Carrier 33CS400-01 owner manual Index, See Display

Page 77

SECTION 20

Index

see Display

12.2

Locked Indication

see Keypad Lockout

M

Manual

changeover, 3.3 cool, 3.2 heat, 3.2

MISC

jumper, see Jumpers output, 16.2-16.3

Mode icon, 1.2, 2.3

Multi-stage

Operation, 12.4

N

Non-Programmable

Off Mode, 1.2, 2.3

Outdoor,

see Outside

Outside

button, see Buttons icon, 2.3

sensor, 2.3, 4.2, 12.1- 12.2, 13.2, 17.3

viewing temperature, 2.3, 4.2, 13.2, 17.3

Override

button, see Buttons icon, 2.3

timer, 5.1 viewing run-time,

10.2, 19.1

P

Pan, Service

see Dry Contact

I

IR Receiver, 18.1

IR Remote Control,

18.1

J

Jumpers

DEHUM, 16.3

ECON, 16.3

ELEC, 11.3 electric heat, 11.3 gas electric, 11.2 heat pump, 11.2, 19.1 HUM, 8.2, 16.2-16.3 reversing valve, 11.2,

19.1

Y2, 16.2-16.3

K

Keypad Lockout, 2.4,

7.3

L

LCD

Thermostat, 3.3-3.4

Polarity, see Dry Contact

Normally

 

R

 

 

 

Open/Closed,

 

 

dry contact, 14.2

 

 

dehum terminal,

 

 

9.5

 

Random Start, 14.5

 

O

 

 

 

 

 

Red Indicator, 2.2

 

 

Remote Sensor

 

 

calibrate, 17.3

O Reversing Valve,

control to, 13.3-

 

 

 

Page 20.3

Image 77
Contents OWNER’S 4Z95 How to Use This Manual Glossary of Terms Page Table of Contents Contents Heating Only Selecting the Heat or Cool ModeHeating or Cooling OffAdjusting the setpoints Selecting Your Desired TemperatureContents Button Front PanelCool Display FeaturesService Filter icon Section Humidify/DeHumidify icon Sections Contents Press the Mode button repeatedly To enter Setup screensUntil this setup screen appears Manual or Auto-Changeover ThermostatCooling Only Operating Mode when the Thermostat is Configured to beHeating or Cooling Selecting Your Desired Temperature adjusting setpoints Viewing the Outside Temperature Viewing the Indoor Humidity Press the Outside button to view the Outside temperature Viewing the Outside TemperatureTo view the indoor humidity Viewing the Indoor HumidityOverriding the Normal Operation Override OperationUsing the Fan Button Smart Fan Operation Setting the Fan-Off TimeSmart Fan Operation Using the Fan ButtonSetting the Fan-Off Time Delay Level Programming a SecurityAfter a button press Appear on the display, then release the buttons Locking/Unlocking the KeypadProgramming a Security Level Setpoint Installing the HumidityBack of 33CS400-01 Installing the Humidity ModuleMISC3 outputs, please see Section Setting a Thermostat Jumper for Humidity OperationPress the Humidity Adjusting the Humidification SetpointTerminal Using Your Air Conditioner To Dehumidify Using the DehumSetting a Thermostat Jumper for Dehumidification Operation Press the Mode button once Adjusting the Dehumidification SetpointAppears only if is set to on Using Your Air Conditioner to DehumidifyUsing the Dehum Terminal Run-Time 10.4 Run-Time 10.2Run-Time 10.3 Viewing the Override Operation Run-Time Viewing the Humidification Run-Time Viewing the UV Light Run-Time Electric Heat and Heat Pump Operation OFF = Gas Electric Operation Viewing the Heat Pump Reversing Valve Jumper SettingsViewing the Electric Heat Jumper Setting 73 74HEAT Using Emergency Heat12.3 Adjusting the Heat/Cool Differential Adjusting the Cycles Per Hour Adjusting the Deadband Adjust the deadband For the 1st stage Select On or Off On 2nd stage will Selecting 2nd Stage Turn Off Temperature13.2 Installing the RemoteControlling or Reading Remote Temperature RS1...13.3 Installing the Remote Sensors Controlling or Reading Remote Temperature RS1 Dry Contact Programming 14.3 Dry Contact Operation 14.214.4 14.5Appears only if is YES Dry Contact OperationDry Contact Programming Service PanUnoccupied Random Start Operation 15.2 Setting and Resetting Service Filter Fan Run-TimeTo enter this setup screen Press the Reset Filter buttonHow to Set and Reset the UV Light Run-Time Alert Until this setup screen appears How to Set and Reset the Humidifier Run-Time Alert16.3 Configuring the Jumpers 16.2MISC3 MISC2 MISC1 Configuring the JumpersHUM Jumper Setting Explanation of Jumper SettingsY2 Jumper Setting Factory Defaults, Calibration, and Sensors Factory Default Settings for default values see Resetting the Thermostat toI200 Pm Calibrating the Temperature and Humidity SensorsAccessories Advanced Setup Table Index Electric Heating See Display IndexSetpoint Warranty