2700-I WOOD INSERT (ACT)

R

Calculating Alternate

Floor Protection

Material

Thermal Conductivity: k value

The k value indicates the amount of heat (in BTU’s) that will flow in 1 hour through 1 square foot of a uniform material 1 inch thick for each degree (F) of temperature difference from one side of the material to the other. The LOWER the k factor means less heat is being conducted through the non-combustible material to the combustible material beneath it. The k value of a material must be equal or smaller then the required k value to be accept- able.

(BTU) (inch) (foot2 (hour) (oF)

Thermal Resistance: R value

The R value is a measure of a material’s resistance to heat transfer. R value is convenient when more than one material is used since you can add the R values together, whereas you can not do this for k value. The HIGHER the R factor means less heat is being conducted through the non-com- bustible material to the combustible material beneath it. The R value of a material must be equal or larger then the re- quired R value to be acceptable.

Converting k to R:

Divide 1 by k and multiply the results times the thickness in inch- es of the material.

R = 1/k x inches of thickness

Converting R to k:

Divide the inches of thickness by R. k = inches of thickness/R

Calculations:

Example: Floor protection requires k value of 0.84 and 3/4 inch thick.

Alternative material has a k value of 0.6 and is 3/4 inch thick.

Divide 0.6 by .75 = k value of 0.80. This k value is smaller than 0.84 and therefore is acceptable.

WARNING

Asphyxiation Risk.

Do NOT connect this unit to a chimney flue servicing another appliance.

Do NOT connect to any air distribution duct or system.

May allow flue gases to enter the house.

Design, Installation & Location

Consideration must be given to:

Safety

Convenience

Traffic flow

Chimney and chimney connector required

It is a good idea to plan your installation on paper, using exact measurements for clearances and floor protection, before actually beginning the installation. If you are not using an existing chimney, place the appliance where there will be a clear passage for a factory-built listed chimney through the ceiling and roof.

We recommend that a qualified building inspector and your insurance company representative review your plans before and after installation.

If this appliance is in an area where children may be near it is recommended that you purchase a decorative barrier to go in front of the appliance. Remember to always keep children away while it is operating and do not let anyone operate this appliance unless they are familiar with these operating instructions.

WARNING

Fire Risk.

Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:

Installation and use of any damaged appliance.

Modification of the appliance.

Installation other than as instructed by Hearth & Home Technologies.

Installation and/or use of any component part not approved by Hearth & Home Technologies.

Operating appliance without fully assembling all components.

Operating appliance without legs attached (if supplied with unit).

Do NOT Overfire - If appliance or chimney connector glows, you are overfiring.

Any such action that may cause a fire hazard.

WARNING

Fire Risk.

Inspect appliance and components for damage.

Damaged parts may impair safe operation.

Do NOT install damaged components.

Do NOT install incomplete components.

Do NOT install substitute components.

Report damaged parts to dealer.

Page

7007-161H

September 1, 2008

Image 6
Contents Hot glass will cause burns Advanced Combustion Technology ACTDo not Discard this Manual Fire RiskTest Lab & Report No 007Serial Number Model Name Manufactured DateTable of Contents United States and Canada DimensionsClearances to Combustibles Maximum Mantel Depth 10 inches 254mmListings Chimney HEIGHT/DRAFT CONT’D Installation recommendationsInstallation Chimney HEIGHT/DRAFTDesign, Installation & Location Calculating Alternate Floor ProtectionMaterial Firestopping Chimney RequirementsOvalizing Round Stainless Steel Liners Chimney to sheathingInstalling Outside Air Cover Box Fire Risk Asphyxiation RiskMasonry Fireplace Using DIRECT-CONNECT Method Metal Heat Circulating masonryUsa installations only Factory built zero clearance fireplaceLeveling Legs Installation in CanadaDoor Handle Assembly Masonry and HEAT-CIRCULATINGOutside AIR Installation Optional Quick Connect CollarAttaching Panels and Trim to the Insert Panel & Trim Assembly InstructionsPanel and Trim SET 13.1FAN Speed Control ADJUSTMENT, if Necessary TOP Installation InstructionsBlower Installation Shock RiskZero Clearance Adjustable Trim SUPPORT, 2 inch to 10 inch Injury Risk Gloves recommended May have sharp edgesOperation Wood Selection and Storage OverfiringBuilding a Fire Opacity Operating TipsBurn Rates ASH RemovalAir quality and your Quadra-Fire Insert START-UP AIR SystemPrimary AIR System Maintenance Creosote Chimney CleaningWhen cleaning glass Ceramic Blanket Brick replacement instructionsBaffle Removal & Installation BaffleExploded View Ceramic BlanketDescription Part Description Alphabetical OrderPart Description Alphabetical Order DescriptionAppliance Item # Accessories in alphabetically order Part NumberItem # Wood Insert, Advanced Combustible Technology ACT 2700-IService And Maintenance Log Date of Service Performed By Description of ServiceWarranty Policy CONDITIONS, Exclusions & Limitation of LiabilityHearth & Home Technologies Limited Warranty Cont’d Wood Insert ACT