BRK electronic Mx-1000 manual

Page 30

SW 1/3 – Delay On Auto:

OFF: Automatically turn off the delay mode once a day at the set time [the delay mode first being turned on manually].

ON: Automatically turn the delay mode on once a day and off once a day at the set times.

Requires optional clock module.

●SW 1/4 - Config Non-Latch Zones:

OFF: Configuration mode disabled.

ON: Enables selected zones to be configured to non-latching fire mode via the Engineer’s Select feature.

[Not EN54 compliant function].

●SW 1/5 - Config I/S Zones:

OFF: Configuration mode disabled.

ON: Enables selected zones to be configured to Intrinsically Safe alarm thresholds and passive end of line fault monitoring via the Engineer’s Select feature. [For use with appropriate I.S. barriers/Isolators, typically 330 Ohm zener barriers or galvanic isolators].

[Not EN54 compliant function. Provided to meet existing customer requirements.]

SW 1/6 - Config M/S Zones:

OFF: Configuration mode disabled.

ON: Enables selected zones to be configured to short circuit fire mode via the Engineer’s Select feature.

SW 1/7 - Config Delay Zones:

OFF: Configuration mode disabled.

ON: Enables selected zones to be configured to Delay Mode via the Engineer’s Select feature.

SW 1/8 - Configure Delay O/Ps:

OFF: Configuration mode disabled.

ON: Enables the selection of outputs, via the Engineer’s Select feature, to which the panel delay will apply.

SW 1/9 - 2 Stage Delay:

OFF: Single Stage Delay Mode.

ON: Two Stage Delay Mode.

SW 1/10 - Alarms on Evac Only:

OFF: Sounders operate on any fire condition including evacuate.

ON: Selects sounders to operate only when the panel is in the evacuate condition

[Not EN54 complaint function. Provided to meet existing customer requirements.]

SW 2/1 - Silence Before Reset:

Select type of reset mode. [Not EN54 compliant function. Provided to meet existing customer requirements]:

OFF: Reset available when panel is in the [un-silenced] fire or fault condition.

ON: Fire Condition Reset available only when panel is in Alarm Silenced condition. Fault reset available when panel is in the fault condition.

SW 2/2 to 2/5 - Delay/Minutes:

Page 30 of 40

Image 30
Contents Technical Data Sheet List Of Contents List Of Figures List of TablesOverview of Installation and Commissioning Install all field wiring and equipmentIntroduction Internal Panel Views Mx-1002 / Mx-1004 Internal ViewMx-1032 Internal View Page Mx-1016 16 -Zone Typical Wiring Schematic Typical Wiring DiagramCircuit Connection Details 2-16 Zone Motherboard Termination Details16 Zone Expansion Board Termination Details Mx-1000 Series C1627 Motherboard Features C1627 Motherboard Layout10 Mx-1000 Series C1632 16-Zone Expansion Board Features Power SuppliesVisual indications Battery Disconnect 11.3 32-Zone Power Supply Features And ConnectionsInstallation Electrical SafetyElectrical Safety Installation Instructions 12.2.1 Mx-1000 Series Panel Installation InstructionsQuantity Description Type Page Installation And Connection Of The C1631 Repeater Interface Repeater Connection Diagram Commissioning Commissioning ChecklistAn Overview Of The Commissioning Procedure IntroductionPre-Commissioning Wiring Check Powering up ConfigurationCommissioning Procedure Commissioning zones Commissioning the Fire and Fault Routing Outputs Commissioning the Fire Protection control signalCommissioning the Class Change Input Commissioning ancillary inputs Commissioning ancillary outputsCommissioning repeaters User Controls and Indications User Indications showing optional clock moduleSwitch Functionality Button Availability Description User Controls showing optional clock moduleEngineer’s Zone/Output Configuration Process Zone or Output ConfigurationOperating the Engineer’s functions Page Engineer’s Zone/Output Configuration Time-out Warning Invalid Configuration conditionsList of configuration DIL switches and their functions Page Delay Switch Settings Delay 2/2 2/3 2/4 2/5 DurationRepeater Quantity C1631 setting for quantity of repeatersC1631 setting for repeater addresses Repeater AddressStandard Module Engineer Mode Optional Clock Module Configuration and SettingEnable/disable earth fault monitoring To Zero the Alarm CounterHhmmss Time Set MM flashing Hhmmss OFF Time MM flashing Link DIL Switch Pole Position Selected Function Configuring the Clock ModuleC1651 Clock Module DIL switch 1 and Link 1 Settings Link Position Selected FunctionWP DIL Switch Error Message 16.3 C1651 Clock Module PCB FeaturesClock Module Error Messages Eeprom Error MessageEeprom 0 Error Eeprom 1 Error ROM Checksum Error messageMechanical, Electrical & Environmental Specification Mechanical Mx-1000 Series Panel Repeater Specification ZoneBattery Mx-1000 Series Panel Repeater Specification Zone Powersonic

Mx-1000 specifications

The BRK electronic Mx-1000 is an innovative and versatile device designed for both home and industrial use, primarily focusing on smoke and carbon monoxide detection. Its advanced features enhance safety, ensuring peace of mind for users in various environments.

One of the standout features of the Mx-1000 is its dual-sensor technology. It combines both photoelectric and ionization sensors, maximizing its ability to detect different types of smoke. Photoelectric sensors are highly effective at identifying smoldering fires, which are often associated with slow-burning materials. On the other hand, ionization sensors excel at detecting fast-flaming fires. This dual capability ensures comprehensive fire detection, making the Mx-1000 one of the most reliable devices in its category.

Another notable characteristic is its built-in carbon monoxide detector. Carbon monoxide is a silent killer, and the Mx-1000 addresses this threat by providing early warning signals when harmful levels of this gas are detected. The integration of both smoke and carbon monoxide detection in a single unit simplifies safety measures and reduces the number of devices required for home and workplace safety.

The Mx-1000 is equipped with advanced digital technology that enhances its functionality. A state-of-the-art microprocessor evaluates alarm conditions more intelligently, which minimizes the chances of false alarms. This feature is particularly beneficial for households that might experience frequent smoke triggers from cooking or other benign sources.

User-friendliness is a key design aspect of the Mx-1000. It features a clear LED display that indicates the operational status, and a simple test button allows users to verify functionality with ease. The device also features a low-battery indicator, ensuring users are always informed about its operational state.

Installation is straightforward, with options for both wall and ceiling mounting to accommodate various room layouts. The Mx-1000 is designed to appeal to a wide range of customers, from DIY enthusiasts to professional installers.

In addition to its technological advancements, the BRK electronic Mx-1000 is built with reliability in mind. Its durable construction is meant to endure various conditions, ensuring longevity and consistent performance over time. This combination of top-tier technology, user-friendly features, and robust design makes the Mx-1000 a trusted choice for those seeking comprehensive safety solutions in smoke and carbon monoxide detection.