Bryant T2-PAC installation instructions Check Thermostat Operation

Page 20

Step 4 — Check Thermostat Operation

The Legacy Series thermostats have a built-in installer test capability. Use it to check thermostat and equipment operation without delays or setpoint adjustments to force heating or cooling.

To enter the Installer Test mode, use the same process as is used to enter Installer Configuration, only hold the FAN key longer. More specifically, press and hold the FAN for about 15 seconds until the display reads In on the left and St on the right for the programmable model, or InS in the smaller display for the non-programmable model. The MODE will be OFF. The MODE key (upper left) can now be used to select heat, cool, or emergency heat, if this is a HP thermostat. Selecting one of the available modes will immediately command the equipment to turn on in that mode. It will run for 3 minutes and then return the mode to off. With HP thermostats (having 2 stages of heating), the test will run for 3 minutes on each stage. If the thermostat is programmable, the clock display counts down from 180 seconds while each stage operates. Changing the mode to OFF will terminate any running test immediately.

During any test, the display icons will be displayed the same as for normal operation of that stage, as follows:

SELECTED MODE

DISPLAY ICONS

 

 

off

off

 

 

cool

cool on

 

 

heat

heat on, aux heat on

 

 

Em Heat

aux heat on

 

 

To terminate the Installer Test mode press the DONE or FAN button. If the thermostat is left in Installer Test mode, it will revert back to normal operation after 15 minutes.

18

Image 20
Contents Legacy Series Programmable Thermostat Designed and Assembled in the U.S.APage Table of Contents Safety Considerations Introduction Models Installation ConsiderationsPower Installation Thermostat LocationEnvironmental Hazard Backplate Mounting Secure Wires to Terminal Strip Terminal Designations Set Thermostat Configuration Configuration Options Summary Option 01 Equipment type Configuration Options SelectionTo Enter the Configuration Mode Option 03 Fahrenheit/Centigrade Option 04 Fan G on with W outputOption 07 Zoning Option 10 Reversing valveOption 12 Smart Recovery programmable model only Option 11 Minimum Deadband Between Heating And Cooling Option 13 Room Air Temperature Offset Option 15 Auto Changeover Availability Option 16 Maximum Cycles Per Hour Option 17 Minimum Time Between Equipment StagesOption 18 Backlight Configuration Option 21 Keypad LockoutOption 27 Maximum Heating Setpoint Option 99 Reset to Factory DefaultsOption 26 Minimum Cooling Setpoint Check Thermostat Operation Checklist Display Lighting Features and AccessoriesBatteries Door Switch Mounting OptionsWiring TimersOperational and Connection Information Rc/Rh ConnectionsError Codes Minimum On TimerCycle Timer Auto Changeover TimerOutputs Cool Heat EM HeatWiring Diagrams Single Speed A/C Thermostat Typical InstallationWiring Diagrams Single-stage Furnace with Air Conditioner and Split Power Thermostat Heat Stage 3 furnace Heat/Cool Stage Fan 24VAC Hot Heating FV/FK Fan Coil w/2-Stage Air Conditioner FV/FK Fan Coil w/2-Stage Heat Pump Thermostat Configuration Record Mode SettingsConfiguration Options Page Page Page Page IIT2---PAC---05