Trane RT-SVX19A-E4 manual Setting the economizer or 0-50% motorized hood option, ECA board LED

Page 47

Operation

Setting the economizer or 0-50% motorized hood (option)

The ECA board is mounted on the damper actuator. To access the ECA board on economizers:

Remove the access panel located on the economizer section.

The electrical power must be disconnected to set the minimum position and check the economizer.

Disconnect the power supply, put the thermostat fan selector to "ON" and the "HEAT/COOL" selector to "OFF". This puts the damper in the minimum ventilation position.

To set the required minimum ventilation air position, turn the dial on the ECA clockwise to increase ventilation, or anti- clockwise to decrease ventilation. The damper will open at this setting whenever the fan circuit is powered up.

When the arrow on the dial adjustment screw is pointing to 8 o'clock, the minimum position is roughly 0%. When the dial is pointing to 12 o'clock it is roughly 25%, and when the dial is pointing to 4 o'clock it is roughly 50%

To check the damper is functioning correctly, the ECA is equipped with an indicator light in the middle of the board. This light operates as in Table 35.

Table 35 - ECA board LED

OFF:

No Power or Failure

ON:

Normal, OK to Economize

 

 

Slow Flash:

Normal, Not OK to

 

 

Economize

 

 

Fast Flash:

Communications Failure

 

 

Pulse Flash:

Error Code:

 

 

 

1

Flash:

Actuator Fault

 

 

 

2

Flashes:

C02 Sensor

3

Flashes:

RA Humidity Sensor

 

 

 

4

Flashes

RATemp Sensor

 

 

 

5

Flashes:

OA Quality Sensor

 

 

 

6

Flashes:

OA Humidity Sensor

 

 

 

7

Flashes:

OATernp Sensor

 

 

 

8

Flashes:

MATemp Sensor

 

 

 

9

Flashes:

RAM Fault

 

 

10 Flashes:

ROM Fault

 

 

11 Flashes:

EEPROM Fault

 

 

 

While setting the minimum position the damper may move toward the new setting in several small steps. Once the damper has remained in the same position for 10 to

15 seconds it can be assumed it is in the new position.

RT-SVX19A-E4

47

Image 47
Contents Installation Operation Maintenance Reception in France only Safety recommendationsForeword ReceptionStorage WarrantyMaintenance contract RefrigerantContents Unit Options Unit handling Reception of unitsRooftop unit Unit size Roof curb Installation TKD-WKD-YKD accessoriesSling lengths and maximum unit weight Minimum clearances Minimum clearances mm Dimensions/Weights/ClearancesWeigths & center of gravity Figure Weights of Options & accessoriesUnit mounting on roof Installing the unitInstalling the unit on the ground Horizontal discharge units TKH,WKH,YKH Downflow discharge units TKD,WKD,YKD Using the rooftop curbConnection of duct network Condensate drain line connection Condensate drain pipingUnit Gas pipework installationGas leak check procedure Gas burner modelsFilter arrangement Filter installationFan Speed RPM Standard Drive Supply fan adjustmentMotor sheave / Fan speed Belt tensioning To increase airflowTo decrease airflow To increase belt tensionComponent air pressure drops YKD/YKH Pressure drop through accessoriesTKH TKD/TKH Pressure drop through accessoriesAirflow EU2/G2 EU4/G4 100% TKDWKH WKD/WKH Pressure drop through accessoriesFilter 100% WKDYK 155 External static pressure Supply fan performancesYK 175 External static pressure YK 250 External static pressure TK 200 External static pressure TK 175 External static pressure275 300 TK 250 External static pressureExternal Static Pressure Pa 275 300 WK 155 External static pressure TKD/TKH, WKD/WKH units YKD/YKH units Factory supplied Disconnect switch OptionPower wiring Electrical connectionWith Electric heat Electrical data YKD/YKH Unit WiringElectrical Characteristics Unit amps Scroll compressors Compressor electrical phasingOutdoor Fan 155 175 200 250 Compressor155 175 200 250 Indoor Fan 155 200 CompressorElectrical data TKD/TKH Supply fan motor Electrical data Combustion Blower Motorr Electrical data YKD/YKH Supply fan motorElectrical data WKD/WKH Supply fan motor Unit controlled by thermostat Control wiringZone sensor wire size and maximum length Maximum length Zone sensor wire sizeUnit controlled by Tracker supervisor Unit controlled by BASWall-mounted and duct-mounted CO2 sensors SpecificationsCO2 sensors CO2 sensor wire size Power supply requirementsWiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorMounting the duct-mounted CO2 sensor CO2 sensor maintenanceRemote potentiometer Remote potentiometer dimensionsDuct mounting of fire thermostat Fire thermostatSmoke detector High temperature safety thermostatRemote fault relay Clogged filter detectorCommunication Interfaces Water connection inlet/outlet 1 ¼ ISO R7 Hot water coil Installation and connectionHot water coil Down flow units onlySoft Starter Electric Heater25% manual fresh air hood 25% fresh air hoodDownflow version Barometric reliefOperation with a conventional thermostat OperationConventional thermostat Heat Pump Thermostat signals are as followsConventional thermostat Gas/ Electric, Electric Heat OK to Unoccupied modeCooling/Economizer Operation Cooling/Economizer Operation with Thermostat1,2ECA board LED Setting the economizer or 0-50% motorized hood optionMinimum fresh air adjustment Test mode procedure at the ReliaTel control board Test proceduresPower-up initialization Step Step Test ModeAuto Test Mode Test modesGas valve Unit start-upGas burner data Marking category of the gas section in different countriesOperating pressures Starting the unit in cooling modeFinal installation checklist Check torque of power cables contactEvaporator Fan Operation Cooling without an EconomizerCooling with an Economizer Low Ambient OperationIgnition Module Potentiometer SettingEconomizer Set-Up ReliaTel Control Heating OperationLED status Final installation checklistDiagnostics Refrigerant charge End user routine maintenanceAir filters Hot water coil option Service technician maintenanceCondenser coil System Status Checkout Procedure TroubleshootingCooling Failure Service FailureSystem failure Heating FailureFan Failure Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Clogged Filter SwitchThermistor Resistance / Temperature Chart Temperature/resistance coefficient is negativeLiterature order number

RT-SVX19A-E4 specifications

The Trane RT-SVX19A-E4 is a groundbreaking rooftop unit designed for versatile commercial heating and cooling applications. This model stands out for its innovative technology and robust features, making it a preferred choice for many businesses seeking efficient climate control solutions.

One of the primary characteristics of the RT-SVX19A-E4 is its exceptional energy efficiency. It utilizes advanced variable-speed technology, allowing it to adjust the compressor's output based on real-time demand. This not only reduces energy consumption significantly but also provides more accurate temperature control, enhancing overall comfort within the space. The unit is designed with high-efficiency fan motors and optimized heat exchangers, which contribute to its impressive Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings.

The Trane RT-SVX19A-E4 also features a robust and durable design, built to withstand a variety of weather conditions. Its all-weather cabinet protects the internal components from environmental stresses, ensuring longevity and reliable performance. The unit is equipped with corrosion-resistant materials that enhance its durability, making it suitable for both coastal and urban environments.

Another notable feature is its advanced control system. The RT-SVX19A-E4 comes with Trane's IntelliPak controls, which provide users with precise monitoring and management capabilities. This smart control system enables remote access via internet connectivity, allowing facility managers to monitor performance, adjust settings, and diagnose issues in real-time, improving operational efficiency and reducing maintenance costs.

Additionally, the RT-SVX19A-E4 offers a range of customization options. It can be tailored to meet specific operational needs, with various configurations available for air flow, heating, and cooling needs. This flexibility ensures organizations can find a solution that best fits their requirements, whether it be for an office building, retail space, or industrial facility.

In conclusion, the Trane RT-SVX19A-E4 represents a significant advancement in rooftop HVAC technology, combining energy efficiency, durability, and intelligent controls. Its ability to adapt to varying demands, coupled with customizable options, makes it an excellent investment for businesses looking to enhance their indoor climate while minimizing energy expenses.