Trane RT-SVX19A-E4 manual Electrical data YKD/YKH Supply fan motor

Page 30

Installation

Table 26 - Electrical data - YKD/YKH Supply fan motor

 

 

 

TKD/H

TKD/H

TKD/H

TKD/H

 

 

 

155

175

200

250

 

 

 

 

 

 

 

 

 

 

Indoor Fan

 

 

 

 

 

 

 

 

 

Nominal Airflow

(m3/h)

8500

9850

11210

14100

 

Static pressure available (4)

(Pa)

175

250

200

125

 

 

 

 

 

 

 

 

Maximum static pressure available (5)

(Pa)

325

400

375

350

 

 

 

 

 

 

 

 

Type

 

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

 

 

 

 

 

 

 

 

Diameter / Width

(in / in)

15" / 15"

15" / 15"

18" / 18"

18" / 18"

 

 

 

 

 

 

 

 

Drive type

 

Belt

Belt

Belt

Belt

 

 

 

 

 

 

 

 

 

 

 

Number

#

 

1

 

1

 

1

1

 

 

 

 

 

 

 

 

 

 

 

Motor HP (Standard/Oversized)

(kW)

2.2

/ 3.0

3.0

/ 4.6

3.0

/ 4.6

4.6 / -

 

 

 

 

 

 

 

 

 

 

 

Motor Rated Amps (Standard/Oversized)

(A)

4.6

/ 6.5

6.5

/ 9.0

6.5

/ 9.0

9 / -

 

 

 

 

 

 

 

 

Motor Locked rotor Amps (Standard/Oversized)

(A)

36.4 / 57

57 / 71.9

57 / 71.9

71.9 / -

 

 

 

 

 

 

 

 

 

 

 

Motor RPM (Standard/Oversized)

(rpm)

1450

/ 2870

2870

/ 2900

2870

/ 2900

2900 / -

(4)At the nominal airflow with standard drive

(5)At the nominal airflow with oversized drive when available

Table 27 - Electrical data - WKD/WKH Supply fan motor

 

 

 

WKD/H

WKD/H

WKD/H

 

 

 

125

155

200

 

 

 

 

 

 

 

 

 

Indoor Fan

 

 

 

 

 

 

 

 

Nominal Airflow

(m3/h)

7140

8500

11210

 

Static pressure available (4)

(Pa)

200

175

200

 

 

 

 

 

 

 

Maximum static pressure available (5)

(Pa)

425

325

350

 

 

 

 

 

 

 

Type

 

FC Centrifugal

FC Centrifugal

FC Centrifugal

 

 

 

 

 

 

 

Diameter / Width

(in / in)

15" / 15"

15" / 15"

18" / 18"

 

 

 

 

 

 

 

Drive type

 

Belt

Belt

Belt

 

 

 

 

 

 

 

 

 

 

Number

#

 

1

 

1

 

1

 

 

 

 

 

 

 

 

 

 

Motor HP (Standard/Oversized)

(kW)

2.2

/ 3.0

2.2

/ 3.0

3.0

/ 4.6

 

 

 

 

 

 

 

 

 

 

Motor Rated Amps (Standard/Oversized)

(A)

4.6

/ 6.5

4.6

/ 6.5

6.5

/ 9.0

 

 

 

 

 

 

 

Motor Locked rotor Amps (Standard/Oversized)

(A)

36.4 / 57

36.4 / 57

57 / 71.9

 

 

 

 

 

 

 

 

 

 

Motor RPM (Standard/Oversized)

(rpm)

1450

/ 2870

1450

/ 2870

2870

/ 2900

(4)At the nominal airflow with standard drive

(5)At the nominal airflow with oversized drive when available

Table 28 - Electrical data - Combustion Blower Motorr

 

 

 

YKD/H

YKD/H

YKD/H

YKD/H

 

 

 

155

175

200

250

 

 

 

 

 

 

 

Gas burner

 

 

 

 

 

 

Heating Models

 

G350

G350

G350

G350

 

 

 

 

 

 

 

 

Heating Input (G20)

(kW)

77

77

77

77

 

 

 

 

 

 

 

 

Heating Output

(kW)

69.3

69.3

69.3

69.3

 

 

 

 

 

 

 

 

Steady State Efficiency

(%)

90

90

90

90

 

 

 

 

 

 

 

 

No. Burners

 

1

1

1

1

 

 

 

 

 

 

 

 

No. Stages

 

2

2

2

2

 

 

 

 

 

 

 

 

Gas Connection Pipe Size

 

3/4" NPT

3/4" NPT

3/4" NPT

3/4" NPT

 

 

 

 

 

 

 

30

RT-SVX19A-E4

Image 30
Contents Installation Operation Maintenance Reception Safety recommendationsForeword Reception in France onlyRefrigerant WarrantyMaintenance contract StorageContents Unit Options Reception of units Rooftop unitUnit handling Roof curb Installation TKD-WKD-YKD accessories Sling lengths and maximum unit weightUnit size Dimensions/Weights/Clearances Minimum clearances Minimum clearances mmWeights of Options & accessories Weigths & center of gravity FigureInstalling the unit Installing the unit on the groundUnit mounting on roof Downflow discharge units TKD,WKD,YKD Using the rooftop curb Connection of duct networkHorizontal discharge units TKH,WKH,YKH Condensate drain piping Condensate drain line connectionGas burner models Gas pipework installationGas leak check procedure UnitFilter installation Filter arrangementSupply fan adjustment Motor sheave / Fan speedFan Speed RPM Standard Drive To increase belt tension To increase airflowTo decrease airflow Belt tensioningYKD/YKH Pressure drop through accessories Component air pressure dropsTKD TKD/TKH Pressure drop through accessoriesAirflow EU2/G2 EU4/G4 100% TKHWKD WKD/WKH Pressure drop through accessoriesFilter 100% WKHSupply fan performances YK 155 External static pressureYK 175 External static pressure YK 250 External static pressure TK 175 External static pressure TK 200 External static pressureTK 250 External static pressure External Static Pressure Pa 275 300275 300 WK 155 External static pressure Electrical connection Factory supplied Disconnect switch OptionPower wiring TKD/TKH, WKD/WKH units YKD/YKH unitsScroll compressors Compressor electrical phasing Electrical data YKD/YKH Unit WiringElectrical Characteristics Unit amps With Electric heat155 175 200 250 Compressor Outdoor Fan155 200 Compressor Electrical data TKD/TKH Supply fan motor155 175 200 250 Indoor Fan Electrical data YKD/YKH Supply fan motor Electrical data WKD/WKH Supply fan motorElectrical data Combustion Blower Motorr Maximum length Zone sensor wire size Control wiringZone sensor wire size and maximum length Unit controlled by thermostatUnit controlled by BAS Unit controlled by Tracker supervisorSpecifications CO2 sensorsWall-mounted and duct-mounted CO2 sensors Wiring the duct-mounted CO2 sensor Power supply requirementsWiring the wall-mounted CO2 sensor CO2 sensor wire sizeCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatClogged filter detector High temperature safety thermostatRemote fault relay Smoke detectorCommunication Interfaces Down flow units only Hot water coil Installation and connectionHot water coil Water connection inlet/outlet 1 ¼ ISO R7Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodBarometric relief Downflow versionOperation Operation with a conventional thermostatThermostat signals are as follows Conventional thermostat Gas/ Electric, Electric HeatConventional thermostat Heat Pump Cooling/Economizer Operation with Thermostat1,2 Unoccupied modeCooling/Economizer Operation OK toSetting the economizer or 0-50% motorized hood option ECA board LEDMinimum fresh air adjustment Test procedures Power-up initializationTest mode procedure at the ReliaTel control board Test modes Step Test ModeAuto Test Mode StepUnit start-up Gas valveMarking category of the gas section in different countries Gas burner dataCheck torque of power cables contact Starting the unit in cooling modeFinal installation checklist Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerReliaTel Control Heating Operation Potentiometer SettingEconomizer Set-Up Ignition ModuleFinal installation checklist DiagnosticsLED status End user routine maintenance Air filtersRefrigerant charge Service technician maintenance Condenser coilHot water coil option Troubleshooting System Status Checkout ProcedureHeating Failure Service FailureSystem failure Cooling FailureClogged Filter Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Fan Failure SwitchTemperature/resistance coefficient is negative Thermistor Resistance / Temperature ChartLiterature order number

RT-SVX19A-E4 specifications

The Trane RT-SVX19A-E4 is a groundbreaking rooftop unit designed for versatile commercial heating and cooling applications. This model stands out for its innovative technology and robust features, making it a preferred choice for many businesses seeking efficient climate control solutions.

One of the primary characteristics of the RT-SVX19A-E4 is its exceptional energy efficiency. It utilizes advanced variable-speed technology, allowing it to adjust the compressor's output based on real-time demand. This not only reduces energy consumption significantly but also provides more accurate temperature control, enhancing overall comfort within the space. The unit is designed with high-efficiency fan motors and optimized heat exchangers, which contribute to its impressive Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings.

The Trane RT-SVX19A-E4 also features a robust and durable design, built to withstand a variety of weather conditions. Its all-weather cabinet protects the internal components from environmental stresses, ensuring longevity and reliable performance. The unit is equipped with corrosion-resistant materials that enhance its durability, making it suitable for both coastal and urban environments.

Another notable feature is its advanced control system. The RT-SVX19A-E4 comes with Trane's IntelliPak controls, which provide users with precise monitoring and management capabilities. This smart control system enables remote access via internet connectivity, allowing facility managers to monitor performance, adjust settings, and diagnose issues in real-time, improving operational efficiency and reducing maintenance costs.

Additionally, the RT-SVX19A-E4 offers a range of customization options. It can be tailored to meet specific operational needs, with various configurations available for air flow, heating, and cooling needs. This flexibility ensures organizations can find a solution that best fits their requirements, whether it be for an office building, retail space, or industrial facility.

In conclusion, the Trane RT-SVX19A-E4 represents a significant advancement in rooftop HVAC technology, combining energy efficiency, durability, and intelligent controls. Its ability to adapt to varying demands, coupled with customizable options, makes it an excellent investment for businesses looking to enhance their indoor climate while minimizing energy expenses.