BRK electronic Mx-1000 manual Delay Switch Settings, Delay 2/2 2/3 2/4 2/5 Duration

Page 31

Sets the duration of the variable time delay element [i.e. the single stage delay and stage 2 of the two stage delay] in steps of 1 minute within the range 0-9 minutes. See Table 1 - Delay Switch Settings

Table 1 - Delay Switch Settings

Delay

S/W 2/2

S/W 2/3

S/W 2/4

S/W 2/5

Duration

 

 

 

 

 

 

 

 

 

Delay

Off

Off

Off

Off

disabled

 

 

 

 

 

 

 

 

 

1 min

On

Off

Off

Off

 

 

 

 

 

2 min

Off

On

Off

Off

 

 

 

 

 

3 min

On

On

Off

Off

 

 

 

 

 

4 min

Off

Off

On

Off

 

 

 

 

 

5 min

On

Off

On

Off

 

 

 

 

 

6 min

Off

On

On

Off

 

 

 

 

 

7 min

On

On

On

Off

 

 

 

 

 

8 min

Off

Off

Off

On

 

 

 

 

 

9 min

On

Off

Off

On

 

 

 

 

 

10 min

Off

On

Off

On

 

 

 

 

 

10 min

On

On

Off

On

 

 

 

 

 

10 min

Off

Off

On

On

 

 

 

 

 

10 min

On

Off

On

On

 

 

 

 

 

10 min

Off

On

On

On

 

 

 

 

 

10 min

On

On

On

On

 

 

 

 

 

SW 2/6 - Enable Zonal Alarms:

Select the type of sounder alarm response to a fire condition in conjunction with the Pulse Non Alarm Zones switch described below. [Not EN54 compliant function. Provided to meet existing customer requirements] :

OFF: General Alarm Mode – all sounders operate continuously until silenced.

ON: Zonal Sounder Mode - Sounder groups for zones not in the alarm condition may be selected, via the Pulse Non Alarm Zones switch [SW 2/7], to pulse or not to operate.

Note: Zonal alarms on the 2/4 zone panel affects the standard sounder circuits on the motherboard. On the 8, 16 and 32 zone panels, it affects only the [future] expansion module sounder circuits.

SW 2/7- Pulse Non Alarm Zones:

Select the type of zonal sounder alarm response to a fire condition in conjunction with the Zone Alarms switch [SW 2/6] described above. [Not EN54 compliant function. Provided to meet existing customer requirements]:

With the Zone Alarms switch [SW 2/6] in the On position [Zonal Sounder Mode]:

SW2/7 OFF: Zonal sounders for zone in the fire condition operate continuously until silenced. All others are silent.

SW2/7 ON: Zonal sounders operate continuously - all other sounders operate in pulsed mode until silenced.

Page 31 of 40

Image 31
Contents Technical Data Sheet List Of Contents List of Tables List Of FiguresInstall all field wiring and equipment Overview of Installation and CommissioningIntroduction Mx-1002 / Mx-1004 Internal View Internal Panel ViewsMx-1032 Internal View Page Typical Wiring Diagram Mx-1016 16 -Zone Typical Wiring Schematic2-16 Zone Motherboard Termination Details Circuit Connection Details16 Zone Expansion Board Termination Details C1627 Motherboard Layout Mx-1000 Series C1627 Motherboard FeaturesPower Supplies 10 Mx-1000 Series C1632 16-Zone Expansion Board FeaturesVisual indications 11.3 32-Zone Power Supply Features And Connections Battery DisconnectElectrical Safety InstallationElectrical Safety 12.2.1 Mx-1000 Series Panel Installation Instructions Installation InstructionsQuantity Description Type Page Installation And Connection Of The C1631 Repeater Interface Repeater Connection Diagram Introduction Commissioning ChecklistAn Overview Of The Commissioning Procedure CommissioningPre-Commissioning Wiring Check Configuration Powering upCommissioning Procedure Commissioning zones Commissioning the Fire Protection control signal Commissioning the Fire and Fault Routing OutputsCommissioning the Class Change Input Commissioning ancillary outputs Commissioning ancillary inputsCommissioning repeaters User Indications showing optional clock module User Controls and IndicationsUser Controls showing optional clock module Switch Functionality Button Availability DescriptionZone or Output Configuration Engineer’s Zone/Output Configuration ProcessOperating the Engineer’s functions Page Invalid Configuration conditions Engineer’s Zone/Output Configuration Time-out WarningList of configuration DIL switches and their functions Page Delay 2/2 2/3 2/4 2/5 Duration Delay Switch SettingsRepeater Address C1631 setting for quantity of repeatersC1631 setting for repeater addresses Repeater QuantityTo Zero the Alarm Counter Optional Clock Module Configuration and SettingEnable/disable earth fault monitoring Standard Module Engineer ModeHhmmss Time Set MM flashing Hhmmss OFF Time MM flashing Link Position Selected Function Configuring the Clock ModuleC1651 Clock Module DIL switch 1 and Link 1 Settings Link DIL Switch Pole Position Selected FunctionEeprom Error Message 16.3 C1651 Clock Module PCB FeaturesClock Module Error Messages WP DIL Switch Error MessageROM Checksum Error message Eeprom 0 Error Eeprom 1 ErrorMechanical Mx-1000 Series Panel Repeater Specification Zone Mechanical, Electrical & Environmental SpecificationPowersonic Battery Mx-1000 Series Panel Repeater Specification Zone

Mx-1000 specifications

The BRK electronic Mx-1000 is an innovative and versatile device designed for both home and industrial use, primarily focusing on smoke and carbon monoxide detection. Its advanced features enhance safety, ensuring peace of mind for users in various environments.

One of the standout features of the Mx-1000 is its dual-sensor technology. It combines both photoelectric and ionization sensors, maximizing its ability to detect different types of smoke. Photoelectric sensors are highly effective at identifying smoldering fires, which are often associated with slow-burning materials. On the other hand, ionization sensors excel at detecting fast-flaming fires. This dual capability ensures comprehensive fire detection, making the Mx-1000 one of the most reliable devices in its category.

Another notable characteristic is its built-in carbon monoxide detector. Carbon monoxide is a silent killer, and the Mx-1000 addresses this threat by providing early warning signals when harmful levels of this gas are detected. The integration of both smoke and carbon monoxide detection in a single unit simplifies safety measures and reduces the number of devices required for home and workplace safety.

The Mx-1000 is equipped with advanced digital technology that enhances its functionality. A state-of-the-art microprocessor evaluates alarm conditions more intelligently, which minimizes the chances of false alarms. This feature is particularly beneficial for households that might experience frequent smoke triggers from cooking or other benign sources.

User-friendliness is a key design aspect of the Mx-1000. It features a clear LED display that indicates the operational status, and a simple test button allows users to verify functionality with ease. The device also features a low-battery indicator, ensuring users are always informed about its operational state.

Installation is straightforward, with options for both wall and ceiling mounting to accommodate various room layouts. The Mx-1000 is designed to appeal to a wide range of customers, from DIY enthusiasts to professional installers.

In addition to its technological advancements, the BRK electronic Mx-1000 is built with reliability in mind. Its durable construction is meant to endure various conditions, ensuring longevity and consistent performance over time. This combination of top-tier technology, user-friendly features, and robust design makes the Mx-1000 a trusted choice for those seeking comprehensive safety solutions in smoke and carbon monoxide detection.