Trane RT-SVX19A-E4 manual Economizer Set-Up, ReliaTel Control Heating Operation, Ignition Module

Page 56

Operation

Economizer Set-Up

Adjusting the minimum position potentiometer located on the unit economizer Actuator (ECA) sets the required amount of ventilation air.

Two of the three methods for determining the suitability of the outside air can be selected utilizing the enthalpy potentiometer on the ECA, as described below:

1.Ambient Temperature - controlling the economizing cycle by sensing the outside air dry bulb temperature. The Table below lists the selectable dry bulb values by potentiometer setting.

2.Reference Enthalpy - controlling the economizer cycle by sensing the outdoor air humidity. The Table below lists the selectable enthalpy values by potentiometer setting.

If the outside air enthalpy value is less than the selected value, the economizer is allowed to operate.

3.Comparative Enthalpy - By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the unit control processor (RTRM) will be able to establish which conditions are best suited for maintaining the zone temperature, i.e. indoor conditions or outdoor conditions. The potentiometer located on the ECA is non-functional when both the temperature and humidity sensors are installed.

Table 39 - Potentiometer Setting

Potentiometer

Dry BuIb

Enthalpy

Setting

(°C)

(KJ/kg)

 

 

 

A

23*

63

 

 

 

B

21

58

 

 

 

C

19

53

 

 

 

D

17

51

*Factory Setting

ReliaTel™ Control Heating Operation

When the system switch is set to the "Heat" position and the zone temperature falls below the heating setpoint controlband, a heat cycle is initiated when the RTRM communicates ignition information to the Ignition module (IGN).

Ignition Module

Two Stage (IGN) runs self-check (including verification that the gas valve is de-energized). (IGN) checks the high-limit switches (TC01 & TC02) for normally closed contacts. With 115 VAC power supplied to the ignition module (IGN), the hot surface ignition probe (IP) is preheated for approximately

45 seconds. The gas valve (GV) is energized for approximately

7 seconds for trial for ignition, to ignite the burner.

Once the burner is ignited, the hot surface ignition probe (IP) is de- energized by the ignition module (IGN) and functions as the flame sensing device.

If the burner fails to ignite, the ignition module will make two more attempts before locking out. The green LED will indicate a lock out by two fast flashes. An ignition lockout can be reset by:

1.Opening for 3 seconds and closing the main power disconnect switch

2.By switching the "Mode" switch on the zone sensor to "OFF" and then to the desired position

3.Allowing the ignition control module to reset automatically after one hour.

56

RT-SVX19A-E4

Image 56
Contents Installation Operation Maintenance Safety recommendations ForewordReception Reception in France onlyWarranty Maintenance contractRefrigerant StorageContents Unit Options Unit handling Reception of unitsRooftop unit Unit size Roof curb Installation TKD-WKD-YKD accessoriesSling lengths and maximum unit weight Dimensions/Weights/Clearances Minimum clearances Minimum clearances mmWeights of Options & accessories Weigths & center of gravity FigureUnit mounting on roof Installing the unitInstalling the unit on the ground Horizontal discharge units TKH,WKH,YKH Downflow discharge units TKD,WKD,YKD Using the rooftop curbConnection of duct network Condensate drain piping Condensate drain line connectionGas pipework installation Gas leak check procedureGas burner models UnitFilter installation Filter arrangementFan Speed RPM Standard Drive Supply fan adjustmentMotor sheave / Fan speed To increase airflow To decrease airflowTo increase belt tension Belt tensioningYKD/YKH Pressure drop through accessories Component air pressure dropsTKD/TKH Pressure drop through accessories Airflow EU2/G2 EU4/G4 100%TKD TKHWKD/WKH Pressure drop through accessories Filter 100%WKD WKHSupply fan performances YK 155 External static pressureYK 175 External static pressure YK 250 External static pressure TK 175 External static pressure TK 200 External static pressure275 300 TK 250 External static pressureExternal Static Pressure Pa 275 300 WK 155 External static pressure Factory supplied Disconnect switch Option Power wiringElectrical connection TKD/TKH, WKD/WKH units YKD/YKH unitsElectrical data YKD/YKH Unit Wiring Electrical Characteristics Unit ampsScroll compressors Compressor electrical phasing With Electric heat155 175 200 250 Compressor Outdoor Fan155 175 200 250 Indoor Fan 155 200 CompressorElectrical data TKD/TKH Supply fan motor Electrical data Combustion Blower Motorr Electrical data YKD/YKH Supply fan motorElectrical data WKD/WKH Supply fan motor Control wiring Zone sensor wire size and maximum lengthMaximum length Zone sensor wire size Unit controlled by thermostatUnit controlled by BAS Unit controlled by Tracker supervisorWall-mounted and duct-mounted CO2 sensors SpecificationsCO2 sensors Power supply requirements Wiring the wall-mounted CO2 sensorWiring the duct-mounted CO2 sensor CO2 sensor wire sizeCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatHigh temperature safety thermostat Remote fault relayClogged filter detector Smoke detectorCommunication Interfaces Hot water coil Installation and connection Hot water coilDown flow units only Water connection inlet/outlet 1 ¼ ISO R7Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodBarometric relief Downflow versionOperation Operation with a conventional thermostatConventional thermostat Heat Pump Thermostat signals are as followsConventional thermostat Gas/ Electric, Electric Heat Unoccupied mode Cooling/Economizer OperationCooling/Economizer Operation with Thermostat1,2 OK toSetting the economizer or 0-50% motorized hood option ECA board LEDMinimum fresh air adjustment Test mode procedure at the ReliaTel control board Test proceduresPower-up initialization Step Test Mode Auto Test ModeTest modes StepUnit start-up Gas valveMarking category of the gas section in different countries Gas burner dataStarting the unit in cooling mode Final installation checklistCheck torque of power cables contact Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerPotentiometer Setting Economizer Set-UpReliaTel Control Heating Operation Ignition ModuleLED status Final installation checklistDiagnostics Refrigerant charge End user routine maintenanceAir filters Hot water coil option Service technician maintenanceCondenser coil Troubleshooting System Status Checkout ProcedureService Failure System failureHeating Failure Cooling FailureResetting Cooling and Ignition Lockouts Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Fan Failure SwitchTemperature/resistance coefficient is negative Thermistor Resistance / Temperature ChartLiterature order number

RT-SVX19A-E4 specifications

The Trane RT-SVX19A-E4 is a groundbreaking rooftop unit designed for versatile commercial heating and cooling applications. This model stands out for its innovative technology and robust features, making it a preferred choice for many businesses seeking efficient climate control solutions.

One of the primary characteristics of the RT-SVX19A-E4 is its exceptional energy efficiency. It utilizes advanced variable-speed technology, allowing it to adjust the compressor's output based on real-time demand. This not only reduces energy consumption significantly but also provides more accurate temperature control, enhancing overall comfort within the space. The unit is designed with high-efficiency fan motors and optimized heat exchangers, which contribute to its impressive Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings.

The Trane RT-SVX19A-E4 also features a robust and durable design, built to withstand a variety of weather conditions. Its all-weather cabinet protects the internal components from environmental stresses, ensuring longevity and reliable performance. The unit is equipped with corrosion-resistant materials that enhance its durability, making it suitable for both coastal and urban environments.

Another notable feature is its advanced control system. The RT-SVX19A-E4 comes with Trane's IntelliPak controls, which provide users with precise monitoring and management capabilities. This smart control system enables remote access via internet connectivity, allowing facility managers to monitor performance, adjust settings, and diagnose issues in real-time, improving operational efficiency and reducing maintenance costs.

Additionally, the RT-SVX19A-E4 offers a range of customization options. It can be tailored to meet specific operational needs, with various configurations available for air flow, heating, and cooling needs. This flexibility ensures organizations can find a solution that best fits their requirements, whether it be for an office building, retail space, or industrial facility.

In conclusion, the Trane RT-SVX19A-E4 represents a significant advancement in rooftop HVAC technology, combining energy efficiency, durability, and intelligent controls. Its ability to adapt to varying demands, coupled with customizable options, makes it an excellent investment for businesses looking to enhance their indoor climate while minimizing energy expenses.