Operation

Starting the unit in cooling mode

Before start-up, ensure that all power cables are tightened.

Verify that the unit airflow rate is adjusted according to the information provided in the "Supply fan adjustment" section of this manual.

To start the unit in cooling mode:

Place the zone sensor system switch in the "COOL" position.

Position the cooling setpoint approximately 10° below room temperature and place the fan switch in the "AUTO" or "ON" position.

Turn on unit main power supply.

The condenser fan motor, compressor and supply fan motor should operate automatically.

There will be a delay of up to

5 minutes before the unit starts in cooling mode.

Operating pressures

After the unit has operated in cooling mode for a short period of time, install pressure gauges on the gauge ports of the discharge and suction line valves.

Note: To bypass time delays and verify the operation of this unit from the roof, use the "Test procedure" section in this manual. Check the suction and discharge pressures.

Note: Always route refrigerant hoses through the port hole provided and ensure that the compressor access panel is in place.

Cooling shutdown

To exit the test mode, disconnect unit power for 3-5 seconds and reapply. When running the unit using the zone sensor as the control, position the selector switch to "OFF".

There may be a delay of up to

3 minutes before compressors shut down and an additional one minute before the fan shuts down in this setting.

Do not de-energize main power disconnect except when unit is to be serviced. Power is required to keep the compressor crankcase warm and boil off refrigerant in the oil (except on units with Scroll compressors).

Final installation checklist

Are all power cables tightened?

Check torque of power cables contact !

Is the condenser fan and indoor blower operating correctly, i.e. correct rotation and without undue noise?

Are the compressors operating correctly and has the system been checked for leaks?

Have the voltage and running currents been checked to determine if they are within limits?

Have the air discharge grilles been adjusted to balance the system?

Has the ductwork been checked for air leaks and any condensation?

Has the air temperature rise been checked?

Has the indoor airflow been checked and adjusted if necessary?

Has the unit been checked for tubing and sheet metal rattles or any unusual noises?

Are all covers and panels in place and properly fastened?

RT-SVX19A-E4

53

Image 53 Contents
Installation Operation Maintenance Foreword Safety recommendationsReception Reception in France onlyMaintenance contract WarrantyRefrigerant StorageContents Unit Options Unit handling Reception of unitsRooftop unit Unit size Roof curb Installation TKD-WKD-YKD accessoriesSling lengths and maximum unit weight Minimum clearances Minimum clearances mm Dimensions/Weights/ClearancesWeigths & center of gravity Figure Weights of Options & accessoriesUnit mounting on roof Installing the unitInstalling the unit on the ground Horizontal discharge units TKH,WKH,YKH Downflow discharge units TKD,WKD,YKD Using the rooftop curbConnection of duct network Condensate drain line connection Condensate drain pipingGas leak check procedure Gas pipework installationGas burner models UnitFilter arrangement Filter installationFan Speed RPM Standard Drive Supply fan adjustmentMotor sheave / Fan speed To decrease airflow To increase airflowTo increase belt tension Belt tensioningComponent air pressure drops YKD/YKH Pressure drop through accessoriesAirflow EU2/G2 EU4/G4 100% TKD/TKH Pressure drop through accessoriesTKD TKHFilter 100% WKD/WKH Pressure drop through accessoriesWKD WKHYK 155 External static pressure Supply fan performancesYK 175 External static pressure YK 250 External static pressure TK 200 External static pressure TK 175 External static pressure275 300 TK 250 External static pressureExternal Static Pressure Pa 275 300 WK 155 External static pressure Power wiring Factory supplied Disconnect switch OptionElectrical connection TKD/TKH, WKD/WKH units YKD/YKH unitsElectrical Characteristics Unit amps Electrical data YKD/YKH Unit WiringScroll compressors Compressor electrical phasing With Electric heatOutdoor Fan 155 175 200 250 Compressor155 175 200 250 Indoor Fan 155 200 CompressorElectrical data TKD/TKH Supply fan motor Electrical data Combustion Blower Motorr Electrical data YKD/YKH Supply fan motorElectrical data WKD/WKH Supply fan motor Zone sensor wire size and maximum length Control wiringMaximum length Zone sensor wire size Unit controlled by thermostatUnit controlled by Tracker supervisor Unit controlled by BASWall-mounted and duct-mounted CO2 sensors SpecificationsCO2 sensors Wiring the wall-mounted CO2 sensor Power supply requirementsWiring the duct-mounted CO2 sensor CO2 sensor wire sizeMounting the duct-mounted CO2 sensor CO2 sensor maintenanceRemote potentiometer Remote potentiometer dimensionsDuct mounting of fire thermostat Fire thermostatRemote fault relay High temperature safety thermostatClogged filter detector Smoke detectorCommunication Interfaces Hot water coil Hot water coil Installation and connectionDown flow units only Water connection inlet/outlet 1 ¼ ISO R7Soft Starter Electric Heater25% manual fresh air hood 25% fresh air hoodDownflow version Barometric reliefOperation with a conventional thermostat OperationConventional thermostat Heat Pump Thermostat signals are as followsConventional thermostat Gas/ Electric, Electric Heat Cooling/Economizer Operation Unoccupied modeCooling/Economizer Operation with Thermostat1,2 OK toECA board LED Setting the economizer or 0-50% motorized hood optionMinimum fresh air adjustment Test mode procedure at the ReliaTel control board Test procedures Power-up initialization Auto Test Mode Step Test ModeTest modes StepGas valve Unit start-upGas burner data Marking category of the gas section in different countriesFinal installation checklist Starting the unit in cooling modeCheck torque of power cables contact Operating pressuresEvaporator Fan Operation Cooling without an EconomizerCooling with an Economizer Low Ambient OperationEconomizer Set-Up Potentiometer SettingReliaTel Control Heating Operation Ignition ModuleLED status Final installation checklistDiagnostics Refrigerant charge End user routine maintenanceAir filters Hot water coil option Service technician maintenanceCondenser coil System Status Checkout Procedure TroubleshootingSystem failure Service FailureHeating Failure Cooling FailureZone Temperature Sensor ZTS Service Indicator Resetting Cooling and Ignition LockoutsClogged Filter Switch Fan Failure SwitchThermistor Resistance / Temperature Chart Temperature/resistance coefficient is negativeLiterature order number