Installation

Filter installation

To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.

Each unit ships with 40 or 50 mm thick filters. Number and size of filters is determined by size and configuration of the unit.

CAUTION! Do not operate unit without filters in place.

The maximum pressure drops allowable on filters are:

EU2/G2: 120 Pa

EU4/G4: 150 Pa

Table 5 - Filter arrangement

UNIT

 

EU2/G2

 

EU4/G4

Qty

Size

Qty

Size

 

 

 

 

 

 

YKH/YKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH/YKD 175

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

YKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH 250

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

YKD 250

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH/TKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH/TKD 175

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

TKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH 250

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

TKD 250

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH/WKD 125

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH/WKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

WKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

14

RT-SVX19A-E4

Image 14
Contents Installation Operation Maintenance Reception Safety recommendationsForeword Reception in France onlyRefrigerant WarrantyMaintenance contract StorageContents Unit Options Unit handling Reception of unitsRooftop unit Unit size Roof curb Installation TKD-WKD-YKD accessoriesSling lengths and maximum unit weight Dimensions/Weights/Clearances Minimum clearances Minimum clearances mmWeights of Options & accessories Weigths & center of gravity FigureUnit mounting on roof Installing the unitInstalling the unit on the ground Horizontal discharge units TKH,WKH,YKH Downflow discharge units TKD,WKD,YKD Using the rooftop curbConnection of duct network Condensate drain piping Condensate drain line connectionGas burner models Gas pipework installationGas leak check procedure UnitFilter installation Filter arrangementFan Speed RPM Standard Drive Supply fan adjustmentMotor sheave / Fan speed To increase belt tension To increase airflowTo decrease airflow Belt tensioningYKD/YKH Pressure drop through accessories Component air pressure dropsTKD TKD/TKH Pressure drop through accessoriesAirflow EU2/G2 EU4/G4 100% TKHWKD WKD/WKH Pressure drop through accessoriesFilter 100% WKHSupply fan performances YK 155 External static pressureYK 175 External static pressure YK 250 External static pressure TK 175 External static pressure TK 200 External static pressure275 300 TK 250 External static pressureExternal Static Pressure Pa 275 300 WK 155 External static pressure Electrical connection Factory supplied Disconnect switch OptionPower wiring TKD/TKH, WKD/WKH units YKD/YKH unitsScroll compressors Compressor electrical phasing Electrical data YKD/YKH Unit WiringElectrical Characteristics Unit amps With Electric heat155 175 200 250 Compressor Outdoor Fan155 175 200 250 Indoor Fan 155 200 CompressorElectrical data TKD/TKH Supply fan motor Electrical data Combustion Blower Motorr Electrical data YKD/YKH Supply fan motorElectrical data WKD/WKH Supply fan motor Maximum length Zone sensor wire size Control wiringZone sensor wire size and maximum length Unit controlled by thermostatUnit controlled by BAS Unit controlled by Tracker supervisorWall-mounted and duct-mounted CO2 sensors SpecificationsCO2 sensors Wiring the duct-mounted CO2 sensor Power supply requirementsWiring the wall-mounted CO2 sensor CO2 sensor wire sizeCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatClogged filter detector High temperature safety thermostatRemote fault relay Smoke detectorCommunication Interfaces Down flow units only Hot water coil Installation and connectionHot water coil Water connection inlet/outlet 1 ¼ ISO R7Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodBarometric relief Downflow versionOperation Operation with a conventional thermostatConventional thermostat Heat Pump Thermostat signals are as followsConventional thermostat Gas/ Electric, Electric Heat Cooling/Economizer Operation with Thermostat1,2 Unoccupied modeCooling/Economizer Operation OK toSetting the economizer or 0-50% motorized hood option ECA board LEDMinimum fresh air adjustment Test mode procedure at the ReliaTel control board Test proceduresPower-up initialization Test modes Step Test ModeAuto Test Mode StepUnit start-up Gas valveMarking category of the gas section in different countries Gas burner dataCheck torque of power cables contact Starting the unit in cooling modeFinal installation checklist Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerReliaTel Control Heating Operation Potentiometer SettingEconomizer Set-Up Ignition ModuleLED status Final installation checklistDiagnostics Refrigerant charge End user routine maintenanceAir filters Hot water coil option Service technician maintenanceCondenser coil Troubleshooting System Status Checkout ProcedureHeating Failure Service FailureSystem failure Cooling FailureClogged Filter Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Fan Failure SwitchTemperature/resistance coefficient is negative Thermistor Resistance / Temperature ChartLiterature order number

RT-SVX19A-E4 specifications

The Trane RT-SVX19A-E4 is a groundbreaking rooftop unit designed for versatile commercial heating and cooling applications. This model stands out for its innovative technology and robust features, making it a preferred choice for many businesses seeking efficient climate control solutions.

One of the primary characteristics of the RT-SVX19A-E4 is its exceptional energy efficiency. It utilizes advanced variable-speed technology, allowing it to adjust the compressor's output based on real-time demand. This not only reduces energy consumption significantly but also provides more accurate temperature control, enhancing overall comfort within the space. The unit is designed with high-efficiency fan motors and optimized heat exchangers, which contribute to its impressive Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings.

The Trane RT-SVX19A-E4 also features a robust and durable design, built to withstand a variety of weather conditions. Its all-weather cabinet protects the internal components from environmental stresses, ensuring longevity and reliable performance. The unit is equipped with corrosion-resistant materials that enhance its durability, making it suitable for both coastal and urban environments.

Another notable feature is its advanced control system. The RT-SVX19A-E4 comes with Trane's IntelliPak controls, which provide users with precise monitoring and management capabilities. This smart control system enables remote access via internet connectivity, allowing facility managers to monitor performance, adjust settings, and diagnose issues in real-time, improving operational efficiency and reducing maintenance costs.

Additionally, the RT-SVX19A-E4 offers a range of customization options. It can be tailored to meet specific operational needs, with various configurations available for air flow, heating, and cooling needs. This flexibility ensures organizations can find a solution that best fits their requirements, whether it be for an office building, retail space, or industrial facility.

In conclusion, the Trane RT-SVX19A-E4 represents a significant advancement in rooftop HVAC technology, combining energy efficiency, durability, and intelligent controls. Its ability to adapt to varying demands, coupled with customizable options, makes it an excellent investment for businesses looking to enhance their indoor climate while minimizing energy expenses.