American Power Conversion AFX Series manual Net cooling capacity-glycol

Page 24

Net cooling capacity—glycol

 

 

 

 

 

 

MODEL

 

 

 

 

CAPACITY IN BTU/H

6T

8T

10T

12T

14T

18T

20T

26T

28T

80° F DB, 67° F WB

Total (BTUH)

77,700

110,700

130,200

145,800

155,300

225,100

270,000

296,400

328,700

 

(26.7°C DB, 19.4°C WB)

(kW)

(22.8)

(32.4)

(38.1)

(42.7)

(45.5)

(65.9)

(79.1)

(86.8)

(96.2)

50% RH

Sensible (BTUH)

72,300

88,800

123,400

133,600

150,100

184,000

241,000

257,900

282,900

 

(kW)

(21.2)

(26.0)

(36.1)

(39.1)

(44.0)

(53.9)

(70.6)

(75.5)

(82.8)

 

 

 

 

 

 

 

 

 

 

 

75° F DB, 62.5° F WB

Total (BTUH)

71,900

102,000

121,600

133,900

145,800

206,800

256,400

274,400

302,100

(23.9°C DB, 16.9°C WB)

(kW)

(21.1)

(29.9)

(35.6)

(39.2)

(42.7)

(60.6)

(75.1)

(80.3)

(88.5)

50% RH

Sensible (BTUH)

70,300

87,400

121,600

130,600

145,800

179,900

210,600

251,800

277,500

 

(kW)

(20.6)

(25.6)

(35.6)

(38.2)

(42.7)

(52.7)

(61.7)

(73.7)

(81.3)

 

 

 

 

 

 

 

 

 

 

 

75° F DB, 61° F WB

Total (BTUH)

69,597

100,600

121,600

129,294

145,700

201,700

254,400

278,700

305,200

(23.9°C DB, 16.1°C WB)

(kW)

(20.4)

(29.5)

(35.6)

(37.9)

(42.7)

(59.1)

(74.5)

(81.6)

(89.4)

45% RH

Sensible (BTUH)

69,597

94,400

121,600

129,294

145,700

193,600

216,500

278,700

305,200

 

(kW)

(20.4)

(27.6)

(35.6)

(37.9)

(42.7)

(56.7)

(63.4)

(81.6)

(89.4)

 

 

 

 

 

 

 

 

 

 

 

72° F DB, 60° F WB

Total (BTUH)

69,000

97,300

116,100

127,500

139,300

197,200

237,700

266,400

285,400

(22.2°C DB, 15.5°C WB)

(kW)

(20.2)

(28.5)

(34.0)

(37.3)

(40.8)

(57.7)

(69.6)

(78.0)

(83.6)

50% RH

Sensible (BTUH)

69,000

85,300

116,100

125,500

139,300

175,500

230,600

251,800

265,100

 

(kW)

(20.2)

(25.0)

(34.0)

(36.7)

(40.8)

(51.4)

(67.5)

(73.7)

(77.6)

 

 

 

 

 

 

 

 

 

 

 

72° F DB, 58.6° F WB

Total (BTUH)

68,310

96,200

116,100

124,245

139,300

193,000

241,600

268,600

292,500

(22.2°C DB, 14.8°C WB)

(kW)

(20.0)

(28.2)

(34.0)

(36.4)

(40.8)

(56.5)

(70.7)

(78.6)

(85.6)

45% RH

Sensible (BTUH)

68,310

91,200

116,100

124,245

139,300

188,500

241,600

268,600

292,500

 

(kW)

(20.0)

(26.7)

(34.0)

(36.4)

(40.8)

(55.2)

(70.7)

(78.6)

(85.6)

 

 

 

 

 

 

 

 

 

 

 

70° F DB, 58.5° F WB

Total (BTUH)

66,900

94,400

112,500

125,200

135,100

191,100

230,600

259,300

278,600

(22.2°C DB, 14.8°C WB)

(kW)

(19.6)

(27.6)

(32.9)

(36.7)

(39.6)

(56.0)

(67.5)

(75.9)

(81.6)

50% RH

Sensible (BTUH)

66,900

83,500

112,500

125,200

135,100

171,900

225,300

247,100

265,100

 

(kW)

(19.6)

(24.4)

(32.9)

(36.7)

(39.6)

(50.3)

(66.0)

(72.4)

(77.6)

 

 

 

 

 

 

 

 

 

 

 

70° F DB, 57.2° F WB

Total (BTUH)

66,900

93,300

112,500

125,100

135,000

187,300

234,600

261,900

284,100

(22.2°C DB, 14.8°C WB)

(kW)

(19.6)

(27.3)

(32.9)

(36.6)

(39.5)

(54.8)

(68.7)

(76.7)

(83.2)

45% RH

Sensible (BTUH)

66,900

89,400

112,500

125,100

135,000

183,800

234,600

261,900

284,100

 

(kW)

(19.6)

(26.2)

(32.9)

(36.6)

(39.5)

(53.8)

(68.7)

(76.7)

(83.2)

 

 

 

 

 

 

 

 

 

 

 

*Performance Specifications @ 95° F Ambient (AIR/GLYCOL/RC) or @ 105° F Condensing (WATER)

APC NetworkAIR AFX Series: Performance Specifications

19

Image 24
Contents NetworkAIRTM AFX Series Contents Guide Specifications Pump Specifications Page Available Models DownflowUpflow front-return Indoor top-discharge centrifugal condenserPage Overview IntroductionCapacity Air patternConfiguration Front accessHumidity control ComplianceDwhu Model SelectionPage Standard Features MicroprocessorController Overall cabinet SetpointBlower assembly Electrical panelHumidifier Electric reheatClogged filter alarm Cooling coilCondenser Air filterEmergency drain PanPage Optional Features EmergencyEnvironmental ExternalAPC NetworkAIR AFX Series Optional Features Reheat System ComponentsPage Performance Specifications Net cooling capacity-air/remote condensingModel Capacity in BTU/H Net cooling capacity-water 26T 28TNet cooling capacity-glycol Page Performance Data Air systemCoolant requirements Pump systemWater regulating valve-2-Way/3-Way, single seated Humidification-solid state electrode canisterFilters Compressor-scrollElectric Reheat Hot gas reheatHot water reheat Steam reheatConnection sizes Electrical Data Electric Reheat-6-14 tonHumidifier VoltageElectric Reheat-18-28 ton Steam/hot water/or no-reheat-6-14 ton Steam/hot water/or no-reheat-18-28 ton Indoor centrifugal condenser units Page Guide Specifications GeneralProduct APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications APC NetworkAIR AFX Series Guide Specifications GPML/s at ft m external head, and operate on Ph, 60-Hz power Visual and audible alarm OptionsAPC NetworkAIR AFX Series Guide Specifications Page Dimensional Data Downflow-6-8 tonDownflow-10-18 ton Downflow-20-28 ton Upflow front-return-6-8 ton Upflow front-return-10-18 ton Upflow front-return-20-28 ton Upflow rear-return-6-8 ton Upflow rear-return-10-18 ton Upflow rear-return-20-28 ton Indoor rear-discharge centrifugal condenser-6-8 ton Indoor rear-discharge centrifugal condenser-10-18 ton Indoor rear-discharge centrifugal condenser-20-28 ton Indoor top-discharge centrifugal condenser-6-8 ton Indoor top-discharge centrifugal condenser-10-18 ton Indoor top-discharge centrifugal condenser-20-28 ton Page Air-Cooled Condensers and Drycoolers Key to the model numberAir-cooled condenser-physical data LbsAir-cooled condenser-electrical data Model TempFLA MCA MOP Single-fan air-cooled condenser-6 ton Dual-fan air-cooled condenser-6-14 ton Triple-fan air-cooled condenser-14-20 ton Dual-fan air-cooled condenser-20-26 ton Triple-fan air-cooled condenser-26-28 ton Drycooler Glycol cooled drycooler-physical dataGlycol cooled drycooler-electrical data Tonnage Ambient FLA MCA MOPDual-fan fluid cooler-6-8 ton Triple-fan fluid cooler-10-12 ton Dual-fan fluid cooler-14-18 ton Triple-fan fluid cooler-20-28 ton Page Pump Specifications Pump electrical dataFLA MCA Page Guidelines for Installation Service accessRoom preparation Unit locationPower unit RiggingFloorstand Utility connectionsWater supply Page APC Worldwide Customer Support

AFX Series specifications

The American Power Conversion (APC) AFX Series is a groundbreaking line of uninterruptible power supplies (UPS) designed to meet the demands of modern businesses. APC, a subsidiary of Schneider Electric, is known for its reliable power management solutions that ensure the availability of critical equipment. The AFX Series stands out for its advanced features, cutting-edge technologies, and robust characteristics that cater to a diverse range of applications.

One of the standout features of the AFX Series is its flexible architecture. The series offers modular scalability, allowing users to expand power capacity as needed. This modular design is particularly beneficial for growing businesses that require a power solution that can adapt to changing demands without the need for a complete replacement. The AFX units boast a compact footprint, making them suitable for deployment in server rooms, data centers, or environments with space constraints.

Another significant characteristic of the AFX Series is its high efficiency. The UPS units are designed to operate at a remarkable efficiency level, often exceeding 95%, which translates into reduced energy consumption and lower operating costs. This efficiency not only benefits the environment but also enhances the overall reliability of power delivery.

In terms of technology, the AFX Series leverages advanced lithium-ion battery technology. Lithium-ion batteries have a longer lifespan and faster charge times compared to traditional lead-acid batteries. This innovation ensures that uptime is maximized, while maintenance efforts are minimized, allowing IT personnel to focus on more critical tasks.

The AFX Series is also equipped with intelligent monitoring and management features. Users can take advantage of real-time data and analytics through an intuitive web interface, providing insights into power performance and battery health. This capability aids in proactive maintenance, ensuring potential issues are addressed before they lead to downtime.

Furthermore, the AFX Series supports a range of connectivity options, including SNMP, USB, and serial interfaces. These options enable seamless integration into existing management systems, allowing for centralized monitoring and control.

In summary, the American Power Conversion AFX Series is a powerful solution for organizations seeking reliability, efficiency, and scalability in their UPS systems. With its modular architecture, high operational efficiency, advanced lithium-ion technology, and user-friendly management capabilities, the AFX Series is an exemplary choice for businesses aiming to safeguard their critical infrastructure against power interruptions.