American Power Conversion AFX Series manual Steam/hot water/or no-reheat-18-28 ton

Page 33

Steam/hot water/or no-reheat—18–28 ton

HUMIDIFIER

 

 

 

Electric

 

 

Steam or None

 

VOLTAGE

 

 

208

230

460

575

208

230

460

575

18T

FLA

Air

85.7

82.5

41.1

32.9

69.3

67.7

33.7

26.9

 

 

Water

79.3

76.1

37.9

30.3

62.9

61.3

30.5

24.3

 

 

Glycol

89.9

86.7

44.1

34.5

73.5

71.9

36.7

28.5

 

 

Remote Condensing

34.0

30.8

15.4

12.4

17.6

16.0

8.0

6.4

 

 

 

 

 

 

 

 

 

 

 

 

WSA

Air

113.7

110.1

56.2

44.3

93.2

91.6

46.9

36.8

 

 

Water

113.7

110.1

56.2

44.3

93.2

91.6

46.9

36.8

 

 

Glycol

113.7

110.1

56.2

44.3

93.2

91.6

46.9

36.8

 

 

Remote Condensing

42.5

38.5

19.3

15.5

22.0

20.0

10.0

8.0

 

 

 

 

 

 

 

 

 

 

 

 

MOP

Air

125.0

125.0

70.0

50.0

125.0

125.0

60.0

50.0

 

 

Water

125.0

125.0

70.0

50.0

125.0

125.0

60.0

50.0

 

 

Glycol

125.0

125.0

70.0

50.0

125.0

125.0

60.0

50.0

 

 

Remote Condensing

45.0

40.0

20.0

15.0

25.0

25.0

15.0

15.0

 

 

 

 

 

 

 

 

 

 

 

20T

FLA

Air

104.8

100.4

49.9

39.9

85.8

83.4

41.4

33.0

 

 

Water

96.8

92.4

45.9

36.7

77.8

75.4

37.4

29.8

 

 

Glycol

110.0

105.6

52.5

41.9

91.0

88.6

44.0

35.0

 

 

Remote Condensing

45.4

41.0

20.5

16.5

26.4

24.0

12.0

9.6

 

 

 

 

 

 

 

 

 

 

 

 

WSA

Air

144.7

139.8

65.8

49.3

120.9

118.5

55.2

40.7

 

 

Water

144.7

139.8

65.8

49.3

120.9

118.5

55.2

40.7

 

 

Glycol

144.7

139.8

65.8

49.3

120.9

118.5

55.2

40.7

 

 

Remote Condensing

56.8

51.3

25.6

20.6

33.0

30.0

15.0

12.0

 

 

 

 

 

 

 

 

 

 

 

 

MOP

Air

175.0

175.0

80.0

80.0

150.0

150.0

70.0

50.0

 

 

Water

175.0

175.0

80.0

80.0

150.0

150.0

70.0

50.0

 

 

Glycol

175.0

175.0

80.0

80.0

150.0

150.0

70.0

50.0

 

 

Remote Condensing

50.0

50.0

25.0

20.0

35.0

30.0

15.0

15.0

 

 

 

 

 

 

 

 

 

 

 

26T

FLA

Air

118.9

107.4

53.6

42.8

99.9

90.4

45.1

35.9

 

 

Water

110.5

99.8

49.8

39.8

91.5

82.8

41.3

32.9

 

 

Glycol

122.4

110.6

55.2

44.1

103.4

93.6

46.7

37.2

 

 

Remote Condensing

45.4

41.0

20.5

16.5

26.4

24.0

12.0

9.6

 

 

 

 

 

 

 

 

 

 

 

 

WSA

Air

156.1

151.2

66.7

53.8

132.4

130.0

56.1

45.2

 

 

Water

156.1

151.2

66.7

53.8

132.4

130.0

56.1

45.2

 

 

Glycol

156.1

151.2

66.7

53.8

132.4

130.0

56.1

45.2

 

 

Remote Condensing

56.8

51.3

25.6

20.6

33.0

33.0

15.0

12.0

 

 

 

 

 

 

 

 

 

 

 

 

MOP

Air

175.0

175.0

80.0

80.0

175.0

175.0

70.0

60.0

 

 

Water

175.0

175.0

80.0

80.0

175.0

175.0

70.0

60.0

 

 

Glycol

175.0

175.0

100.0

80.0

175.0

175.0

90.0

70.0

 

 

Remote Condensing

50.0

50.0

25.0

20.0

35.0

30.0

15.0

15.0

 

 

 

 

 

 

 

 

 

 

 

28T

FLA

Air

115.2

104.1

52.0

41.7

96.2

87.1

43.5

34.8

 

 

Water

107.7

97.3

48.6

39.0

88.7

80.3

40.1

32.1

 

 

Glycol

117.9

106.5

53.2

42.7

98.9

89.5

44.7

35.8

 

 

Remote Condensing

45.4

41.0

20.5

16.5

26.4

24.0

12.0

9.6

 

 

 

 

 

 

 

 

 

 

 

 

WSA

Air

156.1

151.2

78.9

63.0

132.4

130.0

68.3

54.4

 

 

Water

156.1

151.2

78.9

63.0

132.4

130.0

68.3

54.4

 

 

Glycol

156.1

151.2

78.9

63.0

132.4

130.0

68.3

54.4

 

 

Remote Condensing

56.8

51.3

25.6

20.6

33.0

30.0

15.0

12.0

 

 

 

 

 

 

 

 

 

 

 

 

MOP

Air

175.0

175.0

100.0

100.0

175.0

175.0

90.0

70.0

 

 

Water

175.0

175.0

100.0

100.0

175.0

175.0

90.0

70.0

 

 

Glycol

175.0

175.0

100.0

100.0

175.0

175.0

90.0

70.0

 

 

Remote Condensing

50.0

50.0

25.0

20.0

35.0

30.0

15.0

15.0

 

 

 

 

 

 

 

 

 

FLA= Full Load Amperes

MOP=Maximum Overcurrent Protection

WSA=Wire Size Amperes

 

 

 

 

 

*Values are calculated based on 3– phase power

 

 

 

 

28

APC NetworkAIR AFX Series: Electrical Data

Image 33
Contents NetworkAIRTM AFX Series Contents Guide Specifications Pump Specifications Page Downflow Available ModelsUpflow front-return Indoor top-discharge centrifugal condenserPage Introduction OverviewCapacity Air patternFront access ConfigurationHumidity control ComplianceModel Selection DwhuPage Standard Features MicroprocessorController Setpoint Overall cabinetElectrical panel Blower assemblyHumidifier Electric reheatCooling coil Clogged filter alarmCondenser Air filterPan Emergency drainPage Emergency Optional FeaturesEnvironmental ExternalAPC NetworkAIR AFX Series Optional Features System Components ReheatPage Performance Specifications Net cooling capacity-air/remote condensingModel Capacity in BTU/H 26T 28T Net cooling capacity-waterNet cooling capacity-glycol Page Air system Performance DataCoolant requirements Pump systemHumidification-solid state electrode canister Water regulating valve-2-Way/3-Way, single seatedFilters Compressor-scrollHot gas reheat Electric ReheatHot water reheat Steam reheatConnection sizes Electric Reheat-6-14 ton Electrical Data Humidifier VoltageElectric Reheat-18-28 ton Steam/hot water/or no-reheat-6-14 ton Steam/hot water/or no-reheat-18-28 ton Indoor centrifugal condenser units Page Guide Specifications GeneralProduct APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications GPML/s at ft m external head, and operate on Ph, 60-Hz power Options Visual and audible alarmAPC NetworkAIR AFX Series Guide Specifications Page Downflow-6-8 ton Dimensional DataDownflow-10-18 ton Downflow-20-28 ton Upflow front-return-6-8 ton Upflow front-return-10-18 ton Upflow front-return-20-28 ton Upflow rear-return-6-8 ton Upflow rear-return-10-18 ton Upflow rear-return-20-28 ton Indoor rear-discharge centrifugal condenser-6-8 ton Indoor rear-discharge centrifugal condenser-10-18 ton Indoor rear-discharge centrifugal condenser-20-28 ton Indoor top-discharge centrifugal condenser-6-8 ton Indoor top-discharge centrifugal condenser-10-18 ton Indoor top-discharge centrifugal condenser-20-28 ton Page Key to the model number Air-Cooled Condensers and DrycoolersLbs Air-cooled condenser-physical dataAir-cooled condenser-electrical data Model TempFLA MCA MOP Single-fan air-cooled condenser-6 ton Dual-fan air-cooled condenser-6-14 ton Triple-fan air-cooled condenser-14-20 ton Dual-fan air-cooled condenser-20-26 ton Triple-fan air-cooled condenser-26-28 ton Glycol cooled drycooler-physical data DrycoolerGlycol cooled drycooler-electrical data Tonnage Ambient FLA MCA MOPDual-fan fluid cooler-6-8 ton Triple-fan fluid cooler-10-12 ton Dual-fan fluid cooler-14-18 ton Triple-fan fluid cooler-20-28 ton Page Pump Specifications Pump electrical dataFLA MCA Page Service access Guidelines for InstallationRoom preparation Unit locationRigging Power unitFloorstand Utility connectionsWater supply Page APC Worldwide Customer Support