American Power Conversion AFX Series manual Options, Visual and audible alarm

Page 41

Options

Smoke detector(s). Smoke detector(s) shall be factory-installed in the

 

return air to sense concentrations of smoke and send a signal to the

 

microprocessor to shut down the unit and activate a visual and audible alarm.

 

Firestat. A firestat shall be factory-installed in the return air to sense heat

 

and send a signal to the microprocessor shutting down the unit and activating

 

a visual and audible alarm.

 

Water detector(s). Water detector(s) shall be factory-wired and shipped in

 

the bottom of the unit to sense water and send a signal to the microprocessor,

 

giving the operator possible alarm indications options for shutdown. The

 

water detector has a 15 ft (5 m) cable for mounting in the subfloor.

 

Remote sensor(s). The temperature and humidity sensors shall be shipped

 

loose in a 2" × 4" × 1.5" (51 mm × 102 mm × 38 mm) box and 50 ft (15 m) of

 

cable supplied for connection to the unit mounted controller.

 

Remote shutdown. A relay shall be factory installed in the unit with a two

 

pin terminal block to be field wired to a ______(24, 120, or 220 VAC) signal

 

which will shut down the unit control circuit when the signal is received.

 

Essential/non-essential lockout. An essential/non-essential lockout relay

 

shall be factory-installed and wired to a two-pin terminal block to prevent

 

operation of reheat or humidifier operation when a ______ (24, 120, or 220

 

VAC) signal is received.

 

Floorstand. An adjustable floorstand fabricated form heavy gauge steel

 

shall be provided. The height shall be adjustable from 6” to 36” (115 mm to

 

915 mm) on Upflow units and 12” to 36” (230 mm to 915 mm) on Downflow

 

units. Pedestals and vibration pads shall be included. Each pedestal shall be a

 

3/4" (19 mm) threaded rod, capable of a 2000-lb. (910 kg) vertical load. Zone

 

4 seismic floorstands shall ship loose and shall be _______ in (mm) high, up

 

to 36" (915 mm).

 

Air Deflector. A 90° air deflector shall ship loose and shall be _______ in.

 

(mm) high.

 

Top-discharge plenum. A top-discharge plenum shall be supplied with a

 

gasket material for mounting to an upflow unit. Manually adjustable, double-

 

deflecting grilles shall be provided on 3 or 4 sides. A combination of sound

 

lining and insulation material shall be used. Plenum height shall be 20" in

 

(508 mm) or 24" (610 mm).

 

Duct flange. A 1" (25 mm) duct flange shall be factory-installed on the top

 

of the upflow unit at the blower outlet.

 

Redundant group control. ________ (up to 6) units shall be capable of

 

being connected together to form a redundant group. The master

 

microprocessor controller shall monitor the status of the slave

 

microprocessor controllers and determine—based on run time alarm

 

conditions and local requirements, which the units in the redundant group

 

shall run.

 

Remote display panel. A remote microprocessor control display with

 

keypad shall be shipped loose in a 12" × 8" × 3"

 

(300 mm × 200 mm × 80 mm) box and 50 ft (15 m) of cable supplied for

 

connection to the units’ microprocessor logic board.

36

APC NetworkAIR AFX Series: Guide Specifications

Image 41
Contents NetworkAIRTM AFX Series Contents Guide Specifications Pump Specifications Page Downflow Available ModelsUpflow front-return Indoor top-discharge centrifugal condenserPage Introduction OverviewCapacity Air patternFront access ConfigurationHumidity control ComplianceModel Selection DwhuPage Controller Standard FeaturesMicroprocessor Setpoint Overall cabinetElectrical panel Blower assemblyHumidifier Electric reheatCooling coil Clogged filter alarmCondenser Air filterPan Emergency drainPage Emergency Optional FeaturesEnvironmental ExternalAPC NetworkAIR AFX Series Optional Features System Components ReheatPage Model Capacity in BTU/H Performance SpecificationsNet cooling capacity-air/remote condensing 26T 28T Net cooling capacity-waterNet cooling capacity-glycol Page Air system Performance DataCoolant requirements Pump systemHumidification-solid state electrode canister Water regulating valve-2-Way/3-Way, single seatedFilters Compressor-scrollHot gas reheat Electric ReheatHot water reheat Steam reheatConnection sizes Electric Reheat-6-14 ton Electrical DataHumidifier VoltageElectric Reheat-18-28 ton Steam/hot water/or no-reheat-6-14 ton Steam/hot water/or no-reheat-18-28 ton Indoor centrifugal condenser units Page Product Guide SpecificationsGeneral APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications GPML/s at ft m external head, and operate on Ph, 60-Hz power Options Visual and audible alarmAPC NetworkAIR AFX Series Guide Specifications Page Downflow-6-8 ton Dimensional DataDownflow-10-18 ton Downflow-20-28 ton Upflow front-return-6-8 ton Upflow front-return-10-18 ton Upflow front-return-20-28 ton Upflow rear-return-6-8 ton Upflow rear-return-10-18 ton Upflow rear-return-20-28 ton Indoor rear-discharge centrifugal condenser-6-8 ton Indoor rear-discharge centrifugal condenser-10-18 ton Indoor rear-discharge centrifugal condenser-20-28 ton Indoor top-discharge centrifugal condenser-6-8 ton Indoor top-discharge centrifugal condenser-10-18 ton Indoor top-discharge centrifugal condenser-20-28 ton Page Key to the model number Air-Cooled Condensers and DrycoolersLbs Air-cooled condenser-physical dataFLA MCA MOP Air-cooled condenser-electrical dataModel Temp Single-fan air-cooled condenser-6 ton Dual-fan air-cooled condenser-6-14 ton Triple-fan air-cooled condenser-14-20 ton Dual-fan air-cooled condenser-20-26 ton Triple-fan air-cooled condenser-26-28 ton Glycol cooled drycooler-physical data DrycoolerGlycol cooled drycooler-electrical data Tonnage Ambient FLA MCA MOPDual-fan fluid cooler-6-8 ton Triple-fan fluid cooler-10-12 ton Dual-fan fluid cooler-14-18 ton Triple-fan fluid cooler-20-28 ton Page FLA MCA Pump SpecificationsPump electrical data Page Service access Guidelines for InstallationRoom preparation Unit locationRigging Power unitFloorstand Utility connectionsWater supply Page APC Worldwide Customer Support

AFX Series specifications

The American Power Conversion (APC) AFX Series is a groundbreaking line of uninterruptible power supplies (UPS) designed to meet the demands of modern businesses. APC, a subsidiary of Schneider Electric, is known for its reliable power management solutions that ensure the availability of critical equipment. The AFX Series stands out for its advanced features, cutting-edge technologies, and robust characteristics that cater to a diverse range of applications.

One of the standout features of the AFX Series is its flexible architecture. The series offers modular scalability, allowing users to expand power capacity as needed. This modular design is particularly beneficial for growing businesses that require a power solution that can adapt to changing demands without the need for a complete replacement. The AFX units boast a compact footprint, making them suitable for deployment in server rooms, data centers, or environments with space constraints.

Another significant characteristic of the AFX Series is its high efficiency. The UPS units are designed to operate at a remarkable efficiency level, often exceeding 95%, which translates into reduced energy consumption and lower operating costs. This efficiency not only benefits the environment but also enhances the overall reliability of power delivery.

In terms of technology, the AFX Series leverages advanced lithium-ion battery technology. Lithium-ion batteries have a longer lifespan and faster charge times compared to traditional lead-acid batteries. This innovation ensures that uptime is maximized, while maintenance efforts are minimized, allowing IT personnel to focus on more critical tasks.

The AFX Series is also equipped with intelligent monitoring and management features. Users can take advantage of real-time data and analytics through an intuitive web interface, providing insights into power performance and battery health. This capability aids in proactive maintenance, ensuring potential issues are addressed before they lead to downtime.

Furthermore, the AFX Series supports a range of connectivity options, including SNMP, USB, and serial interfaces. These options enable seamless integration into existing management systems, allowing for centralized monitoring and control.

In summary, the American Power Conversion AFX Series is a powerful solution for organizations seeking reliability, efficiency, and scalability in their UPS systems. With its modular architecture, high operational efficiency, advanced lithium-ion technology, and user-friendly management capabilities, the AFX Series is an exemplary choice for businesses aiming to safeguard their critical infrastructure against power interruptions.