Fused Disconnect VIII. Install GAS PipingField Control Wiring Field Power Wiring Connections Optional Convenience OutletElectrical Data Make OUTDOOR-AIR Inlet Adjust MentsXI. Install OUTDOOR-AIR Hood Manual Outdoor-Air DamperXII. Install ALL Accessories Outdoor-Air Hood Component LocationApplicable Voltages and Motors Motormaster V Control Installation 580F240Motormaster V Control Package Usage EconoMi$erIV Standard Sensors Outdoor Air Damper LeakageReturn Air Pressure Drop in. wg CFMTemperature F EconoMi$erIV Control ModesEconoMi$erIV Sensor Usage EconoMi$erIV Controller Potentiometer LED LocationsEnthalpy Changeover Set Points EconoMi$erIV Controller CO2 Sensor Standard Settings Tran LlsvLPS Page START-UP IV. Refrigerant Service PortsVI. Internal Wiring Unit PreparationFan Performance 580F180275 Low Heat Units AirflowFan Performance 580F180360 High Heat Units 7200 7500Rpm Bhp Watts 500 Fan Performance 580F210275 Low Heat UnitsFan Performance 580F210360 High Heat Units 500 000 10,000 Fan Performance 580F240275 Low Heat UnitsRpm Watts Bhp 000 Fan Performance 580F240360 High Heat Units 000 500 10,000General Notes for FAN Performance Data Tables Fan Performance 580F300275 Low Heat UnitsFan Performance 580F300360 High Heat Units Air Quantity Limits Accessory/FIOP Static Pressure in. wg 580F180-300Fan Rpm at Motor Pulley Settings Evaporator-Fan Motor DataService Cleaning XIII. Operating SequenceIV. Evaporator FAN Service and Replacement II. LubricationVII. Power Failure Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VIII. Refrigerant ChargeNatural Gas IX. GAS Valve AdjustmentPerfect Humidity System Charging Main BurnersXI. Filter Drier XV. Replacement PartsXVII. Optional Hinged Access Doors XII. Protective DevicesSpark Gap Adjustment Typical Wiring Schematic 580F240, 208/230 V Shown Typical Component Arrangement 580F240 Shown Comp AHACLO EquipTroubleshooting Unit Troubleshooting II. ECONOMI$ERIV TroublshootingProblem Cause Remedy EconoMi$erIV Troubleshooting CompletionHeating Service Analysis Cooling Service Analysis IGC Control Heating and Cooling Demand Control Enthalpy EconoMi$erIV Input/Output LogicInputs Outputs Terminal†Humidistat IndexService Training Call for Free CatalogCopyright 2006 Bryant Heating & Cooling Systems Catalog no Page PRE-START-UP START-UP ChecklistTemperatures II. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 64 pages 4.35 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.