For Output Delay configuration, through Sounders, Fire Protection and Fire Routing outputs in forward [Select↓] or reverse [Select ↑] sequence starting at Sounders.

3. To change the configuration of a selected zone or output:

With the cursor flashing on the selected zone or output:

Operation of the ENABLE button will apply the configuration functionality to the selected zone/output causing the associated fault/disabled LED to provide a continuous indication.

Operation of the DISABLE button will clear the configuration from the selection and restore normal operation. The fault/disabled LED will clear.

By repeating steps 2 and 3, any number of zones [or outputs] can be configured.

4. To quit the programmable configuration mode:

To return the panel to normal operating mode applying the updated configuration:

Open the panel door and return the selected Config DIL switch on the motherboard to the OFF position.

The CONFIG ENABLED LED on the motherboard will clear, the panel buzzer will silence and the flashing System Fault indication and zone/output configuration status indications on the display will clear as will the cursor and the Select indications. Any current alarms, disablements, will be re-indicated along with any active status indications [Delay on etc.].

Close and lock the panel door.

Return the ACCESS keyswitch to the “0” position to disable the controls on the display.

IMPORTANT NOTE: WHILE THE PANEL IS IN THE ENGINEER’S ZONAL/OUTPUT CONFIGURATION MODE, ALL ZONAL INPUTS ARE IN PERMANENT RESET AND OUTPUTS ARE INHIBITED – THE PANEL WILL NOT RESPOND TO ANY FIRE ALARM.

15.3To Restore the Factory Default Configuration for Zones & Outputs:

Open the panel door and locate the DIL switches SW1-4 to SW1-8 on the motherboard [Config Non-latch Zones; Config I.S. Zones; Config M/S Zones; Config Delay Zones; Config Delay O/Ps] and move the switch actuator on each switch to the On position.

The Config Enabled LED on the motherboard will flash.

The Panel’s System Fault LED will flash and the buzzer will operate.

Any standing fault or disablement indications will clear.

It will not be possible to enter the Select Mode.

Press the Disable button on the panel’s display.

Return DIL switches 1-4 to 1-8 to the OFF position.

The Config Enabled LED on the motherboard will clear.

The Panel’s System Fault LED will flash and the buzzer will clear.

The factory default configuration [all zones as latching fire, non-delay, standard [non- intrinsically safe] will be restored and the Fire Routing, Fire Protection and Sounder outputs will no longer be delayed

Page 28 of 40

Image 28
Contents Technical Data Sheet List Of Contents List Of Figures List of TablesInstall all field wiring and equipment Overview of Installation and CommissioningIntroduction Internal Panel Views Mx-1002 / Mx-1004 Internal ViewMx-1032 Internal View Page Mx-1016 16 -Zone Typical Wiring Schematic Typical Wiring Diagram2-16 Zone Motherboard Termination Details Circuit Connection Details16 Zone Expansion Board Termination Details Mx-1000 Series C1627 Motherboard Features C1627 Motherboard LayoutPower Supplies 10 Mx-1000 Series C1632 16-Zone Expansion Board FeaturesVisual indications Battery Disconnect 11.3 32-Zone Power Supply Features And ConnectionsInstallation Electrical SafetyElectrical Safety 12.2.1 Mx-1000 Series Panel Installation Instructions Installation InstructionsQuantity Description Type Page Installation And Connection Of The C1631 Repeater Interface Repeater Connection Diagram Commissioning Checklist An Overview Of The Commissioning ProcedureCommissioning IntroductionPre-Commissioning Wiring Check Configuration Powering upCommissioning Procedure Commissioning zones Commissioning the Fire Protection control signal Commissioning the Fire and Fault Routing OutputsCommissioning the Class Change Input Commissioning ancillary outputs Commissioning ancillary inputsCommissioning repeaters User Controls and Indications User Indications showing optional clock moduleSwitch Functionality Button Availability Description User Controls showing optional clock moduleZone or Output Configuration Engineer’s Zone/Output Configuration ProcessOperating the Engineer’s functions Page Invalid Configuration conditions Engineer’s Zone/Output Configuration Time-out WarningList of configuration DIL switches and their functions Page Delay Switch Settings Delay 2/2 2/3 2/4 2/5 DurationC1631 setting for quantity of repeaters C1631 setting for repeater addressesRepeater Quantity Repeater AddressOptional Clock Module Configuration and Setting Enable/disable earth fault monitoringStandard Module Engineer Mode To Zero the Alarm CounterHhmmss Time Set MM flashing Hhmmss OFF Time MM flashing Configuring the Clock Module C1651 Clock Module DIL switch 1 and Link 1 SettingsLink DIL Switch Pole Position Selected Function Link Position Selected Function16.3 C1651 Clock Module PCB Features Clock Module Error MessagesWP DIL Switch Error Message Eeprom Error MessageEeprom 0 Error Eeprom 1 Error ROM Checksum Error messageMechanical, Electrical & Environmental Specification Mechanical Mx-1000 Series Panel Repeater Specification ZoneBattery Mx-1000 Series Panel Repeater Specification Zone Powersonic

Mx-1000 specifications

The BRK electronic Mx-1000 is an innovative and versatile device designed for both home and industrial use, primarily focusing on smoke and carbon monoxide detection. Its advanced features enhance safety, ensuring peace of mind for users in various environments.

One of the standout features of the Mx-1000 is its dual-sensor technology. It combines both photoelectric and ionization sensors, maximizing its ability to detect different types of smoke. Photoelectric sensors are highly effective at identifying smoldering fires, which are often associated with slow-burning materials. On the other hand, ionization sensors excel at detecting fast-flaming fires. This dual capability ensures comprehensive fire detection, making the Mx-1000 one of the most reliable devices in its category.

Another notable characteristic is its built-in carbon monoxide detector. Carbon monoxide is a silent killer, and the Mx-1000 addresses this threat by providing early warning signals when harmful levels of this gas are detected. The integration of both smoke and carbon monoxide detection in a single unit simplifies safety measures and reduces the number of devices required for home and workplace safety.

The Mx-1000 is equipped with advanced digital technology that enhances its functionality. A state-of-the-art microprocessor evaluates alarm conditions more intelligently, which minimizes the chances of false alarms. This feature is particularly beneficial for households that might experience frequent smoke triggers from cooking or other benign sources.

User-friendliness is a key design aspect of the Mx-1000. It features a clear LED display that indicates the operational status, and a simple test button allows users to verify functionality with ease. The device also features a low-battery indicator, ensuring users are always informed about its operational state.

Installation is straightforward, with options for both wall and ceiling mounting to accommodate various room layouts. The Mx-1000 is designed to appeal to a wide range of customers, from DIY enthusiasts to professional installers.

In addition to its technological advancements, the BRK electronic Mx-1000 is built with reliability in mind. Its durable construction is meant to endure various conditions, ensuring longevity and consistent performance over time. This combination of top-tier technology, user-friendly features, and robust design makes the Mx-1000 a trusted choice for those seeking comprehensive safety solutions in smoke and carbon monoxide detection.